6.6.7 Analog Dipswitches
The analogs are controlled by the dipswitches accessible via the top sliding panel. For milliamp sensor
operation (current loop), turn the dipswitch on by placing it in the up (ON) position. For voltage
operation, place the dipswitch in the down (OFF) position.
You can access the analog dipswitches via the sliding hatch panel on top of the unit
WARNING: Do not put the dipswitches in the upward, ON position (current loop mode)
unless you are sure of the analog setting. Having the dipswitch on puts a 250 ohm
resistor across the input lines. Any voltage beyond 5V or 20 mA will damage
components.