Intended Use
7
WARNING
Do not open the enclosure in the presence of an explosive
atmostphere.
!
WARNING
All permits and proper site procedure and practises must be
followed and the equipment must be isolated from the power
supply before opening the enclosure in the field.
!
Field of View
The sensor can detect
fi
res of 0.1m
2
or greater, at 44m within a 90° horizontal
fi
eld of view. The detector will only
respond to visible
fl
ames within the
fi
eld of view. Hence the detector will not to certain common sources of false alarms
such as re
fl
ected
fl
are radiation. This also reduces the likelihood of cross-propagation of alarms caused by
fi
res or
combustion products of
fi
res burning out with the
fi
eld of view.
The detectors should be aligned to view the intended hazard taking into account any obstruction and congestion.
Software analysis of the actual detector coverage may be required to ensure adequate coverage of the hazards. This
analysis can also be used to optimise the number of detectors and the loop con
fi
guration.
Visual Flame Detector does not have a traditional cone of vision like other IR
fl
ame detector’s. The detector’s
fi
eld of
view is a rectangular pyramidal shape and represents a radial projection of the detector’s rectangular sensing element.
The illustrations below show the Field of View and range for a
fi
re of 0.1m
2
.
50m
30m
40m
20m
10m
5m
0
˚
15
˚
30
˚
45
˚
-15
˚
-30
˚
-45
˚
60
˚
-60
˚
-75
˚
-90
˚
-105
˚
-120
˚
-135
˚
-150
˚
-165
˚
180
˚
165
˚
150
˚
135
˚
120
˚
105
˚
90
˚
75
˚
50m
30m
40m
20m
10m
5m
0
˚
15
˚
30
˚
45
˚
-15
˚
-30
˚
-45
˚
60
˚
-60
˚
-75
˚
-90
˚
-105
˚
-120
˚
-135
˚
-150
˚
-165
˚
180
˚
165
˚
150
˚
135
˚
120
˚
105
˚
90
˚
75
˚
Horizontal Field of View
Vertical Field of View
Содержание Flame 5000
Страница 28: ...Supplier s Declaration of Conformity...
Страница 29: ...Approval Certificates...
Страница 30: ......
Страница 31: ......
Страница 32: ......
Страница 33: ......
Страница 34: ......