Page 8 • DRI-STEEM Ultra-sorb Steam Dispersion Panel Installation, Operation, and Maintenance Manual
F i e l d a s s e m b l y o f M o d e l LV
STEP 2 - Bolt the mounting flanges to the supply header
assembly
Refer to Figure 8-1 and 8-2. Attach the two mounting flanges
as indicated using ¼" - 20 bolts with the nuts only finger tightened.
STEP 3 - Insert the dispersion tubes
Refer to Figure 8-4. Insert the plain ends (no slip couplings) of
the dispersion tubes into the slip coupling already mounted on the
supply header assembly. The slip couplings are factory lubricated;
if well aligned during insertion, no further lubrication should be
needed. Push and twist the tube in until it bottoms out on the inter-
nal shoulder of the slip coupling. See Figure 8-3.
C A U T I O N !
Use care to avoid cutting the internal O-rings of the
slip couplings.
OM-260-2
OM-260-3
¼" - 20 bolt
Washer and nut
Mounting
flange
Steam
inlet
Steam
inlet
Slip coupling
with shoulder
Dispersion
tube
Condensate
drain tube
OM-238-6
Shoulder
O-rings
OM-239
¼" - 20 bolts
Mounting flange
Figure 8-1:
Supply header assembly
Figure 8-2:
Detail view of mounting flange
Figure 8-4:
Dispersion tubes
Figure 8-3:
Detail view of slip coupling
Supply header assembly
Supply header assembly
US-IOM-0108.pdf 8
4/21/2010 11:34:58 AM