background image

Normal Operation

A Polytron Pulsar 2 Open Path Gas Detector should always be re-zeroed 

whenever it is re-sited, cleaned or re-aligned.

Normal Operation

The Dräger Polytron Pulsar 2 Open Path Gas Detector generates a 4-20mA signal, 

proportional to the measured gas concentration, when the device configured for 
analogue  signal  transmission.    It  can  also  be  configured  for  digital  transmission 

through the use of HART.

Current

Meaning

20.5 mA

Over-range

4-20 mA

Measuring

3.5 mA

Pre-warning (dirty optics or mis-alignment)

2 mA

Beam Block

<1 mA

Fault

NOTE: 
A sudden release of a large amount of pressurised and/or refrigerated gas 
can result in a loss of visibility caused by condensation of atmospheric water 

or the released gas itself.  As true for all optical open path systems, this may 

induce a beam block on the Dräger Polytron Pulsar Open Path Gas Detector 

which will impair detector’s ability to detect the gas. The beam block warning 
would be activated and reported to the user. Although the scenario is rather 

unlikely, choosing shorter rather than longer path lengths when installing 

Pulsars in this application can further reduce occurrence. In environments 

where fog generated by gas leaks is a frequent problem, beam blocks should 
be taken as indication for potential hazards and the use of additional point 

detectors should be considered.

Other configurable settings in the Receiver, (such as the quantity of gas for full-
scale in the 4-20mA current loop, baseline deadband or auto zero tracking - AZT), 

are less frequently changed and are often the same for all Dräger Polytron Pulsars 
at the same site. The current values active in the Receiver can be read by selecting 

SETS

 in ‘Rx Main Menu’. A new configuration file can be written from the Hand 

Held Terminal with 

USER

 in ‘Rx Memory Menu’. To see the settings that are available 

to be sent, choose 

SETS

 in the ‘Not Connected’ menu. To change them, connect 

the Dräger Hand Held Terminal to a computer in the non-hazardous area, go to 

PC

 

in the ‘Not Connected’ menu, and run the Dräger software supplied.

AZT automatically cancels small deviations of gas reading that persist for a long 

time. The rate is set in units of LEL.m/h. Baseline Dead-Band is the threshold 
of gas readings that cause the analogue output to rise above either 4mA or the 

Warning  Current.  AZT  and  baseline  deadband  settings  should  be  chosen  while 

considering the ambient condition at the point of installation. In particular in harsh 

outdoor environments where a slow increase of gas is not possible, higher AZT and 

baseline deadband settings can be chosen. In indoor applications where small leaks 

could lead to a slow increase of gas concentrations, AZT and baseline deadband 

values must be kept at a low level. 

NOTE:

The Dräger Polytron Pulsar is supplied with default configurations as listed 
in the Specifications section of the Technical Manual. Any changes to these 
default settings are carried out as part of the commissioning process. 

Receiver AZT and Dead-Band default settings: 

Auto Zero Tracking rate

range: 0 - 12 LFLm per hour

default: 0.05* LFLm per hour

Dead-Band

range: 0 - 0.5

default: LFLm 0.3** LFLm

*AZT default values or lower comply with EN 60079-29-4:2009 and the requirements of the DNV marine 

approval (DNV except duct mount IFU).

Note: Default AZT settings on older Pulsars. This should be taken into account when replacing older units in 

harsh environments.
** Default values or lower comply with EN 60079-29-4:2009 and the requirements of the DNV marine approval 
(DNV except duct mount IFU).
Note: Default deadband settings on older Pulsars. This should be taken into account when replacing older 
units in harsh environments. 

Содержание Polytron Pulsar 2

Страница 1: ...Gas Detector en WARNING You must read understand and follow these instructions for use before you use the gas detector in order to ensure the proper operation and function of the gas detector Polytron...

Страница 2: ......

Страница 3: ...ding and strict observation of these instructions This gas detector is only to be used for the purposes specified herein Maintenance The device must be inspected and serviced by experts at regular int...

Страница 4: ...e location Choosing the path of the beam and Mechanical Installation 1 The siting of an open path gas detector is often not as critical as a point detector since the released gas only has to find its...

Страница 5: ...Polytron Pulsar 2 Open Path Gas Detector should be mounted to a stable structure free of excessive vibration Good choices would be a steel bulkhead brick wall concrete post or a rigid steel structure...

Страница 6: ...5 5 6 6 7 7 S S E E 1 1 2 2 3 3 4 4 5 5 6 6 7 7 S S E E DRAWING NO GD8 59 TITLE Connection Diagram Ex e Terminal Box OPTION 2 powered via Receiver PRODUCT GD8 ISSUE NO 1 6 24 11 2011 Not for manufact...

Страница 7: ...given in Figure 6 Place the socket components outer cap thrust washers outer seal etc onto the cable whilst ensuring that the cable armour braid is fitted between the clamp cone and sleeve Fit the con...

Страница 8: ...o turn the socket insert it should not rotate If the insert does rotate then it is not fitted correctly and requires adjustment to secure it into position Finally secure the remaining components of th...

Страница 9: ...display When aligned tighten the eight transmitter adjustment socket head screws and fully clamp Disconnect the Hand Held Terminal from the transmitter and reconnect to the receiver Figure 8 AP800 Att...

Страница 10: ...enu then select ZERO A message is displayed SAFETY WARNING Are you sure beam path is free of gas If you are sure there is no gas present select YES otherwise press any other key to abort zero Once YES...

Страница 11: ...n be written from the Hand Held Terminal with USER in Rx Memory Menu To see the settings that are available to be sent choose SETS in the Not Connected menu To change them connect the Dr ger Hand Held...

Страница 12: ...for p n 2350325 The Hand Held Terminal The Dr ger Ltd Hand Held Terminal is a robust and weatherproof unit certified for use in hazardous areas It replaces the MTL611B Communicator based on a Psion O...

Страница 13: ...ld Terminal or Communicator and has an infra red signal to a Data Wand This multiplicity of functions allows the AI500 to be used in systems with different levels of complexity In a fully engineered i...

Страница 14: ...onal regulations WARNING The Dr ger Polytron Pulsar 2 Open Path Gas Detector contains no user serviceable components In the event of suspected failure of the transmitter or receiver the suspect unit s...

Страница 15: ...ns with Safety Integrity Level SIL and any other configuration when applicable observe the Technical Manual How to Dispose of the Device From August 2005 regulations apply to the whole of the EU for t...

Страница 16: ...0 C bis 60 C IECEx Certificate Number IEC Ex SIR 04 0006 Ex d ia IIC T5 Ta 40 C to 60 C Ex d ia IIC T6 Ta 40 C to 40 C UL Classi fied Class I Div 1 Groups C D CSA NRTL C Class I Div 1 Groups C D FM AN...

Страница 17: ......

Страница 18: ...lyth Northumberland NE24 4RG United Kingdom Tel 44 1670 352 891 Fax 44 1670 544 475 www draeger com Dr ger Safety AG Co KGaA Revalstra e 1 23560 L beck Germany Tel 49 451 882 0 Fax 49 451 882 20 80 ww...

Отзывы: