RTS HUMIDIFIER RX SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
• The following information is not intended to supersede any requirements of
federal, state, or governing codes having jurisdiction; prior to locating the
unit, authorities having jurisdiction should be consulted.
• The RTS humidifier must be level and located so there is enough clearance
for opening the access panels (see recommended clearances on Page
• The unit should be located so prevailing winds do not blow into the air
intakes.
• When located on the roof, the air intakes must be a minimum of 14”
(360mm) off the roof to prevent intake of snow or splashed rain.
• Locate unit so air intakes are not too close to other exhaust fan outlets,
gasoline storage, or other contaminants that could potentially cause
dangerous situations. Using and storing gasoline or other flammable vapors
and liquids in open containers near this appliance is hazardous.
Outdoor enclosure: Location
INSTALLATION