P r o g r a m m i n g S e c t i o n s :
5 . 6 C o m m u n i c a t o r P r o g r a m m i n g P W S S e c t 6
33
Special Closing:
a
Special Closing
reporting code will be
transmitted if the partition(s) is armed using any of the
following methods:
• Quick Arm
• Auto-arm
• Arming via the DLS Software
• Arming via Keyswitch
• Away Function Key Arming
• Arming with the Maintenance Code.
• Stay Function Key arming
Late to Close:
a
Late to Close
reporting code will be trans-
mitted if a partition isn't armed before the auto-arm start
time when the late to close option, (Section 017, option 5)
is enabled.
[342]-[343] - Opening (Disarming) Reporting
Codes Access Codes 1-32
The panel will transmit an
Opening
reporting code
to indi-
cate partition(s) is disarmed. A different reporting code
can be transmitted for each user code, partition master
code and system master code to identify who armed the
partition(s).
[344] - Miscellaneous Opening (Disarming)
Reporting Codes
Opening by Duress Code 33/34:
This reporting code will be
transmitted in addition to the duress reporting code if a
partition(s) is disarmed using a Duress Code
Opening by Master or Supervisory Code:
The panel will
transmit this reporting code to indicate a partition(s) is
armed. A different reporting code can be transmitted for
each User Code, Supervisory Code and System Master
Code to identify who armed the partition(s).
Auto Arm Cancellation:
This reporting code is transmitted
when the Auto Arming sequence is canceled or Postponed
Special Opening:
A
Special Opening
reporting code will
be transmitted if the partition(s) is disarmed using any of
the following methods:
• Disarming using the Maintenance Code
• Disarming via the DLS Software
• Disarming via keyswitch
[345] - Maintenance Alarm Reporting Codes
Battery Trouble Alarm:
the panel will transmit a
Battery
Trouble Alarm
reporting code when the backup battery
drops below 11.5 V
DC
.
AC Failure Trouble Alarm:
the panel will transmit an
AC
Failure Trouble Alarm
reporting code when the AC to
the panel is lost and the AC Failure Communication
Delay timer expires.
Bell Circuit Trouble Alarm:
a
Bell Circuit Trouble Alarm
reporting code will be transmitted immediately if an open
condition is measured on the Bell Output of the main
panel.
Fire Trouble Alarm:
a
Fire Trouble Alarm
reporting code
will be transmitted immediately when an open condition
is measured on any fire zone.
Auxiliary Power Supply Trouble Alarm:
the
Auxiliary
Power Supply Trouble Alarm
reporting code will be
transmitted if the AUX output is shorted.
TLM Trouble:
a
TLM Trouble
reporting code can only be
transmitted if a LINKS1000/2X50 Communicator is being
used (see Section 5.26 LINKS1000 Cellular Communica-
tor). The panel will only transmit the signal after the time
programmed for the TLM Trouble Delay.
General System Trouble:
a
General System Trouble
reporting code will be transmitted if the panel detects any
of the following:
• AC Power Failure
• Low Battery
• AUX Output Trouble
• Output #1 on the PC5200/PC5204 Power Supply/Out-
put Module.
General System Supervisory Trouble:
a
General System
Supervisory Trouble
reporting code will be transmitted if
any module goes missing from the Keybus. If the module
is a zone expander the panel will also transmit the
Zone
Expander Supervisory Alarm Trouble
reporting code.
[346] - Maintenance Restoral Reporting Codes
Battery Trouble Restoral
: the
Battery Trouble Restora
l
reporting code will not be transmitted until the battery
has been charged over 12.5 V
DC
.
AC Failure Trouble Restoral
: the
AC Failure Trouble
Restoral
reporting code will be transmitted once AC
power has been restored for the amount of time pro-
grammed for AC Failure Communication delays.
Bell Circuit Trouble Restoral
: the
Bell Circuit Trouble
Restoral
reporting code will be transmitted as soon as the
open condition on the bell output is corrected.
Fire Trouble Restoral
: the
Fire Trouble Restoral
report-
ing code will be transmitted when the correct resistance
value is measured on any Fire type zone.
Auxiliary Power Supply Trouble Restoral
: the panel
constantly checks the AUX output, when the excessive
current draw is removed the panel will reset the output
and transmit an
Auxiliary Power Supply Trouble Resto-
ral
reporting code.
TLM Restoral:
the TLM Restoral reporting code will be
transmitted immediately after the Trouble is restored.
General System Trouble Restoral
: a General System
Trouble Restoral
reporting code will be transmitted when
the panel detects none of the following:
• AC Power Failure
• Low Battery
• AUX Output Trouble
•Output #1 on the PC5200 /
PC5204 power Supply/Output Module after a Trouble
was reported.
General System Supervisory Restoral
: the General Sys-
tem Trouble Restoral reporting code will be transmitted
when the control panel detects all modules enrolled on
the keybus
[347] - Miscellaneous Maintenance Reporting Codes
Telephone Number 1 (2) FTC Restore:
if the panel fails to
transmit information to the central station it will display a
failure to communicate Trouble condition. The panel will
transmit a
Phone Number 1 Failure
to Communicate
reporting code or a
Phone Number 2 Failure to Communi-
cate
reporting code the next time it calls the central sta-
tion. The panel will transmit the old events, followed by
the failure to communicate, followed by the new events.
Event Buffer 75% Full:
If the event buffer is uploaded on
a regular basis an
Event Buffer 75% Full
reporting code
can be transmitted to warn that the Buffer is almost full.
DLS Lead In:
The
DLS Lead In
reporting code will only
be transmitted if the DLS Call Back feature is being used
(see Section 5.8 "Downloading"). Before the panel calls the
computer back it will call the central station and transmit
the reporting code to indicate a download session is
about to begin.
DLS Lead Out:
After a downloading session is attempted
and/or completed, the panel will transmit a
DLS Lead
Out
reporting code.
Zone Fault Alarm:
The
Zone Fault Alarm
reporting code
will be transmitted when there is a short detected on any
DEOL zone and/or a loss of Supervisory on a wireless
zone.
Zone Fault Restoral:
The
Zone Fault Restoral
reporting
code will be transmitted when the fault condition on the
zone is corrected.