48
12.7.1 Basic Configuration
Fig. 12.7.1.1
The Provisioning > Alarms menu
Alarms
Id
Alarm Id number
Description
User-definable description for the discrete alarm input.
Rev (Reverse)
Reverse: Check this box to reverse the polarity of the alarm point. Left un-checked,
this means a normally-open contact closure is an alarm. When polarity is reversed, a
normally-closed alarm point is clear when closed.
Notification
Devices
Check which notification device(s), 1 through 8, you want to send alarm notifications
for that alarm point.