sufficiently ventilated, you must provide for outside
air to be allowed in by means of the outside air
connection kit or an optional adjustable damper.
Air outlet grates must be fitted at the top of the
hearth and just below the cover plate. The
minimum air outlet opening is 500 cm
2
.
The inlet and outlet grates are available as
options.
Do not use combustible material in the
convection space, and avoid the effect of
thermal bridging when using materials that
conduct heat.
Follow the instructions below when building the
hearth:
1. Build the base of the hearth and fit the air inlet
grates into the masonry.
You can place the air inlet grates on all sides of
the base.
Make sure the door of the appliance can swing
freely over the hearth floor.
2. Build the hearth up to the smoke dome.
Ensure that a clearance of 2 mm is maintained
between the stove and the masonry to
accommodate the thermal expansion of the
stove.
3. The inside of the convection space may, if
desired, be cladded with reflective, insulating
material.
Additional cladding of the convection space
prevents unnecessary thermal radiation
towards outer walls and/or adjacent rooms. It
also prevents damage to the hearth wall
insulation.
4. Build the rest of the hearth up to the flue gas hole
in the ceiling.
The masonry may not rest on the stove. Use a
support such as a steel beam. Leave a
clearance of at least 3 mm between the
support and the appliance.
5. Close the convection space with the cover plate.
6. Put the air outlet grates under the cover plate.
7. Make an opening above the cover plate in order to
prevent any pressure build-up.
The figure below shows an example of the placing of a
stove in a hearth built in accordance with the
instructions given above.
L
M
09.20015.043
A
B
C
D
E
F
G
H
I
J
K
N
O
A
Chimney (flue)
B
Seal
C
Cover plate
D
Insulation 10 cm
E
Fireproof wall min. 10 cm (e.g. cellular concrete)
F
Combustible wall
G
Convection space
H
Fireproof ceiling
I
Combustible ceiling
J
Convection air outlet
K
Insulation
L.
Fireproof floor
M
Combustible floor
N
Opening to prevent pressure build-up
O
Connection pipe
Subject to change because of technical improvements
13
Содержание 2180CBBS
Страница 24: ...2180CBBS 09 20017 026 24 Wijzigingen op grond van technische verbeteringen voorbehouden...
Страница 25: ...Wijzigingen op grond van technische verbeteringen voorbehouden 25 2180CBGD 09 20017 028...
Страница 31: ......
Страница 53: ...Appendix 2 Measurements 2180CBS and 2180CBC 09 20017 024 Subject to change because of technical improvements 23...
Страница 54: ...2180CBBS 09 20017 026 24 Subject to change because of technical improvements...
Страница 55: ...2180CBGD 09 20017 028 Subject to change because of technical improvements 25...
Страница 61: ......
Страница 85: ...2180CBBS 09 20017 026 Sous r serve de modifications dues des am liorations techniques 25...
Страница 86: ...2180CBGD 09 20017 028 26 Sous r serve de modifications dues des am liorations techniques...
Страница 114: ...Anlage 2 Abmessungen 2180CBS und 2180CBC 09 20017 024 24 nderungen aufgrund technischer Verbesserungen vorbehalten...
Страница 115: ...2180CBBS 09 20017 026 nderungen aufgrund technischer Verbesserungen vorbehalten 25...
Страница 116: ...2180CBGD 09 20017 028 26 nderungen aufgrund technischer Verbesserungen vorbehalten...
Страница 144: ...Anexo 2 Medidas 2180CBS y 2180CBC 09 20017 024 24 Dovre se reserva el derecho de realizar cambios por razones t cnicas...
Страница 145: ...2180CBBS 09 20017 026 Dovre se reserva el derecho de realizar cambios por razones t cnicas 25...
Страница 146: ...2180CBGD 09 20017 028 26 Dovre se reserva el derecho de realizar cambios por razones t cnicas...
Страница 174: ...Allegato 2 Dimensioni 2180CBS e 2180CBC 09 20017 024 24 Con riserva di modifiche per miglioramenti tecnici...
Страница 175: ...2180CBBS 09 20017 026 Con riserva di modifiche per miglioramenti tecnici 25...
Страница 176: ...2180CBGD 09 20017 028 26 Con riserva di modifiche per miglioramenti tecnici...
Страница 182: ......