48
Fig. 6.13.2.
Jumper settings for analog alarm inputs and control relays
For control relay jumpers, the open position corresponds to normally open operation, and the closed
position corresponds to normally closed operation. See Figure 6.13.2.
Note:
Default settings may be different if you ordered a special configuration NetGuardian.
Bypassing Password
6.15
1. Power down the unit by removing the power cable or fuse
2. Remove screw from the top access panel (The same panel that is used to access the controls. See
picture in previous section)
3. Rotate the panel to expose the Dip switches
4. Set dip switch 1 of the 4 position dip switches to the ON position. Refer to fig 6.13.1.
5. Power up the unit
6. The default password "dpstelecom" will now be accepted by the unit
7. In the Edit->Logon page, change the logon password to "dpstelecom" or another desired password
8. Power down the unit and set dip switch 1 to the OFF position
9. Reapply power to the unit