7
RTS HUMIDIFIER RX SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Models, capacities, and electrical specifications (Europe)
SPECIFICATIONS
Table 7-1:
RTS humidifier capacities, electrical specifications (Europe)
RTS model
230V Single Phase
400V Three Phase
Maximum Steam
Power
Total
Maximum
Current
Draw
Heater
Configuration
Maximum Steam Capacity
Power
Total
Maxi-
mum
Current
Draw
Heater
Configuration
lbs/hr
kg/hr
kW
amps
lbs/hr
kg/hr
kW
amps
RX-63-3
—
—
—
—
—
—
—
—
—
—
RX-75-3
74.4
33.7
25
107.8
3-023
—
—
—
—
—
RX-90-3
90.9
41.2
30
131.8
3-003, 3-023
—
—
—
—
—
RX-102-3
99.2
45.0
34
143.8
6-016
—
—
—
—
—
RX-144-3
—
—
—
—
—
—
—
—
—
—
RX-162-3
—
—
—
—
—
—
—
—
—
—
RX-189-3
—
—
—
—
—
189
85.7
63
97.4
6-019, 3-025
RX-216-3
—
—
—
—
—
216
98.0
72
116.9
3-019, 6-025
RX-243-3
—
—
—
—
—
243
110.2
81
116.9
9-025
RX-102-4
—
—
—
—
—
—
—
—
—
—
RX-126-4
121.2
55.0
42
175.7
4-003, 4-023
—
—
—
—
—
RX-144-4
132.3
60.0
48
191.7
8-016
—
—
—
—
—
RX-162-4
—
—
—
—
—
—
—
—
—
—
RX-216-4
—
—
—
—
—
—
—
—
—
—
RX-264-4
—
—
—
—
—
264
119.7
88
155.9
4-011, 8-025
RX-288-4
—
—
—
—
—
288
130.6
96
155.9
4-019, 8-025
RX-324-4
—
—
—
—
—
324
146.9
108
155.9
12-025
• All RTS humidifier models operate at 50/60 Hz.
• For wire sizing, the highest leg draw is shown due to current imbalance.
• *600931 are the first digits of the heater part number.
• Maximum amps is determined based on the heaters used by each model. Some voltage/kW combinations show higher amperage values than
what the unit capacity will allow.