7.3.3 Wall terminal (C11)
When using a wall terminal (C11), the following applies:
The construction of the chosen system has to be allowed.
1
Check that the vertical pipe length falls between the minimum and maximum lengths (see table 7-5).
1
Check that the horizontal pipe length (wall terminal excluded) falls within the minimum and maximum length (see table
7-5).
3
In all tables below, 1 bend has been included in the concentric system. It is possible, however, to add extra bends. For
each additional bend, the maximum allowed horizontal length of the concentric system is reduced. This is done as
follows:
- An additional 90° bend shortens the maximum allowed length of the concentric system by 2 metres.
- An additional 45° bend shortens the maximum allowed length of the concentric system by 1 metre.
3
At least 1 metre should always be placed on the appliance vertically, unless stated otherwise in the table.
1
Determine the correct adjustment of the appliance (see table 7-5).
1
Adjust the appliance correctly with, for instance, a restrictor slide and an air inlet guide (see section 8.2).
The rosette of the wall terminal is too small to seal the opening in case of passage through combustible material. That is
why a heat-resistant intermediate plate of sufficient size should first be mounted to the wall. Then, the rosette is
mounted on the intermediate sheet.
3
When using a wall terminal, place the terminal with a downward slope of 1 cm / metre towards the outside, in order to
prevent rain water from raining in.
I nst allation manual
3 0
0,5 - 0,8m
0 m
38C-744ZZ
1x90°
0
0
38C-744W
1x90°
Table 7-5a
Table 7-5b
Setting
Air inlet guide
Restrictor slide
Apply
x
x
- Only use a 200/130 mm concentric system, including wall
terminal.
- In the case of this configuration, an unpainted stainless
steel wall terminal must be used..
- Factory setting: Air inlet guide 1 mounted, air inlet guide
2 and restrictor slide are supplied separately.
- Only use a 200/130 mm concentric system, including wall
terminal.
- Factory setting: Air inlet guide 1 mounted, air inlet guide
2 and restrictor slide are supplied separately.
Setting
Air inlet guide
Restrictor slide
Apply
x
x
Содержание Maestro 60/2 Tall RCH
Страница 15: ...Installation manual 15 A D B C 38C 2500 7 4...
Страница 17: ...Installation manual 17 1 3 4 2 38C 2504 tooltip tooltip 7 6...
Страница 19: ...Installation manual 19 38C 2793 1 2 3 4 5 6 7 7...
Страница 21: ...Installation manual 21 1 3 2 4 38C 2619 586 5mm 1 2 38C 2503 7 8 7 9...
Страница 23: ...Installation manual 23 5 7 8 6 38C 2507 1 60 1 3 2 4 2 mm 38C 2506 1 7 10 7 11...
Страница 24: ...Installation manual 24...
Страница 29: ...Installation manual 29...
Страница 32: ...Installation manual 32...
Страница 37: ...Installation manual 37 1 2 3 4 5 6 7 8 9 12 11 10 38C 2511 2 7 15...
Страница 47: ...Installation manual 47 38P 0820 2 8 16...
Страница 48: ...Installation manual 48 38P 0815 2 Eco Glow 38P 0814 2 Eco Glow 8 17 8 18...
Страница 49: ...Installation manual 49 A C 38P 0816 2 B 8 19...
Страница 50: ...Installation manual 50 D E 38P 0817 2 1 cm 8 20...
Страница 51: ...Installation manual 51 38P 0819 0 Eco Glow F 38P 0818 0 G Eco Glow 8 21 8 22...
Страница 52: ...Installation manual 52...
Страница 57: ...Installation manual 57...
Страница 64: ...Installation manual 64...
Страница 65: ...Installation manual 65...
Страница 66: ...Installation manual 66...
Страница 67: ...Installation manual 67...
Страница 68: ...DRU Verwarming B V The Netherlands Postbus 1021 NL 6920 BA Duiven Ratio 8 NL 6921 RW Duiven Installation manual...