13
Telco Connection
5.4
The NetGuardian 216 G4 features an RJ11 Telco port on the back of the unit. This port is used for dial-
up notification via your cell phone and alphanumeric pager.
Fig. 5.6
Telco Port Pinout
50-Pin Alarm and Control Relay Connector
5.5
The primary connectors for discrete alarms, analog alarms and control relays are the 50-pin Amphenol
connector on the NetGuardian's back panel.
Discretes 1–16
RTN
ALM
RTN
ALM
ALM 1
1
26
ALM 9
9
34
ALM 2
2
27
ALM 10
10
35
ALM 3
3
28
ALM 11
11
36
ALM 4
4
29
ALM 12
12
37
ALM 5
5
30
ALM 13
13
38
ALM 6
6
31
ALM 14
14
39
ALM 7
7
32
ALM 15
15
40
ALM 8
8
33
ALM 16
16
41
Analogs 1–4
+
–
ANA 1
21
46
ANA 2
22
47
ANA 3
23
48
ANA 4
24
49
GND
25
50
Control Relatys 1–2
NO/NC
CO
CTRL 1
17/42
43
CTRL 2
19/44
18
FUSE
20/NA
45
Содержание D-PK-NG216