85
the DSCP Poller after a certain period
of time.
Check battery power. Make sure signal
is not physically obstructed.
28
Wireless
Sensor Power
Fault
Power to DSCP unit is shorting or
cannot provide enough current causing
a fault with the sensor power.
Check sensor wiring for any faulty
connections or shortened cables.
29
Wireless
Sensor Power
Low
DSCP unit is not providing enough
power to the sensors.
Check sensor wiring for any faulty
connections or shortened cables.
30
Wireless
Sensor Update
This unit has received a sensor reading
update from a wireless device.
This alarm is normal and is used to log
wireless activity.
33
Power Up
The unit has just come-online. The set
alarm condition is followed immediately
by a clear alarm condition.
Seeing this alarm is normal if the unit
is powering up.
34
PPP Backup
Mode
The unit's Backup PPP mode is
currently in use.
PPP Backup mode comes on when the
ethernet link goes down. Check the
ethernet for connectivity.
35
Server Restore Manual Server Shutdown/Restore
process is in progress.
Server shutdown is active when Manual
Shutdown/Restore is in progress.Wait
for shutdown/restore process to finish.
36
Lost
Provisioning
The internal NVRAM may be damaged.
The unit is using default configuration
settings.
Use Web or latest version of NGEditG5
to configure unit. Power cycle to see if
alarm goes away. May require RMA.
Table 14.1.1.A.
System Alarms Descriptions
Note:
Table 14.1.1.A. continues on following pages.
Содержание NetGuardian 832A
Страница 9: ...4 Hardware kit containing a WAGO connector ...
Страница 34: ...29 right ...
Страница 39: ...34 Fig 6 9 1 Optional 66 block pinout for Discretes 1 24 ...
Страница 40: ...35 Fig 6 9 2 Optional 66 block pinout for Analogs 1 8 Discretes 25 32 Relays 1 8 ...
Страница 50: ...45 ...
Страница 73: ...68 13 2 8 DSCP Configuration Configure your Serial Data Ports through the Edit Ports screen ...
Страница 104: ...99 ...
Страница 105: ...100 ...
Страница 106: ...101 ...