background image

22

Fault Finding

Check the ‘O’ ring seal on the enclosure cover to ensure that it is not damaged or perished; replace as required.  

• 

NOTE: That the ingress protection is compromised if the seal is not correct.
Clean the enclosure faceplate (inside) with a mild detergent solution and a soft cloth until the window is clear of 

• 

all contamination.  Wash the window thoroughly with clean water and dry with a clean lint free cloth or tissue.
No-setting waterproof grease should be evenly applied to the 

fl

 ame path on both the enclosure cover and body.

• 

Clean the detector lens. This should be done with a soft, dry and clean cloth.  Avoid touching the electronics.

• 

Clean the detector enclosure faceplate. Use a degreasing agent on the outside in order to remove deposits.

• 

Visually inspect detector electronics and inside the enclosure body for any sign of damage or moisture, replace 

• 

or rectify as required.
The enclosure cover must be screwed on to a minimum of 5 full turns or until fully tight and secured using the 

• 

locking screw provided.

The remaining points cover detector function testing, this should be done on a continuous basis or every 6 months 
depending on the environment.

Reinstate the detector back into service.

• 

Ensure that ‘inhibits’ are applied, then, using the Dräger FS-5000, function test the detector. Note the detector 

• 

LED indicator, within the detector housing, changes colour to RED.  Check the complete display system for 
correct function and indication.

Functional Testing

The detector can be function tested using the Dräger FS-5000, which has been speci

fi

 cally designed to provide a 

convenient means of 

fi

 eld testing the detector.  

CAUTION

Use only Draeger approved parts and accessories with this 
equipment.

!

CAUTION

Do not attempt to replace the window as the glass and the 
front cover are individually matched pairs to me the stringent 
requirements of the hazardous area certification.

!

CAUTION

To maintain safety standards, commissioning and regular 
maintenance should be performed by qualified personel.

!

Содержание Flame 5000

Страница 1: ...me Detector Technical Manual en Technical Manual 2 34 WARNING You must read understand and follow these instructions for use before you use the flame detector in order to ensure the proper operation a...

Страница 2: ...ents For Your Safety 3 Intended Use 6 Operation 20 Maintenance 21 Fault Finding 23 Technical Specifications 24 Approvals 26 Accessories 27 Supplier s Declaration of Conformity 28 Approval Certificates...

Страница 3: ...r Maintenance Use in areas subject to explosion hazards The Dr ger Flame Detector 5000 is certified for and intended for use in potentially hazardous areas Equipment and components which are used in e...

Страница 4: ...ead and taken into consideration when specifying cable core sizes to be used In addition local regulations should be considered before wiring the system and installation should be completed by appopri...

Страница 5: ...These words and the hazard they describe are as follows DANGER Indicates an imminently hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a potentially...

Страница 6: ...or Video Surveillance camera or as a combined unit Detector Overview The detector unit is comprised of two primary components the detector enclosure and the detector assembly The detector assembly sh...

Страница 7: ...view The detectors should be aligned to view the intended hazard taking into account any obstruction and congestion Software analysis of the actual detector coverage may be required to ensure adequat...

Страница 8: ...r has a horizontal field of view of 90 and a vertical field of view of 65 The location and orientation of the detector in relation to the protected area determines the actual footprint Achieving the d...

Страница 9: ...from local electrical interference sources Ensure su cient detection to achieve adequate coverage for all likely hazards Minimise exposure to contamination of the detector face plate Ensure ease of ma...

Страница 10: ...ear the exhaust Optical Contamination There are many sources of contamination such as oil water deluge water rain and sea spray snow ice and internal misting The design of the detector incorporates an...

Страница 11: ...Installation of the Dr ger Flame Detector 5000 11 Detector mounting bracket Detector mounting bracket dimensions Dimensions shown in Millimeters...

Страница 12: ...uld be taken to ensure that the PC s and Panel s power supply are at the same ground potential Even small di erences in earth potentials can cause an earth fault current to flow resulting in video cor...

Страница 13: ...ion links are mounted in the rear section of the enclosure and are accessible by removal of the rear cover from the enclosure The electronics and the field terminals are separated so that there is no...

Страница 14: ...ALRM 12 Alarm Resistor ALRM 13 Alarm Resistor 485B 14 RS485 termination Ve If the detector is connected in the above manner and if a fire alarm is signalled with the alarm resistor connected between t...

Страница 15: ...detector is connected in the above manner if a fire alarm is signalled then the 4 20mA outputs generate 18mA if a fault develops the 4 20mA signal indicates 0 or 2 mA dependant on the fault see table...

Страница 16: ...e one detector Cable Selection The installation local regulations and standards determine the overall cable specification This section specifies suitable cable characteristics to ensure correct operat...

Страница 17: ...he maximum cable length increasing the supply voltage up to a maximum of 32V can dramatically increase cable length Prudence dictates that a cable is selected with a lower resistance than calculated a...

Страница 18: ...take into account where it is to be located and how it is to be mounted Mechanical Installation When locating the Dr ger Flame Detector 5000 consideration should be given to maintenance access to the...

Страница 19: ...for commissioning 1 The threaded flame path of the enclosure cover and body must be protected from damage during installation Any 2 such damage can destroy the validity of the enclosure The electronic...

Страница 20: ...and aware of what actions to take in the event of a fire being detected Status Indicators The detector LED indicator is used to reveal the Dr ger Flame Detector 5000 s current state as shown below LED...

Страница 21: ...faceplate this should be carried out at least every 6 months Detectors that require maintenance should be taken o line and inhibited Detectors which require to be opened up will need to be isolated el...

Страница 22: ...cover must be screwed on to a minimum of 5 full turns or until fully tight and secured using the locking screw provided The remaining points cover detector function testing this should be done on a c...

Страница 23: ...cult Check the most obvious possible causes first Work systematically through the problem Keep good notes on the original problem each step taken and the results observed Power Supply If the detector...

Страница 24: ...2 5 kg 5 5 lbs 2 8 kg 6 2 lbs Stainless Steel ver Dimensions L x D 220 x 100 mm 9 x 4 inches Cable Entries M20 M25 or 3 4 NPT Terminal Wire Size 2 5mm2 Ingress Protection IP 66 NEMA 4X Temperature Hum...

Страница 25: ...stem Initialisation occurs RS 485 Transceiver Line Termination Resistor 120 Driver Di erential 1 5 VDC Driver Fan Out 0 3 UL Receiver Common Mode Input Range 7 to 12 VDC Receiver Input Threshold 0 2 V...

Страница 26: ...61000 4 6 1996 A1 2001 10V rms 100 80 modulation Response Time min 4 seconds upto 30 seconds max Operating Distance 2 44 m Hazardous Area Label This label shows the certification and conditions of the...

Страница 27: ...ideo mode Stainless Steel 420 93 23 Dr ger Flame 5000 M25 4 20mA PAL video mode Stainless Steel 420 93 35 Dr ger Flame 5000 M25 Relay NTSC video mode Stainless Steel 420 93 36 Dr ger Flame 5000 M20 4...

Страница 28: ...Supplier s Declaration of Conformity...

Страница 29: ...Approval Certificates...

Страница 30: ......

Страница 31: ......

Страница 32: ......

Страница 33: ......

Страница 34: ......

Страница 35: ...Kingdom Tel 44 0 1670 352 891 Fax 44 0 1670 540 033 www draeger com 4209319_01_2008_en Draeger Safety UK Ltd 3rd Edition February 2008 Subject to alteration Distributed in the US by Draeger Safety In...