background image

2  Safety

2.1  Intended use

The glide rail system GSR XEA BG is used for the 
sequential locking control of 2 winged doors. The glide 
rail system GSR‑EMF XEA BG is used for the 
sequential locking control and for the locking 
mechanism to keep open 2 winged doors. The locking 
mechanism is used in conjunction with external RMZ 
to keep open fire and smoke protection closures. Fire 
and smoke protection closures must meet the building 
regulation requirements ‘’self‑locking’’. The 
electromechanical locking device is no substitution for 
a door stop. The locking device is released manually or 
via an external RMZ.

2.2  Limitation of liability

The manufacturer does not assume liability for 
damages in the following events:
•  Nonobservance of this instruction.
•  A deviating application of the intended use.
•  The assignment of insufficiently skilled staff.
•  Unauthorized modifications.
•  Technical alterations.
•  The use of spare parts which are not authorized.

2.3  Prerequisites for the 

operation of catching devices

The use of the slide rail systems as catching devices 
(GSR‑EMF XEA BG) is subject to special regulations 
by reason of official admission standards. These 
regulations refer in particular to the inspection, the 
continuing surveillance and the maintenance. Follow 
the details from the data sheet about the use of 
catching devices.
Additional requirements apply for the use as fire and 
smoke protection closures in conjunction with the 
external RMZ and RM. A separate verification of 
suitability is required for the respective fire / smoke 
protection door. 

3  Product description

The slide rail system ensures the correct order when 
closing 2‑winged doors. 
The slide rail system is intended for the mounting into 
the opposite hinge side. The slide rail system is 
suitable for DIN‑L and DIN‑R doors and for door 
widths of 1500‑2500 mm.

GSR XEA BG

The GSR XEA BG comprises the following 
components:
•  Slide rail system with sequential locking control.

GSR-EMF XEA BG

The GSR‑EMF XEA BG comprises the following 
components:
•  Slide rail system with sequential locking control
•  Built‑in electromechanical locking device for each 

door leaf 

The active leaf can either be locked independently 
from the fixed leaf or both door leaves can be locked.

3.1  EMF

The EMF is an electromechanical locking mechanism 
with adjustable release force, which enables locking 
the door without spring back. After a cut‑off of power 
supply, the locking device sets in and the door will be 
closed securely through the door closer. 

3.2  Technical data of the EMF

Operating voltage:

24 V DC  
in France also 48 V DC

Power consumption:

2 x 1.4 W = 2.8 W 
in France also  
2 x 2.2 W = 4.4 W

Duty cycle:

100 % ED

Release torque:

approx. 25 – 65 Nm at 90°  
opening angle (dependent 
on the set closing force on 
the closer)

Door opening angle:

80° – 120°

The drive happens via an external RMZ.

3

GSR XEA BG/GSR-EMF XEA BG

2017-10

dormakaba Mounting instructions

WN 059385 45532

Safety

Содержание GSR XEA BG

Страница 1: ...il 4 4 4 Mount the door closer 4 4 5 Shorten the connecting tube 4 4 6 Adjust the triggering roller on the door leaf 4 4 7 Mount the connecting tube 4 4 8 Set the sequential locking control 5 4 9 Check the sequential locking control 5 4 10 Connect the EMF 5 5 Start up 5 5 1 Set the fixture point 5 5 2 Set the release force 5 5 3 Mount the paneling 6 5 4 Check the EMF 6 5 4 1 Release EMF manually 6...

Страница 2: ... is authorized by dormakaba The operating of the slide rail system can be carried out by any person who is mentally and physically able 1 3 Provided documents Mounting instructions Additionally with GSR EMF XEA BG Data sheet about the use of catching devices 1 4 Symbols and abbreviations used 1 4 1 Safety instructions WARNING This statement indicates a situation of potential risk which could lead ...

Страница 3: ... for the use as fire and smoke protection closures in conjunction with the external RMZ and RM A separate verification of suitability is required for the respective fire smoke protection door 3 Product description The slide rail system ensures the correct order when closing 2 winged doors The slide rail system is intended for the mounting into the opposite hinge side The slide rail system is suita...

Страница 4: ...Insert the end caps connector into the slide rail 2 A Tighten the slide rail B Tighten the slide rail on the pre installed mounting plate C Tighten the slide rail on the pre installed lintel casing angle 4 4 Mount the door closer ATTENTION Risk of damaging the slide rail system The dimensions on the drill template of the door closer are not suitable for the mounting of this product Use the dimensi...

Страница 5: ... trigger the trigger must be moved 1 Close the fixed leaf 2 Loosen the screw 3 Push the trigger into the direction of the triggering roller 4 Tighten the screw 4 10 Connect the EMF Only for GSR EMF XEA 1 Lay the EMF connecting cables of the fixed leaf to the active leaf in a way that it is not resulting in jamming the connecting rod 2 Tighten the cable with zip ties 3 Insert the connection cable o...

Страница 6: ...ease of the RMZ etc The door leaves are released and close The active leaf closes only when the fixed leaf is closed 6 Operating Only for GSR EMF XEA 6 1 Open and lock door 1 Open door leaves to the fixture point The door leaves remain standing after letting go 6 2 Close door 1 Firstly press shut the fixed leaf then the active leaf against the resistance or press the optional manual release button...

Страница 7: ...7 GSR XEA BG GSR EMF XEA BG 2017 10 dormakaba Mounting instructions WN 059385 45532 ...

Страница 8: ...dormakaba Deutschland GmbH DORMA Platz 1 58256 Ennepetal Germany T 49 2333 793 0 F 49 2333 793 4950 www dormakaba com Translation of the original manual subject to change without notice ...

Отзывы: