Installation of the Dräger Flame Detector 5000

Equation 2: Characteristic Impedence Calculation

L

= Cable Impedance (mH)

C

= Cable Capacitance (

—

F)

Zo

= Characteristic Impedance (Ohms)

C

L

)

(

Zo

y

 

ȍ

The RS485 communications cabling should be a twisted pair stranded cable with an overall screen.  Where multi-
core cables are used then individual screened twisted pairs are recommended.  The cable should have the following 
characteristics:

RS485 Communications Cable Characteristics

Cable

Characteristic

Characteristic 

Impedance

Capacitance

Conductor 

Resistance

Attenuation @ 1MHz

Inductance

Nominal

120

Ω

50nf/Km

- -

- -

- -

Absolute Limit

90

Ω

 to 120

Ω

100nf/Km

120

Ω

12dB

0.7mH/Km

The maximum cable length is dependent on the cable manufacturer’s attenuation speci

fi

 cation, which is approximately 

proportional to conductor size. The characteristic impedance of a transmission line is the same as for the video 
above.

Installation Check-Points

Experience has shown that poor installation and commissioning practice may result in an unreliable 

fi

 re detection system 

that is prone to malfunction, unwanted alarms, and at the same time fails to meet the site performance targets.  Before 
installing the detector it is important to take into account where it is to be located and how it is to be mounted. 

Mechanical Installation

When locating the Dräger Flame Detector 5000 consideration should be given to maintenance access to the 

• 

detector.  
The detector mounting should be secure and vibration free.

• 

It is advisable to check the detection locations, prior to fabrication of the mounting supports, as changes are 

• 

frequently made during construction at site which can a

 ect detector coverage.

The installation should allow for easy detector removal for maintenance or repair.

• 

The detector should be 

fi

 xed to a stable supporting structure using the mounting bracket provided.  The supporting 

1. 

structure must allow for horizontal adjustment of the detector orientation.  The support structure should be in place 
prior to detector installation.  
The threaded 

fl

 ame path of the enclosure cover and body must be protected from damage during installation.  Any 

2. 

such damage can destroy the validity of the enclosure.
The detector electronics shall be protected from mechanical damage and external sources of EMI such as X-rays, 

3. 

RFI and electrostatic discharge.
Fit the mounting bracket to the support structure using 8mm bolts (not provided).  The detector (bracket) should 

4. 

be oriented to provide the desired coverage.
The hex head bolts should be 

fi

 tted to the enclosure body prior to mounting to the bracket. The detector enclosure 

5. 

Содержание Flame 5000

Страница 1: ...me Detector Technical Manual en Technical Manual 2 34 WARNING You must read understand and follow these instructions for use before you use the flame detector in order to ensure the proper operation a...

Страница 2: ...ents For Your Safety 3 Intended Use 6 Operation 20 Maintenance 21 Fault Finding 23 Technical Specifications 24 Approvals 26 Accessories 27 Supplier s Declaration of Conformity 28 Approval Certificates...

Страница 3: ...r Maintenance Use in areas subject to explosion hazards The Dr ger Flame Detector 5000 is certified for and intended for use in potentially hazardous areas Equipment and components which are used in e...

Страница 4: ...ead and taken into consideration when specifying cable core sizes to be used In addition local regulations should be considered before wiring the system and installation should be completed by appopri...

Страница 5: ...These words and the hazard they describe are as follows DANGER Indicates an imminently hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a potentially...

Страница 6: ...or Video Surveillance camera or as a combined unit Detector Overview The detector unit is comprised of two primary components the detector enclosure and the detector assembly The detector assembly sh...

Страница 7: ...view The detectors should be aligned to view the intended hazard taking into account any obstruction and congestion Software analysis of the actual detector coverage may be required to ensure adequat...

Страница 8: ...r has a horizontal field of view of 90 and a vertical field of view of 65 The location and orientation of the detector in relation to the protected area determines the actual footprint Achieving the d...

Страница 9: ...from local electrical interference sources Ensure su cient detection to achieve adequate coverage for all likely hazards Minimise exposure to contamination of the detector face plate Ensure ease of ma...

Страница 10: ...ear the exhaust Optical Contamination There are many sources of contamination such as oil water deluge water rain and sea spray snow ice and internal misting The design of the detector incorporates an...

Страница 11: ...Installation of the Dr ger Flame Detector 5000 11 Detector mounting bracket Detector mounting bracket dimensions Dimensions shown in Millimeters...

Страница 12: ...uld be taken to ensure that the PC s and Panel s power supply are at the same ground potential Even small di erences in earth potentials can cause an earth fault current to flow resulting in video cor...

Страница 13: ...ion links are mounted in the rear section of the enclosure and are accessible by removal of the rear cover from the enclosure The electronics and the field terminals are separated so that there is no...

Страница 14: ...ALRM 12 Alarm Resistor ALRM 13 Alarm Resistor 485B 14 RS485 termination Ve If the detector is connected in the above manner and if a fire alarm is signalled with the alarm resistor connected between t...

Страница 15: ...detector is connected in the above manner if a fire alarm is signalled then the 4 20mA outputs generate 18mA if a fault develops the 4 20mA signal indicates 0 or 2 mA dependant on the fault see table...

Страница 16: ...e one detector Cable Selection The installation local regulations and standards determine the overall cable specification This section specifies suitable cable characteristics to ensure correct operat...

Страница 17: ...he maximum cable length increasing the supply voltage up to a maximum of 32V can dramatically increase cable length Prudence dictates that a cable is selected with a lower resistance than calculated a...

Страница 18: ...take into account where it is to be located and how it is to be mounted Mechanical Installation When locating the Dr ger Flame Detector 5000 consideration should be given to maintenance access to the...

Страница 19: ...for commissioning 1 The threaded flame path of the enclosure cover and body must be protected from damage during installation Any 2 such damage can destroy the validity of the enclosure The electronic...

Страница 20: ...and aware of what actions to take in the event of a fire being detected Status Indicators The detector LED indicator is used to reveal the Dr ger Flame Detector 5000 s current state as shown below LED...

Страница 21: ...faceplate this should be carried out at least every 6 months Detectors that require maintenance should be taken o line and inhibited Detectors which require to be opened up will need to be isolated el...

Страница 22: ...cover must be screwed on to a minimum of 5 full turns or until fully tight and secured using the locking screw provided The remaining points cover detector function testing this should be done on a c...

Страница 23: ...cult Check the most obvious possible causes first Work systematically through the problem Keep good notes on the original problem each step taken and the results observed Power Supply If the detector...

Страница 24: ...2 5 kg 5 5 lbs 2 8 kg 6 2 lbs Stainless Steel ver Dimensions L x D 220 x 100 mm 9 x 4 inches Cable Entries M20 M25 or 3 4 NPT Terminal Wire Size 2 5mm2 Ingress Protection IP 66 NEMA 4X Temperature Hum...

Страница 25: ...stem Initialisation occurs RS 485 Transceiver Line Termination Resistor 120 Driver Di erential 1 5 VDC Driver Fan Out 0 3 UL Receiver Common Mode Input Range 7 to 12 VDC Receiver Input Threshold 0 2 V...

Страница 26: ...61000 4 6 1996 A1 2001 10V rms 100 80 modulation Response Time min 4 seconds upto 30 seconds max Operating Distance 2 44 m Hazardous Area Label This label shows the certification and conditions of the...

Страница 27: ...ideo mode Stainless Steel 420 93 23 Dr ger Flame 5000 M25 4 20mA PAL video mode Stainless Steel 420 93 35 Dr ger Flame 5000 M25 Relay NTSC video mode Stainless Steel 420 93 36 Dr ger Flame 5000 M20 4...

Страница 28: ...Supplier s Declaration of Conformity...

Страница 29: ...Approval Certificates...

Страница 30: ......

Страница 31: ......

Страница 32: ......

Страница 33: ......

Страница 34: ......

Страница 35: ...Kingdom Tel 44 0 1670 352 891 Fax 44 0 1670 540 033 www draeger com 4209319_01_2008_en Draeger Safety UK Ltd 3rd Edition February 2008 Subject to alteration Distributed in the US by Draeger Safety In...

Отзывы: