4.4 SETTING HIGH FLOWRATE

Adjustment MUST be made with the pump at the opera-
ting speed required for the desired flowrate and with
maximum air pressure applied to the air relief valve.

Setting of high flowrate is done by :

• Controlling the pump rpm
• Controlling the high pressure setting inside the ACP
• Controlling the line losses in the system

The high pressure setting inside the ACP controls the
maximum air pressure going to the pump air relief valve
through the DMX when the flow detector is activated.
The air pressure on the pump relief valve controls the
maximum product pressure downstream of the pump.
The flowrate will stabilize when the line losses behind
the pump equal the discharge pressure of the pump.

It is Blackmer's field experience that when a truck is desi-
gned for dual use, utilizing a 3" TXD3 Pump, the( ACP ) Air
Control Panel regulators should be set at 100 PSI on the Hi
Pressure Regulator and 50 to 55 PSI on the Low Regulator.
This will allow the pump to overcome back pressure crea-
ted  utilizing 1 1/4" or 13/8" hose and nozzle.

NOTICE :

IN CONDITIONS WHERE THE LINE LOSSES FROM THE TANK TO
THE DMX ARE EQUAL TO THE MAXIMUM INLET VACUUM
ACCEPTABLE INSIDE THE DMX, DMX WILL CREATE FLOW
CYCLING. THIS PHENOMENON WILL LIMIT THE MAXIMUM FLO-
WRATE OBTAINABLE AND MUST BE CORRECTED BY REDU-
CING THE LINE LOSSES FROM THE TANK TO THE DMX.

To increase maximum flowrate :

• Increase pump rotation speed
• Increase the setting of the high pressure regulator of

the ACP. Check in the appropriate IOM for the maxi-
mum allowable pressure to each Blackmer component.

• Reduce the line losses between the pump discharge

and the hose/delivery nozzle (increase piping diame-
ter, hose diameter, reduce number of elbows and
valves, nozzle size, reduce the length of hose, etc)..

NOTICE :

TO AVOID DAMAGE TO THE PUMP AIR/RELIEF VALVE (9C) DO
NOT OVERPRESSURE THE RELIEF VALVE.

In cases where downstream restrictions reach the set
pressure of the relief valve before the flowrate matches
the pump speed, the pump will go into bypass and recir-
culate fluid through the pump internal relief valve.

In those situations, increasing the maximum pressure
setting of the ACP will not lead to significant flowrate
increase. Reduce the restrictions in the discharge piping.

To check for pump over speeding, position the system in
its maximum flowrate configuration (empty hose, nozzle
fully open, hose unwound from hose reel, etc.) Reduce
the pump speed by steps, allowing one minute to stabi-
lize the flowrate between each step. Record the last rpm
value before a flowrate reduction may be noticed.

Set the high pressure regulator and pump rotational
speed to limit the recirculation flowrate through the internal
relief valve.

Some installations will require the limiting of flowrate
and/or pump discharge pressure. For example :

• To reduce the creation of foam in customer tanks
• To allow easier hose handling during delivery

Reduce the setting of the ACP high pressure regulator to
reduce the maximum flowrate.

Check the ACP IOM for the minimum differential setting
between the high pressure and low pressure setting.

After setting the regulator pressure, push down on the
air regulator adjusting knob to it lock in position.

4.5 SETTING THE FLOWRATE AND ENGINE SPEED

NOTICE :

THE AIR RELIEF VALVE LOW PRESSURE SETTING REGULATES
THE DELIVERY HOSE PRESSURE WHEN THE NOZZLE IS CLO-
SED.  ADJUST THE AIR VALVE ONLY HIGH ENOUGH TO OPEN
THE FLOW DETECTOR/CHECK VALVE AND DELIVER THE
REQUIRED LOW FLOWRATE.

At the beginning of the delivery, it is important that the
flowrate and pump discharge pressure are reduced :
• Hose handling is easier when discharge pressure is lower.
• When operating against a closed nozzle, lower dis-

charge pressure reduces horsepower required and
heat buildup in the pump.

In most operations, users will want flowrates to increase
to the maximum as quick as safely possible when delivery
is started.

In some operations, like small tank filing or topping off
tanks, users do not want high flow or high pressure. In
these cases, limit the stabilized flowrate by reducing the
opening of the delivery nozzle and do not allow the engine
speed to increase.

By controlling the setting of the DMX IV Air Elimination
System, truck acceleration and increased pump relief
valve pressure can be prevented. This may be done
without the need for a specific switch on the Truck Fuel
Delivery control panel.

To ensure that the Flow Detector is properly set :

• Determine the desired flowrate when in operation

without the engine speed being increased.

• Set the low pressure regulator of the ACP to its

lowest setting.

• Recirculate the product through the pumping system

and DMX to a tank compartment that is at least half
full and has at least 260 gallons (1000 liters) inside.

• Run the pump at the normal engine speed.
• Recirculate the fluid through the delivery hose to an

empty compartment/tank. NOTE : Remove ALL the
hose from the hose reel to reduce restrictions.

• Increase the ACP low pressure setting in 5 PSI

(0,34 bar) increments, letting the system stabilize in
flow for one minute between each adjustement.
Record the flowrate.

• The Flow detector is triggered when no air is venting

from its exhaust port. When this occurs, output 3 and
5 of the ACP should be at high pressure. If no ven-
ting occurs inside the DMX, port 4 will also be at that
high pressure.

6/15

NT 201B-A00 04.06 DMX IV Air elimination system e

4. SYSTEM CONSIDERATIONS (continued)

Содержание Blackmer DMX IV

Страница 1: ...es March 2006 BLACKMER 1809 Century Avenue Grand Rapids Michigan 49503 1530 U S A Telephone 616 241 1611 o Fax 616 241 3752 E mail blackmer blackmer com Internet address www blackmer com BLACKMER ZI PLAINE DES ISLES F 89000 AUXERRE Tel 33 3 86 49 87 13 Fax 33 3 86 49 87 17 e mail contact blackmer mouvex com Original instructions ...

Страница 2: ...or personal injury death or major property damage Warns of hazards that WILL cause serious personal injury death or major property damage Warns of hazards that CAN cause serious personal injury death or major property damage Warns of hazards that CAN cause personal injury or property damage NOTICE Indicates special instructions which are very important and must be followed SAFETY INFORMATIONS WARN...

Страница 3: ...e serious injury FAILURE TO RELIEVE SYSTEM PRESSU RE PRIOR TO PERFORMING PUMP SERVI CE OR MAINTENANCE CAN CAUSE PER SONAL INJURY OR PROPERTY DAMAGE WARNING Hazardous pressure can cause personal injury or property damage ALL FLUIDS PUMPED MUST BE COMPATI BLE WITH DMX MATERIAL INCOMPATIBI LITY CAN CAUSE FIRE SERIOUS PERSO NAL INJURY OR PROPERTY DAMAGE WARNING Hazardous fluids can cause fire serious ...

Страница 4: ...R DMX III AIR ELIMINATION SYSTEM MUST ONLY BE INSTALLED IN SYSTEMS DESIGNED BY QUALIFIED ENGINEERING PERSONNEL SYSTEMDESIGNMUSTCONFORMWITHTOALLAPPLI CABLE REGULATIONSAND CODESAND PROVIDE WARNING OFALL SYSTEM HAZARDS NOTICE THE ENCLOSED IOM APPLY TO DMX III WHERE THEUPGRADE KIT HAVEBEENINSTALLED SEEENCLOSEAVIEWOFTHEUPGRADEKIT The Blackmer DMX IV Air Elimination System is designed for air free deliv...

Страница 5: ...f High and Low flowrates Setting of High flowrate Setting of flowrate and engine speed acceleration Air Elimination separation Stop flow when meter is no longer supplied with air free liquid Provide air free and vapor free fluid delivery for metered applications Fluid Control Safety of operation when pumping against closed discharge valve Liquid handling from DMX to Flow Detector Provide strained ...

Страница 6: ...r and pump rotational speed to limit the recirculation flowrate through the internal relief valve Some installations will require the limiting of flowrate and or pump discharge pressure For example To reduce the creation of foam in customer tanks To allow easier hose handling during delivery Reduce the setting of the ACP high pressure regulator to reduce the maximum flowrate Check the ACP IOM for ...

Страница 7: ...p to be above a given minimum once the system is primed Performance tests have demonstrated that the following pressure settings are typical for operation with DMX and TXD pumps NOTICE IT IS THE INSTALLER S RESPONSIBILITY ON EACH TRUCK TO CHECK THAT THE PUMP BACKPRESSURE IS SUFFICIENT TO ALLOW THE DMX TO PERFORM ITS AIR ELIMINATION FUNC TION PROPERLY ADDING MORE BACKPRESSURE WILL RESULT IN UNACCEP...

Страница 8: ... that do not eliminate pressure spikes or pres sure increase due to thermal expansion risks a spare volume of air must be trapped in a dedicated area here after called expansion tank to compress in whenever there is a pressure spike or thermal expansion of trapped liquid The compression of air trapped in the expansion tank will limit the maximum pressure inside DMX to an acceptable level see DMX I...

Страница 9: ...P Truck air in connection line marked 1 on Figure 2 this is the same as the first statement in the connections for the ACP and DMX below 2 Connect Line to Engine Speed Control marked 5 on Figure 2 to the feature controlling engine speed Note that if you have 2 DMX Air Elimination Systems installed on the truck and only one truck acceleration system it is allowed to use a shuttle valve to compa re ...

Страница 10: ...ystem is also recommended when operating for exten ded periods more than 1 minute against a closed dis charge valve or nozzle 5 12 FLUSHING THE PUMP Refer to the component IOM for flushing procedures and recommendations 5 13 AIR RELIEF VALVE SETTING Set the pump relief valve by adjusting the high pressure regulator in the Air Control Panel For adjustment proce dure refer to Setting of High Flowrat...

Страница 11: ...MING SERVICE CAN CAUSE SEVERE PERSONAL INJURY OR PROPERTY DAMAGE WARNING Hazardous machinery can cause severe personal injury or property damage FAILURETODISCONNECTANDLOCKOUT ELECTRICAL POWER OR ENGINE DRIVE BEFORE ATTEMPTING MAINTENANCE CAN CAUSE SEVERE PERSONAL INJURY OR DEATH WARNING Hazardous machinery can cause serious personal injury IF PUMPING HAZARDOUS OR TOXIC FLUIDS THE SYSTEM MUST BE FL...

Страница 12: ...es are that the Flow Detector is not returning to its low flow condition or that the Air Control Panel is not functioning properly High probability items 22 33 41 49 Medium probability items 31 32 35 Low probability items 34 44 7 1 6 Low flow rate only The most common root causes are that the Flow Detector is not returning to its low flow condition or that the Air Control Panel is not functioning ...

Страница 13: ...ty the secu rity chamber See 8 above for the troubleshooting pro cedure See the DMX IOM for instructions on chamber draining 13 The air line from the pneumatic cover to the float cover is blocked Replace the air line 14 Air leak in the line between the DMX and the Pump relief valve Repair or replace the line 15 Clogged inlet filter strainer Clean or replace the filter strainer 16 The pneumatic cov...

Страница 14: ...uirements are not met trapping air 48 Clogged oil separator in the ACP 49 Truck acceleration mechanism is faulty 50 Check all piping connections for leaks 51 DMX overpressurized Potential hammer peak or ther mal expansion condition Install expansion tank to limit the effects of this overall system flaw 52 Low pressure regulator is set too low See the SETTING FLOWRATE AND ENGINE SPEED section of th...

Страница 15: ... AUXERRE FRANCE Tél 33 3 86 49 87 13 Fax 33 3 86 49 87 17 Mail contact blackmer mouvex com Site internet www blackmer com 1809 Century Avenue Grand Rapids Michigan 49509 1595 U S A Telephone 616 241 1611 Fax 616 241 3752 E mail blackmer blackmer com Internet Address www blackmer com ...

Отзывы: