Technical Data

Technical Data

Operating Limit:

-40°C to +60°C (-40°C to +140°F), 800 to 1100 hPa, 0 to 

100% rel. hum

IP rating

IP 66/67

Supply Voltage 

ATEX

18 to 30 VDC

UL, CSA

18 to 27 VDC

Power Consumption

Max. 0.95 A @ 24 V, with full heating and all source lamps 
operating. In-rush Current: 1.5A

Rx max: 5 W

Tx max: 13 W

Warm-up:

12 secs.  Beam block time during power interruptions (

 

10ms): 12 secs.

CE Marking

Devices and protective systems for use for the intended 
purpose in explosion-hazard area (Directive 94/9/EC), 
CENELEC only

Dimensions

Approx: 338 x 258 x 216 mm

Weight

6kg, 12,2 lbs, each

Regulatory Approvals

ATEX

Certificate Number SIRA 14ATEX1040

II 2(1)GD
Ex d [ia Ga] op is IIC T6 Gb

Ex tb IIIC T80°C Db
Ta = -40°C bis +40°C

II 2(1)GD
Ex d [ia Ga] op is IIC T5 Gb
Ex tb IIIC T100°C Db

Ta = -40°C bis +60°C

IECEx

Certificate Number IEC Ex SIR 04.0006   
Ex d [ia] IIC T5 (Ta -40°C to +60°C)    
Ex d [ia] IIC T6 (Ta -40°C to +40°C)

UL (Classi-

fied)

Class I, Div. 1, Groups C, D

CSA, 
NRTL/C

Class I, Div. 1, Groups C, D

FM

ANSI/FM 6325
ANSI/ISA-12.13.04

DNV

A-12526

Measuring technique 
characteristics

Infrared absorption dual band technique

Repeatability

±0.1 LELm

Linearity Error

±5% of Full Scale Deflection

Response time to t

90

With digital 
link

≤ 2 seconds

Without 
digital link

≤ 2.5 seconds

Outputs

Self configuring current sink or source. Fully linearised 4-20 

mA gas signal with Fault at 0 mA, Beam-block at 2mA, and 

a configurable Pre-warning for dirty or misaligned optics, 
broken Rx-Tx link, or first lamp failure (0 to 5 mA, default 3.5 

mA).  Over-range at 20.5 mA.  %LEL = ((I (in mA)-4 mA)/ 
16mA * (full scale)). Interrogation/diagnostics of the detector, 
locally via the Hand-Held Terminal, or remotely via 4th-wire

Storage

Temperature:

-40°C to +60°C (-40°C to +140°F)

Pressure:

700 to 1300 hPa

Humidity:

0 to 95% rel. hum

Содержание Polytron Pulsar 2

Страница 1: ...Gas Detector en WARNING You must read understand and follow these instructions for use before you use the gas detector in order to ensure the proper operation and function of the gas detector Polytron...

Страница 2: ......

Страница 3: ...ding and strict observation of these instructions This gas detector is only to be used for the purposes specified herein Maintenance The device must be inspected and serviced by experts at regular int...

Страница 4: ...e location Choosing the path of the beam and Mechanical Installation 1 The siting of an open path gas detector is often not as critical as a point detector since the released gas only has to find its...

Страница 5: ...Polytron Pulsar 2 Open Path Gas Detector should be mounted to a stable structure free of excessive vibration Good choices would be a steel bulkhead brick wall concrete post or a rigid steel structure...

Страница 6: ...5 5 6 6 7 7 S S E E 1 1 2 2 3 3 4 4 5 5 6 6 7 7 S S E E DRAWING NO GD8 59 TITLE Connection Diagram Ex e Terminal Box OPTION 2 powered via Receiver PRODUCT GD8 ISSUE NO 1 6 24 11 2011 Not for manufact...

Страница 7: ...given in Figure 6 Place the socket components outer cap thrust washers outer seal etc onto the cable whilst ensuring that the cable armour braid is fitted between the clamp cone and sleeve Fit the con...

Страница 8: ...o turn the socket insert it should not rotate If the insert does rotate then it is not fitted correctly and requires adjustment to secure it into position Finally secure the remaining components of th...

Страница 9: ...display When aligned tighten the eight transmitter adjustment socket head screws and fully clamp Disconnect the Hand Held Terminal from the transmitter and reconnect to the receiver Figure 8 AP800 Att...

Страница 10: ...enu then select ZERO A message is displayed SAFETY WARNING Are you sure beam path is free of gas If you are sure there is no gas present select YES otherwise press any other key to abort zero Once YES...

Страница 11: ...n be written from the Hand Held Terminal with USER in Rx Memory Menu To see the settings that are available to be sent choose SETS in the Not Connected menu To change them connect the Dr ger Hand Held...

Страница 12: ...for p n 2350325 The Hand Held Terminal The Dr ger Ltd Hand Held Terminal is a robust and weatherproof unit certified for use in hazardous areas It replaces the MTL611B Communicator based on a Psion O...

Страница 13: ...ld Terminal or Communicator and has an infra red signal to a Data Wand This multiplicity of functions allows the AI500 to be used in systems with different levels of complexity In a fully engineered i...

Страница 14: ...onal regulations WARNING The Dr ger Polytron Pulsar 2 Open Path Gas Detector contains no user serviceable components In the event of suspected failure of the transmitter or receiver the suspect unit s...

Страница 15: ...ns with Safety Integrity Level SIL and any other configuration when applicable observe the Technical Manual How to Dispose of the Device From August 2005 regulations apply to the whole of the EU for t...

Страница 16: ...0 C bis 60 C IECEx Certificate Number IEC Ex SIR 04 0006 Ex d ia IIC T5 Ta 40 C to 60 C Ex d ia IIC T6 Ta 40 C to 40 C UL Classi fied Class I Div 1 Groups C D CSA NRTL C Class I Div 1 Groups C D FM AN...

Страница 17: ......

Страница 18: ...lyth Northumberland NE24 4RG United Kingdom Tel 44 1670 352 891 Fax 44 1670 544 475 www draeger com Dr ger Safety AG Co KGaA Revalstra e 1 23560 L beck Germany Tel 49 451 882 0 Fax 49 451 882 20 80 ww...

Отзывы: