DRI-STEEM Ultra-sorb Steam Dispersion Panel Installation, Operation, and Maintenance Manual • Page 21
3. Remove the dispersion tube.
Make sure nothing loose falls
into the header.
Installing High-efficiency tubes
Note:
The photos below show the High-efficiency tubes
without the
clear poly film
for demonstration purposes only. To prevent
dirty insulating material, install the High-efficiency tubes before
tearing off the clear poly film.
Perform the following steps for each
insulated tube being installed:
1. Slide the new slip couplings onto the
high-efficiency dispersion tube as
shown.
2. Push and twist the dispersion tube
onto the supply header until the
slip coupling shoulder bottoms out.
Connect the dispersion tube to the
condensate header with the other
slip coupling.
3. Push the shoulderless slip coupling
against the stop disc on the
condensate header.
4. Rotate the dispersion tube to point
the tubelets perpendicular to the
airstream.
Step 3
Step 1
Slip coupling
with shoulder;
supply-header-
end of tube
Slip coupling
without shoulder;
condensate-header-
end of tube
Step 2
Step 3
Step 4
R e t r o f i t t i n g a n e x i s t i n g U l t r a - s o r b
Note:
See maintenance instructions for high-
efficiency tubes on Page 23.
US-IOM-0108.pdf 21