additional D-Wire Sensors, set up the internal sensor.
12.11.2Advanced Configuration
To access the
Details
configuration screen, click the
Details>>
text on the right of the
Description
cell.
Fig.12.11.2.1
The Provisioning > Sensors menu after clicking Details>> on Sensor 3
From the
Details
configuration screen, you can now select which temperature units you want to use, define
alarm "set" and "clear" descriptions, and define Qualification settings.
Sensors (Details>>)
Record Freq
The amount of time, in minutes(min) or seconds (s), between each recorded
sensor value.
Deadband
The amount (in native units) that the channel needs to go above or below a
threshold in order to cause an alarm.
On set
User-definable description (condition) that will appear for the temperature
alarm on Set. Example: "Alarm"
On clear
User-definable description (condition) that will appear for the temperature
alarm Clear. Example: "Clear"
Qual. Time
(Qualification Time)
The length of time that must pass, without interruption, in order for the
condition to be considered an Alarm or a Clear.
Qual. Type
(Qualification Type)
Allows you to choose whether you want to apply the Qualification Time to
the alarm Set, Clear, or Both.
Units
User-definable display units between Fahrenheit and Celsius temperatures.
F = Fahrenheit
C = Celsius
Thresholds
These settings are used to indicate the severity of the alarm depending on
which threshold values have been passed. Enter values for Major Under
(MjU0, Minor Under (MnU), Minor Over (MnO) and Major Over (MjO).