8. ASSEMBLING THE INDUCTION HEATING TOOL
8.1 UNPACKING AND FIRST START
1. Unpack the device and any accessories supplied and check that they are in good order and
the device and the accessories are not damaged. If you find any defects, do not continue !
2. Leave the device to acclimatise for 15 minutes.
3.
Important:
Remove the sealing ring located under the coolant tank filling hole lid tab. Pull to
remove the lid tab and take out the sealing O-ring. Then push the tab, including the foam
gasket, back into the tank lid. Keep the O-ring for potential future use if sending the machine
via a parcel service.
4. If the focusing head is not attached, screw it on .
5. Fill the device with the liquid coolant supplied via the filling hole .
6. Connect the device to a 230V (16amp recommended) socket and turn it on using the switch at
the back of the device
.
7. The cooling circuit venting is activated automatically, and the letters “FIL” flash on the
electronic display during this. The coolant level decreases noticeably during the filling .
8. After completion of the venting, turn the device off and add the coolant so that the coolant
level is at the upper edge of the gauge at the back of the device (about 1 cm below the top of
the tank).
9. Turn on the device and let the venting proceed. If the level does not sink, the device is filled
and vented correctly. Repeat the procedure as needed.
8.2 COOLANT
REFILLING
Check and refill the liquid coolant before each device starting. Use the original Draper liquid
coolant only!
DO NOT USE WATER !
The device has integrated coolant level inspection. If the coolant runs low, the device
stops heating and displays the error message “E##”. In that case, refill the coolant in the tank
as described in chapter 6.1 point 6 - 9.
9. INDUCTION HEATING TOOL INSTRUCTION
Indicator lamp
Status
RED Parameter
selection
GREEN Value
setting
Description Display
Value
Unit
Return / exit
---
---
Heating mode
REG
CF = constant magnetic field / current
CP = constant heating power
Remote control
rc
OFF
PEd = on/off control, power set on device
PEA = analog, current coil (0-5V/10V)
Input Current Limit
ic.L
min 6.0A, max 16.5A = limitation on maximum input current
Max. output power
Po.L
min 2kVA, max 4.5kvA; default m is 4kVA
Cooling
CoL
Lo = silent mode (workshops, short-term capacity)
Std = standard mode
Hi = max. capacity / does not switch off
Water Fill
FIL
no
yes = activates filling and venting
Factory setting
FAC
no
YES = load factory setting
Unlock code
UnL
Servicing menu code
Firmware Fir
Display
firmware
version
9.6 SETTING
Allows for setting of the induction heater operational parameters.
Press the selection wheel
repeatedly until the indicator lamp glows red. Then turn the
selection wheel
to select the parameter to display or set and press to confirm. The indicator
lamp glows green.
Now you can turn the selection wheel
to set the desired parameter value. Press the selection
wheel
to confirm the setting; this will return you to selection of another parameter, or select
“---” to go to the next setting. To exit to power settings immediately, press and hold down the
selection wheel.
1)
The indicator lamp has to following statuses:
The following parameters can be set:
2)
“HC“ Heating mode
Enables selection of desired heating mode – see chapter Heating modes. The following options
are available:
•
CF = control based on desired magnetic field intensity
•
CP = control to desired heating power
3)
“Po L” Maximum output power
Allows you to select the maximum inverter output power, which is convenient for small coils,
limited by maximum power or current. This enables use of specialised, small or wire coils, which
would otherwise overheat.
The other advantage is the possibility of limiting the max. power to the minimum required,
which in combination with the CP power control mode significantly reduces device
overheating and increases the heating efficiency.
- 18 -
- 11 -