Rack Monitor 8800E/8801E
Document: Operation Manual
Date: 16-Jun-2011
Version: A.6
Page 18 of 35 H71343
Liquid Crystal Display info during normal operation.
After the power up sequence the 8800E will enter the normal operation mode. The following messages will
sequential appear on the LC-Display.
01
S Y S T E M
R E A D Y
02
P L E A S E
C O N N E C T
P L U G
As soon as the plug is connected to the truck the following message page will appear.
(e.g. truck with Ground bolt and Two-Wire Dry sensors)
In line 4 the type of ground verification:
Ground Bolt
In line 5 the type of sensors:
Two Wire Sensors
In line 6 the amount of sensors:
In line 7 the state of the detected sensors:
Dry
If all sensors are dry and a proper ground is verified the indication “permit to load “will appear at line 10.
If less then 8 sensors are connected and the remaining sensors are emulated with a dummy the rack monitor will
indicate the remaining channels as dry Two-Wire sensors.
Note: only when special Dummy is mounted in the socket of the Tank-Truck. Else remaining channels will be
indicated as Dry
01
S Y S T E M
R E A D Y
02
S O C K E T
D E T E C T E D
03
04
G R O U N D
V E R I
F I
C A T I
O N
:
B O L T
05
S E N S O R
T Y P E
D E T E C T E D
:
2 W I
R E
06
S E N S O R
D E T E C T E D
:
1 2 3 4 5 6 7 8
07
S E N S O R
S T A T E
:
D D D D D D D D
08
09
10
P E R M I
T
T O
L O A D
Note: If the plug is not connected to the truck socket it will go into sleep mode after 15 minutes.
The Red Led lamps will lit up every few seconds