background image

Installation of the Dräger Flame Detector 5000

13

then care should be taken to ensure the cable armour braid provides a suitable earth or that the enclosure earth stud 
(external) is separately connected to a suitable earth point using a single core 4mm

2

 earth cable.  

All detector cable screens should be connected to the local clean earth at the control panel.  The screens (and twisted 
pairs) should be maintained to within 1” (25.4mm) of the terminations at the detector, within all junction boxes and at 
the control panel. Where unscreened cables are used for panel wiring, then all cables must be suitably twisted into 
pairs and video cables should be segregated from other signal sources.

Power Supply

The detector requires an absolute minimum supply voltage of 18V, as measured at the detector terminals.  The system 
power supply voltage and power distribution should be arranged such that on the longest cable run the detector(s) 
has a supply voltage of greater than 18V.  All detectors must share a common 0V supply.  In distributed systems with 
multiple DC-DC power supply units all 0V supplies must be connected together.  Where this is not possible the RS485 
and Video signals may need to be galvanically isolated, such as with a 

fi

 bre optic transceiver.

To prevent RS485 communications or video corruption the maximum voltage drop on the 0V return must not exceed 
+4V or -1V.   Voltages greater than these will exceed the common mode input range of the RS485 and Video drivers.  
Power supply cable selection is described in section: Detector Power Supply Cabling

Detector Wiring Terminals

The wiring terminals and con

fi

 guration links are mounted in the rear section of the enclosure and are accessible by 

removal of the rear cover from the enclosure. The electronics and the 

fi

 eld terminals are separated so that there is no 

reason to remove the electronics in order to access the 

fi

 eld terminals. This is to prevent damage to the electronics 

when the unit is being connected to the 

fi

 eld cable. 

The device is supplied in one of two options: 

As a unit that provides relay contacts for the alarm and fault circuits across which alarm and end of line resistors 

1. 

are 

fi

 tted. When the unit is disconnected from the 

fi

 re panel, the output from terminals A and B switch to the 

RS485 protocol; this allows a Dräger Engineer access to the detectors con

fi

 guration from the local equipment 

room. 
As a unit that provides 4-20mA output. When the unit is disconnected from the 

fi

 re panel, the output from terminals 

2. 

A and B switch to the RS485 protocol; again this allows a Dräger Engineer access to the detectors con

fi

 guration 

from the local equipment room.

This may then be used to access the software revision within the detector via the ‘get settings’ menu as described in 
the ‘RS485 Communications’ section. 

The alarm relay and the 4-20mA output is factory selectable for latching and non-latching operation. If the latching 
mode is selected then if an alarm is generated the detector will remain in alarm until the power supply to the unit 
is interrupted.  If the non-latching operation is selected then the detector will remain in alarm for a minimum of 15 
seconds, the 

fi

 re panel to which the detector is connected must be capable of latching the alarm and there is no need 

to interrupt the power supply to the detector to reset the alarm. Local authority having jurisdiction approval is required 
for connection to FM Approved 

fi

 re alarm control units.  

Содержание Flame 5000

Страница 1: ...me Detector Technical Manual en Technical Manual 2 34 WARNING You must read understand and follow these instructions for use before you use the flame detector in order to ensure the proper operation a...

Страница 2: ...ents For Your Safety 3 Intended Use 6 Operation 20 Maintenance 21 Fault Finding 23 Technical Specifications 24 Approvals 26 Accessories 27 Supplier s Declaration of Conformity 28 Approval Certificates...

Страница 3: ...r Maintenance Use in areas subject to explosion hazards The Dr ger Flame Detector 5000 is certified for and intended for use in potentially hazardous areas Equipment and components which are used in e...

Страница 4: ...ead and taken into consideration when specifying cable core sizes to be used In addition local regulations should be considered before wiring the system and installation should be completed by appopri...

Страница 5: ...These words and the hazard they describe are as follows DANGER Indicates an imminently hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a potentially...

Страница 6: ...or Video Surveillance camera or as a combined unit Detector Overview The detector unit is comprised of two primary components the detector enclosure and the detector assembly The detector assembly sh...

Страница 7: ...view The detectors should be aligned to view the intended hazard taking into account any obstruction and congestion Software analysis of the actual detector coverage may be required to ensure adequat...

Страница 8: ...r has a horizontal field of view of 90 and a vertical field of view of 65 The location and orientation of the detector in relation to the protected area determines the actual footprint Achieving the d...

Страница 9: ...from local electrical interference sources Ensure su cient detection to achieve adequate coverage for all likely hazards Minimise exposure to contamination of the detector face plate Ensure ease of ma...

Страница 10: ...ear the exhaust Optical Contamination There are many sources of contamination such as oil water deluge water rain and sea spray snow ice and internal misting The design of the detector incorporates an...

Страница 11: ...Installation of the Dr ger Flame Detector 5000 11 Detector mounting bracket Detector mounting bracket dimensions Dimensions shown in Millimeters...

Страница 12: ...uld be taken to ensure that the PC s and Panel s power supply are at the same ground potential Even small di erences in earth potentials can cause an earth fault current to flow resulting in video cor...

Страница 13: ...ion links are mounted in the rear section of the enclosure and are accessible by removal of the rear cover from the enclosure The electronics and the field terminals are separated so that there is no...

Страница 14: ...ALRM 12 Alarm Resistor ALRM 13 Alarm Resistor 485B 14 RS485 termination Ve If the detector is connected in the above manner and if a fire alarm is signalled with the alarm resistor connected between t...

Страница 15: ...detector is connected in the above manner if a fire alarm is signalled then the 4 20mA outputs generate 18mA if a fault develops the 4 20mA signal indicates 0 or 2 mA dependant on the fault see table...

Страница 16: ...e one detector Cable Selection The installation local regulations and standards determine the overall cable specification This section specifies suitable cable characteristics to ensure correct operat...

Страница 17: ...he maximum cable length increasing the supply voltage up to a maximum of 32V can dramatically increase cable length Prudence dictates that a cable is selected with a lower resistance than calculated a...

Страница 18: ...take into account where it is to be located and how it is to be mounted Mechanical Installation When locating the Dr ger Flame Detector 5000 consideration should be given to maintenance access to the...

Страница 19: ...for commissioning 1 The threaded flame path of the enclosure cover and body must be protected from damage during installation Any 2 such damage can destroy the validity of the enclosure The electronic...

Страница 20: ...and aware of what actions to take in the event of a fire being detected Status Indicators The detector LED indicator is used to reveal the Dr ger Flame Detector 5000 s current state as shown below LED...

Страница 21: ...faceplate this should be carried out at least every 6 months Detectors that require maintenance should be taken o line and inhibited Detectors which require to be opened up will need to be isolated el...

Страница 22: ...cover must be screwed on to a minimum of 5 full turns or until fully tight and secured using the locking screw provided The remaining points cover detector function testing this should be done on a c...

Страница 23: ...cult Check the most obvious possible causes first Work systematically through the problem Keep good notes on the original problem each step taken and the results observed Power Supply If the detector...

Страница 24: ...2 5 kg 5 5 lbs 2 8 kg 6 2 lbs Stainless Steel ver Dimensions L x D 220 x 100 mm 9 x 4 inches Cable Entries M20 M25 or 3 4 NPT Terminal Wire Size 2 5mm2 Ingress Protection IP 66 NEMA 4X Temperature Hum...

Страница 25: ...stem Initialisation occurs RS 485 Transceiver Line Termination Resistor 120 Driver Di erential 1 5 VDC Driver Fan Out 0 3 UL Receiver Common Mode Input Range 7 to 12 VDC Receiver Input Threshold 0 2 V...

Страница 26: ...61000 4 6 1996 A1 2001 10V rms 100 80 modulation Response Time min 4 seconds upto 30 seconds max Operating Distance 2 44 m Hazardous Area Label This label shows the certification and conditions of the...

Страница 27: ...ideo mode Stainless Steel 420 93 23 Dr ger Flame 5000 M25 4 20mA PAL video mode Stainless Steel 420 93 35 Dr ger Flame 5000 M25 Relay NTSC video mode Stainless Steel 420 93 36 Dr ger Flame 5000 M20 4...

Страница 28: ...Supplier s Declaration of Conformity...

Страница 29: ...Approval Certificates...

Страница 30: ......

Страница 31: ......

Страница 32: ......

Страница 33: ......

Страница 34: ......

Страница 35: ...Kingdom Tel 44 0 1670 352 891 Fax 44 0 1670 540 033 www draeger com 4209319_01_2008_en Draeger Safety UK Ltd 3rd Edition February 2008 Subject to alteration Distributed in the US by Draeger Safety In...

Отзывы: