INS T ALLAT I ON M A N U A L
Ø
Use a self-tapping screw to fix the clip binding to the pipe on locations that cannot be reached after installation.
Ø
Attach the concentric system with sufficient fastening brackets, so that the weight is not resting on the appliance.
Observe the following;
•
Place the first fastening bracket 0.5 metre from the appliance, at the most.
•
Place a fastening bracket maximum 0.1 metre from each bend, if the bends are more than 0.25 metre away
from each other. If two bends are closer to one another than 0.25 metre, 1 fastening bracket between these
bends will be sufficient.
•
At least every 1 metre, place a fastening bracket at slanted and horizontal sections.
•
At least every 2 metres, place a fastening bracket at vertical sections.
Ø
Fasten a roof terminal with anchor cables, if it protrudes more than 1,5 metres above the terminal.
Ø
Determine the remaining length for the wall or roof terminal and cut it to size, make sure the correct insertion
length is maintained.
Ø
Place the wall terminal with the (groove/folded) seam at the top.
Ø
Attach the wall terminal from the outside by means of four screws.
!Caution
When using the wall terminal, place the terminal with a downward slope of 1 cm / metre towards the outside, in
order to prevent rain water from raining in.
5.9 Connection to an existing chimney (C91)
The appliance can be connected to an existing chimney. A 100 mm diameter flexible SS pipe is placed in the
chimney for discharging flue gases. The surrounding space is used as combustion air supply.
In case of an appliance connection of ø200/130, 0.8 metres of concentric system must first be connected vertically.
Reduce the concentric system after the first 0.8 metres to a diameter of 150/100. The concentric system of 150/100
can be vertically connected to an existing chimney.
The following requirements apply when connecting to an existing chimney:
•
Only allowed when used in combination with the special DRU chimney set. The installation regulation is parat
of the delivery.
•
The internal size should be at least 150 x 150 mm.
•
The vertical length has a maximum of 12 meters.
•
The total horizontal pipe length may have a maximum length that can be found in appendix 2, table 4.
•
The existing chimney should be clean.
•
The existing chimney should be tight.
For setting the appliance, the same conditions/instructions apply as for the concentric system described above.
11
Содержание 0063CM3071
Страница 29: ...E n g l i s h INSTALLATION MANUAL 29 38C 1868 d 0 0 8 4m 2 5m 38c 744o 1x90 0 8 4m 0 1m 38c 744p 1x90 5 4 5...
Страница 30: ...E n g l i s h INSTALLATION MANUAL 30 T U 2 1 38C 1897 0 X 3 7...
Страница 32: ...E n g l i s h INSTALLATION MANUAL 32 B N P 1 2 12x 38c 2136 0 13...
Страница 34: ...E n g l i s h INSTALLATION MANUAL 34 38P 0169 C B D E F G H A 38p 0443 23 22...
Страница 35: ...E n g l i s h INSTALLATION MANUAL 35 38P 0442 A C B E 38p 0444 D F G H 38P 0445 24 25 26...
Страница 36: ...E n g l i s h INSTALLATION MANUAL 36 38P 0529 0 38P 0530 0 38c 1657 0 27 28 29...
Страница 37: ...E n g l i s h INSTALLATION MANUAL 37 38p 0448 38p 0440 38p 0441 32 30 31...
Страница 39: ...E n g l i s h INSTALLATION MANUAL 39 1 98 Off 1 98 Off B2 B1 B U B U C B D 38p 0319 2 P1 P2 G IN A 38 37...
Страница 41: ...E n g l i s h INSTALLATION MANUAL 41 300 mm 38C 2605 20 mm 20 mm R 40 mm 270 mm 38C 2607 43 42...
Страница 42: ...E n g l i s h INSTALLATION MANUAL 42...
Страница 43: ...E n g l i s h INSTALLATION MANUAL 43...
Страница 44: ...E n g l i s h DRU Verwarming B V The Netherlands Postbus 1021 NL 6920 BA Duiven Ratio 8 NL 6921 RW Duiven EN...