DryGair Dehumidification Unit Model DG-X
Maintaining the Unit
Ver. 12/2020
35
7.3
Quarterly Maintenance
Perform the following every quarter:
•
The monthly maintenance.
•
Clean the evaporator and condenser coils surfaces. For details on cleaning
the coils, see section 7.5.
•
Clean the drainage pan. See details in section 7.5.
•
Check the refrigerant charge:
a.
Run the unit for about 15 minutes.
b.
Open the right-side door and check that there are no bubbles at the
sight glass.
c.
Check that the evaporator coil is wet across its surface. Partial
wetness indicates a loss of refrigerant or low charge.
7.4
Annual Maintenance
Perform the following every year:
Note
It is recommended the yearly inspection and maintenance is performed by
a qualified DryGair person or representative and having a Refrigerant
technician or electrician for assistance.
•
The quarterly maintenance.
•
Paint damaged or chipped body paint to preserve the unit body.
•
Check that the fan is firmly secured to the motor shaft and that the fan
rotates freely. The fan motor is sealed for life and therefore does not need
to be lubricated.
•
Check that the compressor isolators did not become free.
•
Tighten the compressor taps and pressure switches to prevent refrigerant
leaks.
•
Check the electric currents of the compressor and fan.
•
Check all wiring connections and if necessary, tighten the screws
(especially in the electricity panel).
•
Calibrate the humidity sensor. The humidity controller type is IR33,
manufactured by "CAREL"
(