M a i n t e n a n c e
Strainer
•
Inspect the strainer screen at least twice during the first year. If
fouled, inspect it more frequently.
Steam trap
•
At least twice a year verify that the steam trap is functioning
properly. A blocked steam trap is cold. A "blowing" steam trap
is hot and noisy, and the discharge pipe from it is hot for 30
feet. A properly operating steam trap is hot and makes noise
at intervals, and the discharge pipe is progressively cooler
beginning at the trap.
Valves
•
Pneumatic
Inspect annually to be sure the valve closes off steam tightly, the
stem packing is not leaking steam, and the diaphragm in the
actuator is not leaking air.
•
Electric modulating
Inspect annually to be sure that the valve operates freely and
closes off steam tightly and the stem packing is not leaking.
•
Solenoid type
Inspect annually to verify proper functioning with steam-tight
shut off.
O-Rings (slip couplings)
•
Inspect after two or three years of service, replace if necessary.
High-efficiency tubes
•
If the insulating material gets torn, repair the tear with our
Insulating Material Repair Kit before dispersing steam or
moving air through the air handler to prevent further damage.
This available kit uses tested and proven PVDF as repair
material; do not use other adhesives or repair methods in place
of the kit.
•
If the insulating material gets dirty or smudged, gently clean
it with a damp cloth and a solution of soapy water or diluted
non-toxic, biodegradable cleaner/degreaser.
•
Do not clean the insulating material with a pressure washer. The
direct spray could cause damage.
•
If using a torch in the vicinity of the dispersion panel, keep the
flame away from the insulating material to avoid damage.
•
PVDF is inherently resistant to UV light. Indirect, low-intensity
UV-C light from germicidal lamps will not cause the insulating
material to degrade.
•
Do not tighten mounting clamps or fasteners to any part of the
dispersion tube.
US-IOM-0108.pdf 23
4/21/2010 11:34:59 AM