56
Controls
11.8
The NetGuardian's 2-18 control relays can be configured in the
Provisioning
>
Controls
menu. You
can enter your own description for these relays and designate them to a notification device(s).
Fig. 11.17
The Provisioning > Controls screen
Basic Controls Configuration
ID
ID number for the control relay.
Description
User-definable description for the NetGuardian's control relay.
Notification Devices
Check which notification device(s), 1 through 8, you want to send alarm
notifications for the control relay.
Derived Description
Control relays and virtual alarms can be created with a derived formula and
tested with the Parse button. See below for more information.
Momentary Time
Control on time (in milliseconds) when you execute the MOM command.
Max limit of 600 seconds.
Derived controls and alarms can be created from derived formulas using the following operations:
_OR
: Set the current operation to OR.
_AN
: Set the current operation to AND.
_XR
: Set the current operation to XOR.
D
: Tag to change the active display number.
.
: Used like a comma to delimit numbers.
-
: Used to specify a range of points.
Spaces included here are for readability purposes only.
!
Hot Tip!
·
Precedence of the operations are always left to right.
·
All number references can either be one or two digits.
Содержание D-PK-NG216
Страница 13: ...9 Fig 4 2 Fig 4 3...
Страница 18: ...14 Fig 5 7 Amphenol connector pinout...
Страница 20: ...16 Fig 5 9 Optional 66 block connector pinout for controls...
Страница 40: ...36 Fig 10 3...
Страница 43: ...39 Fig 10 8...
Страница 88: ...84...
Страница 98: ......