background image

3G Alarm Communicator Installation Manual

Ethernet Options

19

[112] Ethernet Receiver 2 DNIS

Default (000000)

The DNIS is used in addition to the account code to identify the Communicator module at the central station. Valid range: 000000 -

0

99999. Value is entered as leading 

0

 followed by the 5 digit DNIS. Format is BCD.

NOTE: 

Each Ethernet/Cellular receiver must be programmed with a unique DNIS.

[113] Ethernet Receiver 2 Address

Default (000.000.000.000)

Programming the Ethernet receiver 2 IP address with 000.000.000.000 will disable Ethernet.
Enter the Ethernet receiver 2 IP address. This address will be provided by your central station system administrator. Format is 4 fields,
each field is a 3 digit decimal. Valid range: 000-255.

NOTE: 

When a valid IP address has been programmed, Ethernet Receiver 2 is enabled and will communicate events over the Ethernet

channel.

Ethernet Receiver 2 and Cellular Receiver 2 may be configured to communicate to the same central station receiver.
To configure the device to operate using this common receiver mode functionality, program the Ethernet Receiver 2 and Cellular
Receiver 2, IP address and port number with the same values. When operating in common receiver mode the Ethernet Receiver 2
account code will be used for communications over Ethernet and Cellular.

NOTE: 

Do not program Ethernet Receiver 1 and Ethernet Receiver 2 to communicate to same receiver.

[114] Ethernet Receiver 2 Remote Port

Default (0BF5/3061)

This Section is used to program the port number used by Ethernet Receiver 2. Set the value of this port when your installation is located
behind a firewall, and must be assigned a particular port number as determined by your central station system administrator. Valid
range: 0000 - FFFF.

NOTE: 

Do not program Ethernet Receiver 1 and Ethernet Receiver 2 Port with the same value.

[115] Ethernet Receiver 2 Local Port

Default (0BF9/3065)

Use this Section to program the value of the local outgoing port. You can set the value of this port when your installation is located
behind a firewall and must be assigned a particular port number as determined by your network administrator. Valid range: 0000 -
FFFF. 

NOTE: 

Do not program Ethernet Receiver 1 and Ethernet Receiver 2 Port with the same value.

[116] Ethernet Receiver 2 Domain Name

Default (  )

Programming this Section is 

not

  permitted on a UL/ULC listed system.

Enter the Domain Name as 32 Character ASCII.

E

THERNET

 O

PTIONS

[124] Ethernet Test Transmission Time

Default (9999)

Enter a 4 digit number (0000-2359) using the 24-hour clock format (HHMM) to set the test transmission time of day. 
Valid range: 00 - 23 hours (HH) and 00 - 59 minutes (MM). Programming a value of 9999 will disable the test transmission time.

NOTE: 

The internal date and time will automatically be programmed when the unit communicates with the primary receiver.

[125] Ethernet Test Transmission Cycle

Default (000000)

This value represents the interval between test transmissions, in minutes. Valid range: 000000 - 999999 minutes. Once the unit has sent
the initial periodic test transmission, all future test transmissions will be offset by the programmed number of minutes. See Sections
[026] - [029].

NOTE: 

Minimum value is 000005 minutes. Programming an interval that is less than 5 minutes will disable test transmission.

C

ELLULAR

 R

ECEIVER

 1 O

PTIONS

[201] Cellular Receiver 1 Account Code

Default (0000000000)

The account code is used by the central station to distinguish between transmitters. This account code is used when transmitting heart-
beat signals to the central station receiver. Signals received from the control panel will use the control panel account number. Valid
range: 000000000

1

 - FFFFFFFFF

E

. Programming all 

0

 or all 

F

 will cause a Module Configuration Trouble (yellow LED = 12 flashes).

[202] Cellular Receiver 1 DNIS

Default (000000)

The DNIS is used in addition to the account code to identify the Communicator module at the central station. Valid range: 000000 -

0

99999. Values are entered as leading 

0

 followed by the five digit DNIS. Format is BCD.

NOTE: 

Each Ethernet/Cellular receiver must be programmed with a unique DNIS.

Table 11: Ethernet Test Transmission Interval

Test Transmission Interval

Daily

Weekly

Monthly

Programmed Minutes

001440

010080

043200

Содержание 3G2075

Страница 1: ...LARM COMMUNICATOR Warning This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer Installation Manual...

Страница 2: ......

Страница 3: ...s Sections Ethernet Cellular Programming Options 11 System Options 11 Programming Options 13 Communications Reporting Codes 16 Ethernet Receiver 1 Options 18 Ethernet Receiver 2 Options 18 Ethernet Op...

Страница 4: ...response may not occur in time to protect the occupants or their belongings Motion Detectors Motion detectors can only detect motion within the designated areas as shown in their respective installati...

Страница 5: ...and return to normal entry NOTE Authorized access to Connect24 3G2075 TL2753G is required to modify any Ethernet Cellular Programming Section Spe cific panel Sections must be configured for proper op...

Страница 6: ...ULC INSTALLATION REQUIREMENTS For ULC Residential fire and burglary applications the 3G2075 TL2753G can be used as primary communication channel via either Cellular or Ethernet as applicable or as a b...

Страница 7: ...ber Installer ID Number and an Installer Password Perform the following pre installation 1 Retrieve the installer account and password from the Aurora Technical Services ATS group 2 Call VRU number 1...

Страница 8: ...des shall be observed and respected during installation INSTALLING CAT 5 CABLE TL2753G ONLY A Category 5 CAT 5 ethernet cable must be run from a source with Ethernet Internet connectivity to the Commu...

Страница 9: ...g on to the next number cycling through each of the 4 numbers for a total of 5 times each If all 4 numbers fail the 5 attempts an FTC trouble is displayed on the keypad 4 Panel Sections 301 302 303 an...

Страница 10: ...e location is BAD move the SCW9055 SCW9057 to various suitable locations until 3 or more bars are obtained NOTE The communicator is capable of indicating signal strength even without an active SIM but...

Страница 11: ...heartbeats to Ethernet Receiver 1 or Cel lular Receiver 1 to test the communications path Use this Section to set the interval time in seconds when heartbeats will be sent to the receivers Valid rang...

Страница 12: ...be sent to the programmed receivers based on the settings of the periodic test transmission reporting codes 8 Cellular Low Signal Trouble Default OFF This option masks the Low Signal trouble from the...

Страница 13: ...0000 FFFF 013 DLS Outgoing Port Default 0BFA 3066 The DLS Outgoing Port is used for outgoing session to DLS IV after an SMS request has been sent to the Communicator Use this Sec tion to set the value...

Страница 14: ...e Time BWST Brazil Western Standard Time PST Philippine Standard Time SLT San Luis Time PIT Pratas Islands PYT Paraguay Time PIT Parcel Island Time JFST Juan Fernandez Island Standard Time MYT Malaysi...

Страница 15: ...ca Standard Time PONT Phonpei Standard Time IST Israel Standard Time MAGT Magadan Island Time 3D 3 MSK Moscow Standard Time 5F 11 5 NFT Norfolk Island Time EAT Eastern Africa Time 61 12 NZST New Zeala...

Страница 16: ...ent will occur when communications with the panel have been lost for more than 60 seconds 024 Panel Absent Trouble Restore Default FF Program 00 to disable this event or FF to enable This event will o...

Страница 17: ...r details on settings NOTE The time interval in minutes between periodic tests is programmed in Section 125 Ethernet and Section 225 Cellular 030 FTC Restore Default FF Program 00 to disable this even...

Страница 18: ...ver To configure the device to operate using this Common Receiver Mode functionality program Ethernet Receiver 1 and Cellular Receiver 1 IP address and port number with identical values NOTE When oper...

Страница 19: ...lation is located behind a firewall and must be assigned a particular port number as determined by your network administrator Valid range 0000 FFFF NOTE Do not program Ethernet Receiver 1 and Ethernet...

Страница 20: ...s all 0 or F will cause a Module Configuration Trouble yellow LED 12 flashes 212 Cellular Receiver 2 DNIS Default 000000 The DNIS is used in addition to the Account Code to identify the Communicator m...

Страница 21: ...f minutes See Sec tions 026 029 NOTE Minimum value is 000005 minutes Programming an interval that is less than 5 minutes will disable test transmission 226 Cellular Trouble Delay Default 00 This optio...

Страница 22: ...n 008 or assigned by DHCP 990 Boot Loader Version This Section will display the current Boot Loader version of the Communicator 991 Firmware Version This Section will display the current firmware vers...

Страница 23: ...ss This Section will display the unique12 digit hexadecimal number assigned as the Media Access Control MAC address of the device SYSTEM RESET DEFAULTS 999 Software Default Default 99 The Software def...

Страница 24: ...cate the signal levels with digit 1 and 2 a network status with digit 3 and the trouble status with digit 4 and 5 as indicated in table above For example status code 11000F would display following sta...

Страница 25: ...t 06 Ethernet Trouble Check with your ISP to confirm Internet service is active in your area Ensure your Ethernet cable is securely inserted into the RJ45 jack of the Communicator and the Hub Router S...

Страница 26: ...evel dBm Signal Level Status Action Required No Signal 0 0 0 108 8 bad Check all antenna connections Confirm 3G service is active in area Relocate Panel 1 Bar 1 4 0 2 108 103 weak Relocate Panel if si...

Страница 27: ...range 0000 FFFF ____ ____ ____ ____ 011 Installer Code Default CAFE Valid range 0000 FFFF ____ ____ ____ ____ 012 DLS Incoming Port Default 0BF6 3062 Valid range 0000 FFFF ____ ____ ____ ____ 013 DLS...

Страница 28: ...Valid range 000000 999999 minutes ____ ____ ____ ____ ____ ____ CELLULAR RECEIVER 1 OPTIONS 201 Cellular Receiver 1 Account Code Default 0000000000 Valid range 0000000001 FFFFFFFFFE ____ ____ ____ ___...

Страница 29: ...____ ____ ____ ____ ____ 989 DNS 2 IP Address ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ 991 Firmware Version ____ ____ ____ ____ ____ ____ ____ ____ 992 Ethernet IP Address ____ ___...

Страница 30: ...d materials any upgrades and this EULA and provided the recipient agrees to the terms of this EULA If the SOFT WARE PRODUCT is an upgrade any transfer must also include all prior versions of the SOFTW...

Страница 31: ...ed or repaired in such a manner as to adversely affect performance or prevent adequate inspection or testing to verify any warranty claim Access cards or tags returned for replacement under warranty w...

Страница 32: ...ada technical specifications were met Certification Number IC 160A 3G255SM This device complies with Industry Canada licence exempt RSS standard s Operation is subject to the following tow conditions...

Отзывы: