Page 24 • DRI-STEEM Ultra-sorb Steam Dispersion Panel Installation, Operation, and Maintenance Manual
Tr o u b l e s h o o t i n g g u i d e
Table 24-1:
Ultra-sorb troubleshooting guide
Problem
Possible cause
Action
Humidifier discharges
water in duct
• Steam main overloaded with water due to boiler
discharging water with steam (priming)
• Locate cause of priming and correct.
• Steam trap not draining properly
• Replace, repair, or clean trap as required.
• If condensate return main is overloaded, find an alternative
method for draining.
• Humidifier improperly piped
• Correct the piping as shown on Page 16. For horizontal airflow,
steam inlet should be at the top of the assembly and conden-
sate outlet at the bottom of the assembly. For vertical airflow,
see Page 14.
• Surges of condensate in steam supply due to
condensate collecting at low, undripped point in
steam main
• Install drips and steam traps as required. See Page 16.
• Inadequate steam trap capacity
• Replace with larger trap.
Slip couplings leak water
• Defective o-rings in slip couplings
• Replace o-rings.
Humidity exceeds setting
of humidistat
• Automatic valve not fully closing
• Foreign matter holding valve open; clean valve.
• Valve spring broken; replace spring.
• Valve steam packing too tight; loosen and/or replace packing.
• Steam pressure exceeds close-off rating of valve spring;
replace actuator or valve spring with one that is compatible
with the higher steam pressure.
• Valve installed backwards; re-install.
• Adjust valve linkage.
• Electric control system malfunctioning
• Calibrate or replace.
• Faulty or inaccurately placed humidity controller
• Replace controller or relocate per catalog recommendations.
• Poor location of control components
• Relocate per catalog recommendations.
• Incompatible control components
• Replace per specified recommendations.
• Automatic valve is hunting
• Humidifier capacity is oversized; change to smaller valve.
• Pressure reducing valve is not accurately controlling steam
pressure; repair or replace.
• Boiler pressure is swinging too widely; adjust.
• Excessive outside air volume
• Check fans, dampers, VAV, etc. See formula below.
Mixed Air Inlet formula:
(% outside air
x
moisture content)
+
(% return air
x
moisture content)
=
mixed air inlet in lbs/100cfm (kg/100 m
3
/h)
Control system
malfunctioning
• Incorrect control voltage
• Replace transformer.
• Incorrect control signal
• Replace components.
• Improper wiring connections
• Rewire.
• Incorrect humidity sensor
• Replace.
• Humidity controller out of calibration
• Recalibrate.
Air cannot absorb steam
quantity being
discharged
• Humidifier operates when blower is off
• Provide interlock.
• Valve is hunting
• See above.
• Air temperature in duct too low for steam
quantity being emitted
• Raise duct air temperature.
Humidifier is noisy
• Steam pressure too high
• Reduce pressure.
• Header vibrating within header shell
• Tighten hardware.