INS T ALLAT I ON M A N U A L
5.12 Setting the appliance
The appliance has to be set in such a way that it works correctly in combination with the concentric system.
For that purpose, a restrictor slide is placed and/or the air inlet guide is removed. The conditions for application
with wall terminal and roof terminal are stated in appendix 2, tables 4, 5 and 6.
This appliance is suitable for PowerVent®. For more information, see the PowerVent® installation manual.
5.12.1 Restrictor slide (R)
The restrictor slide (R) is supplied separately. It is mounted as follows (see Appendix 3, fig. 12):
Ø
Unscrew the parkers (S) from the middle plate (T).
Ø
Remove this plate.
Ø
Unscrew the 3 pre-mounted self-tapping screws (U) from the combustion chamber.
Ø
Install the restrictor slide (R). It partly covers the hole of the exhaust pipe.
Ø
At the same time, tighten the 3 self-tapping screws (U) by a few turns, but not yet fully tight;
!Caution
When mounting, the arrow on the restrictor slide should point to the left (see appendix 3, fig. 12).
Ø
Set the position of the restrictor slide (R) using situations B to D in appendix 2, table 6. The letter for the position
on the restrictor slide corresponds with the letter of the situation in table 6.
Ø
Make sure that the point of the triangle belonging to the position that you want and the centre of the self-tapping
screw are exactly aligned;
Ø
Tighten the 3 self-tapping screws (U).
Ø
Place back the middle plate (T).
5.12.2 Air inlet guide (L)
The constructed air inlet guide (1 + 2) is located under the vermiculite plate.
When removing the constructed air inlet guide or removing the additional air inlet guide (1), proceed as follows
(see appendix 3, fig. 13):
Ø
Unscrew the self-tapping screws from the vermiculite plate (B) and remove it from the appliance.
Ø
Unscrew the self-tapping screws (N) of the assembled air inlet guide (1 + 2).
Ø
If no air inlet guide is used: remove the assembled air inlet guide and screw the self-tapping screws (N) back into
the appliance.
Ø
If an air inlet guide (2) is used: Take the assembled air inlet guide from the appliance and remove the additional air
inlet guide (1) with the self-tapping screws (P) from the air inlet guide (2). Place the air inlet guide (2) back in the
appliance and fasten it with the self-tapping screws (N).
Ø
Place the vermiculite plate back in the appliance and fasten it with the self-tapping screws.
13
Содержание 0063CM3071
Страница 29: ...E n g l i s h INSTALLATION MANUAL 29 38C 1868 d 0 0 8 4m 2 5m 38c 744o 1x90 0 8 4m 0 1m 38c 744p 1x90 5 4 5...
Страница 30: ...E n g l i s h INSTALLATION MANUAL 30 T U 2 1 38C 1897 0 X 3 7...
Страница 32: ...E n g l i s h INSTALLATION MANUAL 32 B N P 1 2 12x 38c 2136 0 13...
Страница 34: ...E n g l i s h INSTALLATION MANUAL 34 38P 0169 C B D E F G H A 38p 0443 23 22...
Страница 35: ...E n g l i s h INSTALLATION MANUAL 35 38P 0442 A C B E 38p 0444 D F G H 38P 0445 24 25 26...
Страница 36: ...E n g l i s h INSTALLATION MANUAL 36 38P 0529 0 38P 0530 0 38c 1657 0 27 28 29...
Страница 37: ...E n g l i s h INSTALLATION MANUAL 37 38p 0448 38p 0440 38p 0441 32 30 31...
Страница 39: ...E n g l i s h INSTALLATION MANUAL 39 1 98 Off 1 98 Off B2 B1 B U B U C B D 38p 0319 2 P1 P2 G IN A 38 37...
Страница 41: ...E n g l i s h INSTALLATION MANUAL 41 300 mm 38C 2605 20 mm 20 mm R 40 mm 270 mm 38C 2607 43 42...
Страница 42: ...E n g l i s h INSTALLATION MANUAL 42...
Страница 43: ...E n g l i s h INSTALLATION MANUAL 43...
Страница 44: ...E n g l i s h DRU Verwarming B V The Netherlands Postbus 1021 NL 6920 BA Duiven Ratio 8 NL 6921 RW Duiven EN...