Section 4: Programming Options
Ethernet Test Transmission Time
Enter a 4-digit number (0000-2359) using the 24-hour clock
format (HHMM) to set the time of day an Ethernet test trans-
mission is sent. Programming a value of 9999 disables the
test transmission time.
Note:
The internal date and time is automatically pro-
grammed when the unit communicates with the primary
receiver.
Default:
9999
Valid range:
0000 to 2359, 9999 to disable
Ethernet Test Transmission Cycle
This option is used to program how often, in days, Ethernet
test transmissions are sent. Once the initial test transmission
is sent, all future test transmissions are offset by the pro-
grammed number of days.
Default:
30 days. (Note: Test transmission shall be 24 hours for ULC
and 7 days for UL.)
Valid
range:
000 to 255 Days
Cellular Test Transmission Time
Enter a 4-digit number (0000-2359) using the 24-hour clock
format (HHMM) to set the time of day a cellular test trans-
mission is sent. Programming a value of 9999 disables the
test transmission time.
Note:
The internal date and time will automatically be pro-
grammed when the unit communicates with the primary
receiver.
Default:
9999
Valid range:
0000 to 2359, 9999 to disable
Cellular Test Transmission Cycle
This option is used to program how often, in days, cellular
test transmissions are sent. Once the initial test transmission
is sent, all future test transmissions are offset by the pro-
grammed number of days.
Default:
30 days. (Note: When only cellular is used, test transmission
shall be 24 hours for ULC and 7 days for UL.)
Valid
range:
000 to 255 Days
Commercial Supervision
When this option is enabled, swap detection is provided on
the supervisory packet. When disabled, only supervision of
the communicator path to the receiver is provided.
Default:
Enabled
Valid range:
Enabled/Disabled
Ethernet Supervision Interval (Heartbeat)
This option is used to set the frequency (in seconds) when
supervisory heartbeats are sent to the Ethernet receiver. If
the programmed value is 000 seconds, supervision is dis-
abled.
Note:
Commercial Supervision must be enabled in order to
test the communications path.
Default:
000
Valid range:
001 to 255 Seconds, 000 to Disable
Cellular Supervision Interval ( Heartbeat)
This option is used to set the frequency (in seconds) when
supervisory heartbeats are sent to the cellular receiver. If the
programmed value is 000 seconds, supervision is disabled.
Note:
Commercial Supervision must be enabled in order to
test the communications path.
Default:
000
Valid range:
001 to 255 Seconds, 000 to Disable
CMS Event Heartbeat Interval
This option is used to program the periodic heartbeat inter-
val between the alarm panel and the cellular communicator.
The heartbeat is used to monitor for image/audio file
requests.
Default:
15 Seconds, 0 to disable
Valid range:
000 to 255 Seconds
Communication Trouble Delay Time
This option is used to program the amount of time before the
following troubles are transmitted to the central monitoring
station:
l
Ethernet trouble
l
Cellular trouble
l
Supervision trouble
l
WIFI trouble
Default:
000
Valid range:
000 to 254 seconds, 000=Instant, 255=Disabled
- 27 -