68
System Alarms
15.3
Display
Points
Alarm Point
Description
Solution
1
33
Default
configuration
The internal NVRAM may be damaged.
The unit is using default configuration
settings.
Login to the NetGuardian's web browser
and configure the unit. Power cycle to see
if the alarm clears.
34
DCP poller
inactive
The NetGuardian is configured to listen for
DCP polls but has not received a poll in
over 5 minutes.
Check if unit can ping T/Mon or disable if
not in use.
39
SNMP
community error
Community string does not match your
SNMP master's community string.
Verify both community strings to make
sure they match.
41
Notification 1
failed
A notification 1 event, such as a page or
email, was unsuccessful.
Verify that you can ping both devices.
42
Notification 2
failed
A notification 2 event, such as a page or
email, was unsuccessful.
Use RPT filter debug to help diagnose
notification problems.
43
Notification 3
failed
A notification 3 event, such as a page or
email, was unsuccessful.
Use RPT filter debug to help diagnose
notification problems.
44
Notification 4
failed
A notification 4 event, such as a page or
email, was unsuccessful.
Use RPT filter debug to help diagnose
notification problems.
45
Notification 5
failed
A notification 5 event, such as a page or
email, was unsuccessful.
Use RPT filter debug to help diagnose
notification problems.
46
Notification 6
failed
A notification 6 event, such as a page or
email, was unsuccessful.
Use RPT filter debug to help diagnose
notification problems.
47
Notification 7
failed
A notification 7 event, such as a page or
email, was unsuccessful.
Use RPT filter debug to help diagnose
notification problems.
48
Notification 8
failed
A notification 8 event, such as a page or
email, was unsuccessful.
Use RPT filter debug to help diagnose
notification problems.
49
NTP failed
Communication with Network Time Server
has failed.
Try pinging the Network Time Server’s IP
Address as it is configured. If the ping
test is successful, then check the port
setting and verify the port is not being
blocked on your network.
50
Timed Tick
Toggles state at constant rate as
configured by the Timed Tick timer
variable. Useful in testing integrity of
SNMP trap alarm reporting.
To turn the feature off, set the Timed Tick
timer to 0.
51
Dynamic
memory full
Not expected to occur.
Call DPS Tech Support (559) 454-1600.
52
Unit reset
Unit has rebooted.
If unintentional, call DPS Tech Support:
(559) 454-1600.
55
TRIP error
Not expected to occur.
Make sure Trip ID on the NetGuardian unit
matches the Trip ID on T/Mon for the unit.
If they match, call DPS Tech Support (559)
454-1600.
56
No dial tone
Issue with connectivity.
Check cable. If cable is securely attached,
call DPS Tech Support (559) 454-1600.
57
Modem failed
Indicates an error has occurred during
Modem initialization.
Attempt to reboot the unit. If the problem
persists, call DPS Tech Support (559) 454-
1600.
System Alarms Display Map
Содержание D-PK-NGDLT
Страница 5: ...General FAQs 16 1 73 SNMP FAQs 16 2 74 Technical Support 17 75 End User Lisence Agreement 18 76...
Страница 6: ......
Страница 8: ...2 and other summary status...
Страница 42: ...36 Fig 11 8 1 View the status of System Alarms from the Monitor System Alarms menu...
Страница 83: ...77...
Страница 84: ......