background image

P r o g r a m m i n g   S e c t i o n s :  

5 . 3   B a s i c   P r o g r a m m i n g   P W S   S e c t   3

21

[005] - System Times

This section has 9 sub-sections, 1 for each of the 8 parti-
tions, and 1 for the Bell time-out. A 2-digit entry is
required to access these sub-sections.

NOTE: 

Entry of 000 in these sections will result in a 255-

second time.

Sub-Sections 1-8 each require three 3-digit entries.

[01] - [08]

   Entry Delay 1, Entry Delay 2, and Exit Delay

per partition.

Entry Delay 1:

 030-255 Seconds

This value determines the Entry delay time for Delay 1
type zones. The default Entry Delay 1 time is 30 seconds.

Entry Delay 2:

 030-255 Seconds

This value determines the Entry delay time for Delay 2
type zones. The default Entry Delay 2 time is 30 seconds.

Exit Delay:

 045-255 Seconds

This value determines the Exit delay time when arming
the system. The default Exit Delay time is 60 seconds.

NOTE: 

The Exit Delay must not exceed 255 seconds.

The minimum possible entry is 45 seconds.

NOTE: 

If the Exit Delay is silent (Section 014, Option 6

or Stay Function Key Arming) the Exit Delay will be
twice the programmed value (090-510 seconds).

[09] Bell Time-out:

 001-255 Minutes

The Bell Time-out for all 8 partitions will be the same.

The siren will silence after the number of minutes pro-
grammed for the 

Bell Time-out 

value has passed. The

default Bell Time-out is 4 minutes
The panel supervises the Bell output. If an open condition
is detected, the panel will immediately indicate a Trouble
condition by beeping the keypad twice every 10 seconds
to alert the owner to the problem. The panel can send a

Bell Circuit Trouble 

and 

Trouble Restoral 

reporting

codes to indicate the situation (

see section 5.6, ‘Commu-

nicator Programming’ PWS Sect 6

).

If the 

Temporal Three Fire Signal 

option is enabled, all

Fire signals will follow the Temporal Three Pattern as
described in NFPA 72. If turned OFF all Fire signals will
sound a one second on, one second off cadence.
If 

Fire Bell Continuous 

is enabled, the alarm output will

sound until a code is entered. If disabled, the alarm will
sound until a code is entered or the bell time-out has
expired.

NOTE: 

Only fire zones will follow the Temporal Three

Fire Signal.

Bell Time-out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section [005]
Bell Circuit Trouble Reporting Code . . . . . . . . . . . . . . Section [349]
Bell Circuit Trouble Restoral Reporting Code. . . . . . . . Section [350]
Temporal Three Fire Signal 
Enable/Disable . . . . . . . . . . . . . . . . . . . . . Section [013], Option [8]
Fire Bell Continuous . . . . . . . . . . . . . . . . . Section [014], Option [8]

25

Interior Delay Zone

The Interior Delay Zone is normally used with motion detectors and has a standard Exit Delay time. If the panel is 
armed, and a Delay zone is violated during the Exit Delay (or the Away function key is used), the Interior Delay Zone 
will be active at the end of the Exit Delay. This zone will cause an instant alarm when violated. This zone type will fol-
low the Entry Delay time provided that a Delay zone is violated first. If the panel is armed, and a Delay zone is NOT 
violated during the Exit Delay (or the Stay function key is used, or [*][9] armed), a violation of this zone type will ini-
tiate Entry Delay 1.

26

24-hr Non-Alarm

These zones are active at all times but do not cause an alarm, and do not show up in alarm memory. Zone Attributes 
such as Zone Bypassing and Door Chime affect the functionality of this zone. A 24-hr Non-alarm zone may be used 
for Zone Follower automation applications. 

NOTE: This zone type will be active in Walk Test. Tampers and Faults. Zones programmed as 24-hr Non-
alarm type will not cause alarms.
NOTE:  Alarms on this zone will not initiate Downlook.

27

Delayed 24-hr Water-
flow

These zones will follow the waterflow Delay Timer. When a delayed waterflow zone is violated, the waterflow timer 
will start, (any subsequent delayed waterflow zones that become active do not reset or abort this timer). If there are 
still delayed waterflow zones open when the waterflow timer expires, the panel will go into alarm and communicate 
the event(s) regardless of the armed state. 

28

Instant 24-hr Water-
flow

A waterflow alarm is a Fire alarm. The Fire related bells and Aux functions are activated. This Zone type functions 
similar to Type 27 (Delayed 24-hr waterflow), but does not follow the Waterflow Delay Timer. When this zone is vio-
lated, it will immediately go into alarm.  This zone type always uses a single EOL configuration.

29

Auto Verified Fire Zone 

This zone ensures that an alarm condition persists by resetting a tripped sensor in a fire zone and confirming that the 
sensor has remained tripped or is waiting for the sensor to re-trip within a set period of time (e.g., cycling power to 
a smoke detector to ensure the condition persists when power is restored). The alarm sequence for the zone is indi-
cated below:
    Step #1                       Duration 20 Seconds                    Sensor Reset
    Step #2                       Duration 10 Seconds                    Settle Time (Power-up)
    Step #3                       Duration 60 Seconds                    Check for Verified Alarm

NOTE: If another Fire device detects Fire during the Auto Verify or Delay sequence, the sequence is  termi-
nated and alarms are immediately generated for all pending zones. This applies to all other Fire zones on 
the system regardless of the partition assignments (i.e., two fire alarms anywhere on the system will can-
cel all pending fire delays and create immediate alarms).

30

Fire Supervisory Zone

When this zone is violated, the system turns on the keypad buzzer, and communicates the supervisory alarm condi-
tion to the monitoring station. The buzzer will not follow the Bell Time-out. To silence the buzzer, a valid access code 
must be entered.

NOTE: The fire supervisory alarm is not affected by the waterflow silence inhibit option described in 
[018], Option 4, Pg 32

31

Day Zone 

A zone programmed as this type has different characteristics in the armed and disarmed state. In the disarmed state, 
violating this zone will sound the keypad buzzer but will not log or report the event. In the armed state, violating this 
zone will sound the bell and communicate the event.

87

Delayed 24-hr Fire 
(Wireless)

Used only with wireless smoke detectors. Functions same as Zone Type [07].

88

Standard 24-hr Fire 
(Wireless) 

Used only with wireless smoke detectors. Functions same as Zone Type [08].

[001]-[004]  ZONE DEFINITIONS

Option

Zone Type

Description

Содержание PC5020 Power864

Страница 1: ...ns information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be carefully read PC5O2O PC5O2OCF Version 3 2 DLS 3 v1 3 and higher Now classified in accordance with ANSI SIA CP 01 2000 SIA FAR ...

Страница 2: ...he system may fail to func tion as intended due to the failure of a component Inadequate Testing Most problems that would prevent an alarm system from operating as intended can be found by regular test ing and maintenance The complete system should be tested weekly and immediately after a break in an attempted break in a fire a storm an earthquake an accident or any kind of construction activity i...

Страница 3: ... how a zone is defined according to the SIA specification for Contact ID If Automatic Contact ID is enabled see Appendix A for reporting codes that will be used for each zone type Keypad Buzzer When enabled and the system or Partition is in alarm all assigned keypad buzzers will follow the bell output When disabled the keypad buzzers will only sound for buzzer type alarms This option is off at def...

Страница 4: ... 005 5 3 System Times Access to Entry Delays and Exit Delay for each partition and Bell Time Out for the system 009 011 5 3 Programmable Outputs Access to PGM Output programming for the main board PC5208 and PC5204 modules Output Attributes in Section in Sections 501 514 Partition Assignments in Section 551 564 014 Option 6 5 3 Audible Exit Beeps Enables beeps from the keypad for the duration of E...

Страница 5: ...rd 20 5 2 Keypad Programming 20 5 3 Basic Programming 20 5 4 Advanced Programming 29 5 5 Partition Zone Programming 30 5 6 Communicator Programming 31 5 7 Downloading Options 40 5 8 Programmable Output Programming 41 5 9 International Programming 42 5 10 Module Programming 43 5 11 Special Installer Instructions 44 Section 6 Central Remote Station Fire Installation Instructions 46 6 1 Introduction ...

Страница 6: ...iv PC5020 UL Wiring Diagram NOTE For ULC installations please refer to the ULC Wiring Diagram part 18006238 and the ULC Installation Information Sheet part 29002157 ...

Страница 7: ... 32 user 1 system master 2 supervisor codes 2 duress 1 maintenance and 1 installer code Expandable to 64 zones Keypads with zone inputs available PC5508Z PC5516Z PC5532Z LCD5500Z and LCD5501Z Hardwired expansion available using the PC5108 8 zone expansion module the PC5100 addressable 32 zone expansion module and the PC5700 5720 fire module Wireless expansion available using the PC5132 wire less 3...

Страница 8: ... zones PC5508 Z PC5516 Z PC5532 Z v2 00 and lower LCD5500 Z versions 2 x and lower LCD5501Z versions 1 x and lower PC5100 2 Wire Addressable Device Interface Module The PC5100 module is used to connect 2 wire addressable devices to the system Up to 32 2 wire addressable devices can be added to the system NOTE PC5100 v1 0 and lower modules can only sup port the first 32 zones on the PC5020 system P...

Страница 9: ...an be used for ULC Listed non residential fire applications The PC5720 can also be used as an interface between the control panel and either a serial printer or a DVACS communications network NOTE The PC5700 v1 x and PC5720 v1 x enroll as two expander modules and use two supervisory slots NOTE Do not mix PC5700 v1 x and PC5720 v1 x and lower modules with PC5108 v2 0 and higher modules on the same ...

Страница 10: ...an audio station next to a keypad Dimensions 208mm x 115mm x 18mm 8 2 x 4 5 x 0 25 approxi mately PC55BP2 Backplate Use this backplate when mounting an audio station next to a keypad In addition the backplate will allow you to mount a PC5108 zone expander module or the PC5208 8 low current output module Dimensions 208mm x 115mm x 18mm 8 2 x 4 5 x 0 7 approximately ...

Страница 11: ... each module is properly supervised fol low the guidelines provided in section 2 8 Step 10 Programming the System Sections 4 5 Section 4 0 provides a complete description of how to pro gram the panel Section 5 0 contains complete descriptions of the various programmable features what options are available and how the options function The Programming Worksheets should be filled out completely befor...

Страница 12: ...in incomplete transmis sions 2 3 Wire Routing for Power Non Power Limited All wiring entry points are designated by the arrows All circuits are classified UL installation power limited except for the battery leads which are not power limited A minimum 6 4mm separation must be maintained at all points between power limited and non power lim ited wiring and connections NOTE Wire entry for power limi...

Страница 13: ...Refer to the Installation Instructions for the module for more infor mation NOTE Only jumpers J1 J2 and J3 determine the zone assignment for the module 2 7 Keypad Assignment There are 8 available slots for keypads LED and LCD5501Z keypads by default are assigned to slot 1 The LCD5500Z is assigned by default to slot 8 Keypads can each be assigned to a different slot 1 to 8 which offers two advantag...

Страница 14: ... panel the module does not have enough power the PC5132 does not have any devices added 2 9 Removing Modules If a module is no longer required on the system the panel must be told to stop supervising the module To do this 1 Remove the module from the Keybus 2 Press 8 Installer Code to enter Installer Program ming 3 Press 902 to enable supervision The panel will auto matically search for all module...

Страница 15: ...ption of how fire zones operate see section Basic Programming PWS Sect 3 Keyswitch Zone Wiring Zones may be programmed to be used as keyswitch arm ing zones and must be wired according to the following diagram For a complete description of how keyswitch zones oper ate see section Basic Programming PWS Sect 3 LINKS1000 Supervisory 24 hr Supervisory When using the LINKS1000 cellular communicator any...

Страница 16: ...nd of line supervision connect the zone according to one of the configurations outlined in section 2 10 Zone Wiring NOTE End of line resistors must be placed on the device end of the loop not at the keypad NOTE Keypad zones do not support DEOL resistors Assigning Keypad Zones When using keypad zone inputs each input used must be assigned a zone number in Installer Programming First ensure that you...

Страница 17: ...rogram boxes All other locations in the Section will remain unchanged If the key is pressed the panel will turn OFF the Ready light turn ON the Armed light and exit you from the Section 3 3 Programming Hexadecimal Data On occasion hexadecimal Hex digits may be required To program a Hex digit press the key The panel will enter Hex programming and Ready light will begin to flash The following table ...

Страница 18: ... Emergency keys Fire Auxiliary or Panic to advance to the next digit When all the digits in a section have been viewed the panel will exit the section the Ready light will turn OFF and the Armed light will turn ON waiting for the next three digit programming section number to be entered Press the key to exit the section LCD Keypad When a programming section is entered the keypad will immediately d...

Страница 19: ...tem at any time by entering 1 see section 1 Zone Bypassing or by using the Away function button If a delay zone is violated during the Exit Delay i e somebody leaves through the designated entry exit door all zones will be active after the Exit Delay expires The panel is now Away armed The Bypass light on the keypad will be off Other methods of Stay and Away arming are available see section Functi...

Страница 20: ... can be viewed while armed using the LCD keypad provided the keypad is version 2 0 or later Older keypads will incorrectly display Fire Trou ble If using older LCD keypads program section 013 option 3 as OFF to ensure that Troubles are displayed correctly The various Troubles are described below Light Trouble 1 Service Required Press 1 to determine the specific Trouble Lights 1 8 will light up to ...

Страница 21: ...e Master Code You can change the partition and attribute programming by following the instructions described below You cannot change Master Code partition or attribute programming The Master Code has all partitions and all attributes turned on except for the Bell Squawk on Arm ing Disarming attribute To program which partition s each code will work on 1 Enter 5 Master Code 8 to enter partition pro...

Страница 22: ...e Auto arm Schedule menu See section 4 4 Global and Partition Keypad Operation for more information NOTE Only PKP LCD v2 0 or greater keypads support the 6 3 menu option 4 System Test When 4 is pressed the panel will perform the following sound the alarm output for two seconds light all lights and display pixels on the keypad sound the keypad buzzer for two seconds test the main panel PC5200 PC520...

Страница 23: ...ing of any function key on any keypad may be changed to one of the options listed below see section 2 7 Keypad Assignment for instructions on changing function key programming 00 Null Key The key is not used and will perform no function when pressed 01 Select Partition 1 Provides an easy way to select partition 1 This is the same as pressing and holding the key then pressing and holding the 1 key ...

Страница 24: ... 26 For Future Use 27 Select Partition 3 28 Select Partition 4 29 Select Partition 5 30 Select Partition 6 31 Select Partition 7 32 Select Partition 8 These keys provide users with an easy way to select one of the above partitions For example this is the same as press ing and holding the key then pressing and holding the 3 key to select partition 3 see section Global and Parti tion Keypad Operatio...

Страница 25: ...nes to Partitions 555 560 PC5208 Sect 6 Communicator Programming 561 564 PC5204 301 304 Telephone Numbers Para 5 9 International Programming 310 System Account Code 700 Clock Adjust 311 318 Partition Account Code 701 First International Options Code 320 323 Alarm Reporting Codes Zones 01 64 702 Second International Options Code 324 327 Alarm Restoral Reporting Codes Zones 01 64 703 Delay between D...

Страница 26: ...is tripped or if the F key is pressed during a delay NOTE This zone type should not be used for Commercial Fire applications 08 Standard 24 hr Fire Hardwired On alarm the bell output will sound to indicate that the fire loop has been activated If enabled the communicator will immediately transmit the alarm to the monitoring station NOTE DO NOT change the Zone attributes of Fire type zones from the...

Страница 27: ... 9 armed a violation of this zone type will ini tiate Entry Delay 1 26 24 hr Non Alarm These zones are active at all times but do not cause an alarm and do not show up in alarm memory Zone Attributes such as Zone Bypassing and Door Chime affect the functionality of this zone A 24 hr Non alarm zone may be used for Zone Follower automation applications NOTE This zone type will be active in Walk Test...

Страница 28: ...n partition Y will pulse Fire PGM with the Main Bell Silent alarms will be audible if either partition is in an audible alarm condition 02 Not Used For Future Use 03 Sensor Reset This output will normally be active This option is used to reset power for latching smoke detectors The output will deactivate for five seconds when the 7 2 command is entered see section 7 Command Output Functions The ke...

Страница 29: ...nfigures the PGM1 terminal for operation with the LINKS1000 cellular alarm communicator 17 Away Armed Status This output will activate when the system is armed with the Stay Away zones activated 18 Stay Armed Status The output will activate when the system is armed with the Stay Away zones bypassed 19 Command Output 1 This output is activated by entering the 7 1 command The configuration of the co...

Страница 30: ...ate the respective zone LED if the zone is in the Tamper or Fault states only the Trouble LED will be on OFF Tampers and Faults Show as Open The panel will illuminate the respective Zone LED if the zone is in the Tamper or Fault states The Trouble LED will also light 5 Auto arm Schedule Programming ON Auto arm Schedule in 6 The Auto arm schedules Sect 181 188 are accessible via 6 as well as Instal...

Страница 31: ...pe alarms for the duration of Bell Time out or until an access code is entered 015 THIRD SYSTEM OPTION CODES Option Definition On Off Description 1 F Key ON F Key Enabled Pressing and holding the F key for 2 seconds will generate a Fire alarm The key pad will sound a set of 3 beeps to acknowledge the valid alarm and the bell or siren will pulse one second on one second off if option 8 of Section 0...

Страница 32: ...ing any key on a blanked keypad will remove the blanking 5 Keypad Backlight ing ON Keypad Backlighting is Enabled All keypads on the system will have backlighting on all of the time OFF Keypad Backlighting is Disabled 6 Power Save Mode ON Power Save Mode Enabled If AC power fails all keypad lights including backlighting will be shut OFF The keypad lights will come back ON after a keypress Entry De...

Страница 33: ...ours as they will be missed on the first Sunday in April Events programmed to occur between 0100 and 0200 will occur twice on the last Sunday in October 7 Periodic Camera Test ON Periodic Camera Test Enabled The panel will test all active cameras on the PC5108L every 30 minutes OFF Periodic Camera Test Disabled If this option is OFF the panel will only test all active cameras on the PC5108L upon e...

Страница 34: ...w zone is open on the sys tem or not This Option is OFF at default 5 Keypad Buzzer Alarm ON Keypad Buzzer Follows Bell Enabled The keypad buzzers will follow the selected partition s bell activity OFF Keypad Buzzer Follows Bell Disabled The keypad buzzer will not follow all bell activity Only alarms designated to activate the keypad buzzer will do so This option is OFF at default 6 Cross Zoning Po...

Страница 35: ...e Auto arm will be cancelled If a value between 001 and 255 is programmed then the Auto arm will be postponed for the corresponding number of minutes and the panel will resume normal operation The panel will also log the appropriate user log for the access code which postponed the arming When the postpone time expires the panel Auto arm Pre alert will be re initiated unless the parti tion is armed...

Страница 36: ...1 198 No Activity Timer Partition 1 8 The timer will begin when a delay type zone assigned to the partition is restored The timer is stopped if any zone assigned to the partition is tripped or restored The timer will restart when a delay type zone is again restored When the timer expires the panel will sound the buzzers of all keypads assigned to the partition for the time pro grammed in Section 1...

Страница 37: ...ng String This is a 6 digit Hex entry that is used to disable Call Waiting on a Call Waiting equipped phone line This is typically 70 in most areas Dialing this string before a phone number will disable Call Waiting for the duration of the call If this section is programmed not FF and Sec tion 382 Option 4 is ON the panel will dial this string in place of the first digit of the phone number Sectio...

Страница 38: ...med period when using Police Code Burglary Not Verified this reporting code will be sent after the Burglary Verified Timer expires after a zone alarm occurs Alarm Cancelled this reporting code will be sent if a valid access code is entered during the Alarm Cancel window If a valid access code is entered during this window then the Alarm Cancelled event is logged and sent When the cen tral station ...

Страница 39: ...ly Out put Module General System Supervisory Trouble a General System Supervisory Trouble reporting code will be transmitted if any module goes missing from the Keybus If the module is a zone expander the panel will also transmit the Zone Expander Supervisory Alarm Trouble reporting code 346 Maintenance Restoral Reporting Codes Battery Trouble Restoral the Battery Trouble Restoral reporting code w...

Страница 40: ...l will transmit this reporting code when a TLM Trouble occurs on the PC5700 line 1 and or on line 2 PC5700 TLM 1 2 Restoral the panel will transmit this reporting code when a TLM Restoral occurs on the PC5700 line 1 and or line 2 350 Communicator Format Options Communicator Reporting Formats Each central station telephone number of the panel can be programmed to report using any one of the 5 forma...

Страница 41: ...ogram 4A79 When programming reporting codes two digits must be entered If one digit reporting codes are to be used the sec ond digit must be programmed as a 0 If a 0 is to be transmitted substitute a Hex digit A for the 0 Examples 1 digit reporting code 3 program 30 2 digit reporting code 30 program 3A To prevent the panel from reporting an event program the reporting code for the event as 00 or F...

Страница 42: ...value defines the number of attempts alarm and restoral pairs per zone that the communicator will make before it shuts down for that zone swinger shutdown Program 001 or 002 in this entry When programmed as 000 the communicator will shut down after 2 Alarm Restoral pairs Different limits can be programmed for Zone Alarms Zone Tampers and Maintenance signals After the panel has communicated the pro...

Страница 43: ...timer will be ignored when the system is armed in the Away mode Zones that are bypassed in the 1 Bypass menu will not reset the timer If the system is programmed to monitor Closing Delinquency the timer will be programmed in days The timer will restart every time the system is disarmed Activity Closing Delinquency section 380 option 8 Communications Cancel Window After TX Delay expires and a zone ...

Страница 44: ...for each Opening After Alarm code successfully reported OFF Opening After Alarm Keypad Ringback Disabled 2 Opening After Alarm Bell Ringback ON Opening After Alarm Bell Ringback Enabled When the Opening After Alarm reporting code is successfully transmitted to a programmed telephone number the bell will sound a series of 8 squawks to confirm to the end user that the Opening After Alarm code was se...

Страница 45: ...INKS1000 options for the Communicator Call Direction Options for the event In addition the Call LINKS1000 as well as Land Line option must be selected The panel will call the LINKS1000 and then call the land line when reporting the selected event 8 Local Mode ON Local Mode Enabled The panel will always send events to the PC5108L module Downlook will not be initiated if requested OFF Local Mode Dis...

Страница 46: ...r two rings then misses a ring 2 At this point the panel will start a timer 3 If the panel hears another ring before the Answering Machine Double Call Timer expires it will answer on the first ring of the second call The panel will immediately go on line and begin the download process unless the Call Back option is enabled If enabled the panel and computer will both hang up The panel will then cal...

Страница 47: ...tput states do not occur after a loss and restoral of AC power If you program more than one PGM output as the same output type e g If PGM 1 and PGM 2 are both pro grammed as 19 Command Output 1 the settings for out put attributes 1 2 and 5 must be the same This does not apply to outputs programmed as types 09 and 10 NOTE Attribute 3 must be ON for PGM output option 16 Assigning Partitions to Progr...

Страница 48: ...urs PGM Output Types 03 and 19 22 4 Output Options ON Output Pulsed The output will activate for the duration programmed in for the PGM Output Timer in Section 164 This default period is five seconds OFF Output On Off The output will toggle between on and off when the corresponding 7 command is entered PGM Output Types 19 22 5 Access Code Options ON Access Code Required for Activation OFF No Acces...

Страница 49: ...If these tones are detected the communicator will disengage the phone line and try to place the call again following the Delay Between Dialing Attempts OFF Busy Tone Detection Disabled The communicator will use the standard dialing procedure for every attempt 7 Battery Current Charge ON High Current Battery Charge Approximately 650 700 mA OFF Standard Current Battery Charge Approximately 350 mA 8 ...

Страница 50: ...or all partitions during the Walk Test regardless of programming To perform a Walk Test do the following 1 Enter Installer Programming 2 Enter Section 901 When any zone is violated the panel will activate the Bell Output for two seconds and log the event to the event buffer Check the event buffer to ensure that all zones and FAP keys are functioning properly NOTE If there is no zone activity on th...

Страница 51: ...lts On occasion it may be necessary to default the main con trol panel or one of the modules that can be connected There are several different defaults available including defaulting the main control panel Escort5580 TC mod ule PC5132 wireless expander module PC5400 printer module and LINKS2X50 module NOTE Defaulting the main panel does not default the keypads See the Programming Worksheets Append...

Страница 52: ...ich includes 16 EOL resistors 5 600Ω One black cabinet plug One green grounding strap Mounting hardware for the PC5020CF PCB One EOL resistor 2200Ω One 1000Ω resistor for bell supervision Minimum System Requirements for Commercial Fire Applications PC5020 CF System Components Central Station Fire Monitoring Service PC5020 control unit PC4050CR PC4050CRAR enclosure PC5700 fire module dual dialer or...

Страница 53: ...he end of line resistor this will be indicated as a Zone Trouble Ground Fault resistance 40kΩ to earth ground indi cated as a Ground Fault Trouble on PC5700 zone 7 Typical Fire Devices used on this zone type are Heat Detectors fixed temperature and or rate of rise Fire alarm panel outputs such as Alarms and Troubles Manual pull stations 4 wire smoke detectors Standard Fire Operation When a Fire Mo...

Страница 54: ...anel This detector may be connected to any PGM 1 4 The PGM must be programmed as Sensor Reset see Pro gramming Worksheets PGM2 can either be programmed for a 2 wire smoke detector or a 4 wire smoke detector but both detectors cannot be programmed concurrently on PGM2 For a wiring diagram see Appendix B 6 Sen sor Reset for 4 Wire Smoke Detectors 7 7 Two Wire Smoke Detector Zones PGM2 can be program...

Страница 55: ...ill occur The Bell Time out if used will restart for a full timing period before automatic silencing The new alarm will be shown 8 5 Auto Scroll LCD Keypad Display When an alarm is initiated the Alarm and selected Trou ble conditions will be displayed on the system LCD key pad s If there is more than one Alarm or Trouble present simultaneously the keypad will continuously scroll through each event...

Страница 56: ... the Fire Keys on any keypad are pressed for two seconds NOTE For commercial applications do not program the F key for keypads that are readily accessible by the public For more information regarding this key see the PC5020CF Installation Manual Section 5 3 Basic Programming 015 Third System Option Codes Option 1 System Maintenance Panel Battery Trouble This code will be sent when the control pane...

Страница 57: ...ible alarm device power supply This may require duplicate protection armed by each partition Access to this protected area without causing an alarm will require that all partitions be disarmed In all cases described above the protected area for the control unit must be programmed as not bypassable Casual Users The installer should caution the user s not to give system information to casual users e...

Страница 58: ...during any given armed to armed period incl 24 hr zones A R 1 4A BM 00 BV 00 328 Burglary Not Verified This reporting code will be sent after the Burglary Verified Timer expires after a zone alarm occurs A R 3 78 BG 00 328 Alarm Cancelled This reporting code will be sent if a valid access code is entered during the Alarm Cancel window A R 4 A6 BC 00 329 F Key Alarm Restoral Keypad fire alarm alarm...

Страница 59: ... Lead In Downloading session start MA R 4 11 RB 00 347 DLS Lead Out Downloading session complete MA R 4 12 RS 00 347 Zone Fault Rest One or more zones have faults restored MA R 3 72 UT ZZ UJ ZZ 347 Delinquency Programmed amount of time days or hours for delinquency has expired without zone activity or without system being armed MA R 4 54 CD 00 347 Wireless Device Low Battery Trouble Rest Wireless ...

Страница 60: ...er 1 59 Low Temp 1 32 Interior 1 61 Loss of Air Flow 1 33 24 hr Zone Definition SIA Auto Rep Codes Contact ID Auto Rep Codes Zone Alm Rest Zone Alm Rest Delay 1 BA ZZ BH ZZ 1 3A Delay 2 BA ZZ BH ZZ 1 3A Instant BA ZZ BH ZZ 1 3A Interior BA ZZ BH ZZ 1 3A Interior Stay Away BA ZZ BH ZZ 1 3A Delay Stay Away BA ZZ BH ZZ 1 3A Delayed 24 hr Fire FA ZZ FH ZZ 1 1A Standard 24 hr Fire FA ZZ FH ZZ 1 1A 24 h...

Страница 61: ... Not to be removed by anyone except occupant This equipment should be installed in accordance with the National Fire Code ANSI NFPA 72 National Fire Protection Association Batterymarch Park Quincy MA 02269 Printed information describing proper installation operation testing maintenance evacuation planning and repair service is to be provided with this equipment This unit includes an alarm verifica...

Страница 62: ...G AS SHOWN ABOVE IMPORTANT A minimum 1 4 6 4mm separation must be maintained at all points between battery primary AC wiring and all other wiring connections POWER LIMITED POWER LIMITED NON POWER LIMITED WARNING Do not route any wiring over circuit boards Maintain at least 1 25 4mm separation Cable Tie not provided Cable Tie To prevent wires from falling onto batteries secure them to the enclosure...

Страница 63: ... be in the same room NOTE All circuits are Power Limited except AC and battery leads Voltage Barrier 80VA IMPORTANT A minimum of 1 4 6 4mm separation must be maintained at all points between power limited wiring and all other non power limited wiring and connections Wire entry for power limited wiring must be separate from non power limited wiring IMPORTANT A minimum of 1 4 6 4mm separation must b...

Страница 64: ...facturer s literature when locating smoke detectors RM 1 POWER LOOP SUPERVISORY RELAY 12VDC 35mA MAXIMUM WHT 4 WIRE SMOKE DETECTORS Smoke Detector must be latching type such as DSC MN240 Series To reset smoke detectors enter 7 2 AUX PGM 2 1 Zone Input COM ALARM INITIATING LOOP RESISTANCE 100Ω PGM1 PGM2 PGM3 PGM4 PGM1 PGM2 PGM3 PGM4 NOTE For devices requiring more than 50mA use a relay DSC RM 1 or ...

Страница 65: ...ke Detectors Enter an access code to reset smoke detectors Alarm Test Activate smoke detector or waterflow sensor according to manufacturer s testing instructions Bell and Communicator Test Enter 6 Access Code 4 on a system keypad Trouble Conditions Trouble conditions are indicated by The keypad Trouble light will turn ON The keypad buzzer will beep To view Trouble conditions Press 2 The keypad di...

Страница 66: ...all in an emergency situation It must be able to do this even if other equipment telephone an swering system computer modem etc already has the telephone line in use To do so alarm dialing equipment must be connected to a properly installed RJ 31X jack that is electrically in series with and ahead of all other equipment attached to the same telephone line Proper installation is depicted in the fig...

Страница 67: ...NOTES ...

Страница 68: ...ith Power864 PC5132 v1 X Yes No support for Wireless Keys Pendants or Handheld Keypads Only the first 32 zones can be used as wireless zones PC5132 v2 X Yes No identified Wireless Keys support Only the first 32 zones can be used as wireless zones PC5132 v3 X Yes Only the first 32 zones can be used as wireless zones PC5200 Yes Fully compatible with Power864 PC5204 Yes Fully compatible with Power864...

Отзывы: