background image

WLS912L/WLS922L Wireless Glassbreak Detector

INSTALLATION INSTRUCTIONS

Available Models: WLS912L-433, WLS922L-433

The WLS912L and WLS922L are battery-operated glassbreak sensors,

designed to detect the sound produced by the shattering of framed

glass. Equipped with an RF transmitter, the WLS912L/WLS922L estab-

lishes a supervised, one–way communications link with the alarm con-

trol panel. The WLS912L/WLS922L uses Dynamic Signal Processing*

to provide accurate detection of plate, laminated, wired and tempered

glass types, while rejecting common false alarm sounds.

*Protected under US Patent 5,675,320

Specifications

• Operating Voltage: 3.0V

• Batteries: Two 3V lithium

• Low Battery level: 2.65V

• Battery capacity: 1500mAh

• Operating Temperature: 0°C - 50°C (32°F - 122°F)

• Dimensions: 135 x 60 x 35mm

• Operating Humidity: 5% – 95% RH, non-condensing

• Weight: 130g

• Input rating: 3V

DC

 (max) / 0.2 mA

Maximum Detection Range

Compatible panels and receivers: RF5132-433, RF4164-433,

RFK55XX-433, RF5108, TR5164-433, SCW9045/47-433, SCW9055/

SCW9057-433, SCW9067-433, PC9155-433.

Battery Guidelines and Installation

• Use fresh batteries. Most batteries have a “best before” date printed on

their packaging or on the batteries themselves. Buy batteries that have

a “best before” date of two years or more from your purchase date

• When disposing of used batteries, follow the instructions and precau-

tions printed on the batteries. Many cities and communities have

collection sites or services for used household batteries. Contact your

municipal offices for information on the disposal of used batteries

• Do not mix old and new batteries

• Dispose of any batteries promptly, keep away from children

NOTE: Use only Energizer Lithium EL123AP, Tekcell CR123A, Panasonic

CR123A or Duracell Ultra 123 lithium battery. Use of any other battery may

present a risk of fire or explosion.

CAUTION: The cell used in this device may cause a fire or chemical burn

hazard if mistreated. Do not recharge, disassemble, heat above 100°C

(212°F) or incinerate.

Models WLS912L-433/WLS422L-433 is UL listed for Residential Burglary

and Commercial Burglary applications in accordance withe the follow-

ing standards: UL639, UL1023, UL1610.

To install batteries:

1. Remove the de

t

ector from its mounting plate:

 

If unmounted, hold the

detector by its sides and push down on the top end of the mounting

plate, as shown in the diagram. If mounted, press the detector in the

direction shown in the diagram.

2. Install the batteries positive (+) side first, with the correct polarity, as

shown in the diagram. 

Setting the Dip Switches

The detector has user-selectable dip switch settings as shown.

Dip Switch 1– Not Used

Dip Switch 2– Level 1/Level 2 Detection

This is a sensitivity selection dip switch which may be used to optimize

false alarm immunity for certain acoustic environments. 

The detector is factory set for Level 1 detec-

tion (Dip Switch 2 = OFF). This is the high-

est sensitivity setting for the detector, and

will be suitable for most applications.

For smaller rooms with a significant number

of sound-reflective surfaces (such as bath-

rooms, kitchens, entrances, etc.), Level 2

detection (Dip Switch 2=ON) provides

reduced sensitivity which may be more appropriate.

Selecting a Mounting Location

The detector is unidirectional and picks up sound aimed directly into the

microphone and center of the detector. Coverage is measured from the

center of the detector to the point on the glass farthest from the detector.

Guidelines for optimizing detection and avoiding false alarms

• For optimum protection, the detector should have a direct line of sight

to the protected glass.

• Window coverings will absorb sound from the shattering glass. In these

cases, mount the detector as close as possible to the protected glass,

either on an adjacent wall, the ceiling, or behind the window covering if

possible. 

• The detector should be mounted at least 1.8m (6 feet) off the ground.

• Do not mount the detector on the same wall as the protected glass.

• Avoid installation near noise sources, such as speakers or other

objects which produce sounds continuously.

• Do not install the detector beyond the maximum recommended range,

even if the AFT

-

100 simulator shows additional range - future changes

in room acoustics could reduce the range.

• Application on 24 hour loops should be avoided unless the location is

unoccupied.

• Test false alarm immunity by generating any sounds in the room which

could occur when the alarm system is armed.

NOTE: Test the detector thoroughly for proper placement using the AFT-

100 Glassbreak Simulator. Other simulators may trip the unit, but will not

provide accurate test results.

Testing the detector

Perform the following

tests to ensure that the

detector is mounted in

the best possible loca-

tion.

Detection Test

1. Place the detector in

test mode by

momentarily pressing

down on the tab on the base plate, as shown. The LED blinks periodi-

cally to indicate that it is operating in test mode. You can end the test

mode by momentarily pressing the tab on the base plate. Test mode will

end automatically after 10 minutes.

2. Use double-sided tape to temporarily mount the detector in the selected

location

NOTE: The detector will not respond to the glassbreak simulator unless

the test mode operation has been enabled.

3. At the window to be protected, test the detector using the AFT-100

Glassbreak Simulator. The AFT-100 Glassbreak Simulator gener-

ates plate or tempered glass sounds. Use the plate glass setting if

you are unsure of the glass type. Observe the following when testing

the detector:

• If the WLS912L/WLS922L detects the sound generated by the AFT-

100 three times in a row, the detector is in a good location. If the

detector does not respond each time, relocate the detector and

repeat the test.

• If the window is covered by drapes or blinds, place the AFT-100 tes-

ter behind the closed window coverings and activate it. If the drapes

prevent reliable detection, we suggest that the detector be mounted

behind the drapes either on an adjacent wall or on the ceiling.

• If there are multiple windows, or one large window, activate the tes-

ter at the furthest point on the glass from the detector.

Glass Type Thickness Minimum Glass 

Size (L X W)

Level 1 

Setting

Level 2 

Setting

Plate/

Tempered

1/8" – 1/4"

3 – 6 mm

12" × 12"

30cm ×  30cm

20ft

6m

10ft

3m

Wired/

Laminated

1/4"

6mm

18" × 18"

46cm × 46cm

20ft

6m

DO NOT 

USE

29 0 0 5 7 2 3R0 1 1

Содержание WLS912L-433

Страница 1: ...trances etc Level 2 detection Dip Switch 2 ON provides reduced sensitivity which may be more appropriate Selecting a Mounting Location The detector is unidirectional and picks up sound aimed directly into the microphone and center of the detector Coverage is measured from the center of the detector to the point on the glass farthest from the detector Guidelines for optimizing detection and avoidin...

Страница 2: ...3 sont homologués UL pour les applications cambriolage résidentielles et commerciales conformément aux normes suivantes UL639 UL1023 UL1610 Pour installer les piles 1 Retirez le détecteur de sa plaque de montage S il n est pas monté tenez le détecteur sur les côtés et poussez le haut de la plaque de mon tage vers le bas comme le montre le schéma à droite 2 Installez les piles polarité positive d a...

Страница 3: ...drio operado por batería proyectado para detectar el sonido producido por los astillados de un vidrio quebrado Equipado con un transmisor de RF el sensor establece un link de comunicación supervisado unidireccional con el controlador del sistema Este sensor utiliza la tecnología Dynamic Signal Processing Procesamiento Digital de Señal para aplicar la detección necesaria de los tipos de vidrio lami...

Страница 4: ...tor está instalado en un lugar adecuado Si el detector no responde a cada intento reposicione el detector y repita la prueba Si las ventanas en cuestión estuvieren cubiertas por cortinas o persi anas posicione el probador AFT 100 atrás de estos ítems con la ventana cerrada y actívelo Si las cortinas persianas impidan una detección confiable sugerimos que el detector sea montado atrás de las cortin...

Страница 5: ...ado NOTA Teste o detector minuciosamente para descobrir o posiciona mentoadequadousandoosimuladordequebradevidroAFT 100 Outros simuladores podem acionar o dispositivo mas não fornecerão resulta dos de teste precisos Teste do detector Execute os testes a seguir com cada detector WLS912L WLS922L para verificar se ele está montado no melhor local possível Teste de detecção 1 Coloque o detector no mod...

Страница 6: ...ité aux modalités de ce CLU b Séparation des Composants Le PRODUIT LOGICIEL est fourni sous licence en tant que produit unique Ses parties composantes ne peuvent pas être séparées pour être utilisée sur plus d un MATÉRIEL c PRODUITINTÉGRÉunique SivousavecacquisceLOGICIELavecduMATÉRIEL lePRODUITLOG ICIEL est autorisé à être utilisé avec le MA TÉRIEL en tant que produit intégré unique Dans ce cas le...

Страница 7: ... outros ou colocá lo num servidor ou página Web e Transferência do Programa V Exa poderá transferir todos os seus direitos abrangidos por este CLUF EULA apenas como parte de uma venda ou transferência permanente do HARDWARE desde que V Exa não fique com quaisquer cópias transfira todo o PROGRAMA incluindo todos os componentes meios e materiais impressos quaisquer upgrades e este CLUF EULA desde qu...

Страница 8: ...euventcauserunmauvaisfonctionnementdel appareil Simplified EU Declaration of Conformity Hereby Tyco Safety Products Canada Ltd declares that this radio equipment WLS922L 433 is in compliance with Directive 2014 53 EU Thefulltextof theEU declarationof conformityisavailableat the following internet address http dsc com index php n library o view_documents id 1 Frequency Band s g1 433 04MHz 434 79MHz...

Отзывы: