DORCHESTER DR-SA 16 Скачать руководство пользователя страница 9

9

Electrical connenction

Ionisation current

The minimum ionisation current is 0.9 micro-Amperes DC. 

Below this current the burner controller will assume no flame 

is present. When in normal operation, the ionisation current 
will be about 1.2 to 1.3 micro-Amperes DC when only the 

pilot flame is burning. 

 

(Adjust the main burner pressure to zero to be able to 
measure under this condition). 
With pilot and main burner in operation, the ionisation 
current will be approx. 6.0 to 6.3 micro-Amperes DC. 
Ionisation current can be measured by connecting a 

universal meter in series with the connection to the flame 

probe. Make sure meter is set for Direct Current.  Alternating 
Current gives no information about the system’s behaviour.

2.  

FOR THE INSTALLER

2.1   Installation

This water heater must be fitted in a location that will permit 

the provision of an approved flue system and adequate 

ventilation.
A service clearance of 50 cm at the sides and rear of the 
unit and 100 cm at the front of the unit must be allowed 
for ease of servicing. Adequate distance must be allowed 
between the top of the unit and any obstruction or ceiling to 

allow the flue baffle and anode to be inspected, cleaned or, 

in the case of the anode, replaced if necessary.
The water heater must stand on a level surface resistant 
to heat, insulated in accordance with local by laws and 

Building Regulations and with sufficient strength to support 

the weight of the unit when full of water.  
The heater must stand on its feet as supplied and the 
space beneath the bottom casing kept clear as this is the 
path for combustion air to enter the heater.
This water heater must not be installed in a bathroom, 
bedroom or in a cupboard opening on to such rooms. 
This water heater must not be installed in any area where 

flammable materials are used or stored.

Insufficient ventilation may give rise to a risk of fire, 

explosion or suffocation. If in doubt consult the national 
and local regulations governing the installation of gas 
appliances or local gas service organisation.

2.1.1  Regulations and Related Documents

Gas Safety Installations and Use Regulations 1998,  

(as amended). 

It is law that competent persons, in 

accordance with the above regulations install all gas 
appliances. Failure to install appliances correctly could 
lead to prosecution. It is in your own interest, and that of 
safety, to make sure that this law is complied with.
The installation of the boiler 

MUST 

be in accordance with 

the relevant requirements of the Gas Safety Regulations, 
Building Regulations, IEE Regulations and the Water 

Supply (water fittings) Regulations. 

 

The installation must also be in accordance with any 
relevant requirements of the HSE, local gas region and 
local authority and the relevant recommendations of the 
following documents: -

British Standards

BS 6891:

 Specification for the installation of low-pressure 

gas pipe work of up to 28 mm (R1) in domestic premises (2

nd

 

family gas). For larger installations see 

IGE/UP/2 

below.

BS 6798:

 Specification for installation of gas-fired boilers 

of rated input not exceeding 70 kW net.

BS 6644: 

Specification for installation of gas-fired hot 

water boilers of rated inputs between 70 kW and 1.8 MW 
(net) (2

nd

 and 3

rd

 family gases).

BS 6700: 

Specification for design, installation, testing and 

maintenance of services supplying water for domestic use 
within buildings and their curtilages.

BS EN 806-2:

 Specification for installations inside 

buildings conveying water for human consumption.  
Part 2: Design.

BS 5546:

 Specification for installation of hot water 

supplies for domestic purposes, using gas-fired 

appliances of rated input not exceeding 70 kW.

BS 5440:

 Installation and maintenance of flues and 

ventilation for gas appliances of rated input not exceeding 
70 kW net (1

st

, 2

nd

 and 3

rd

 family gases).  

Part 1: Flues. Part 2: Ventilation.

Institute of Gas Engineers and Managers Publications

IGE/UP/1 

Soundness testing and purging of industrial and 

commercial gas installations.

IGE/UP/1A 

Soundness testing and direct purging of 

small low-pressure industrial and commercial natural gas 
installations.

IGE/UP/2 

Gas installation pipe work, boosters and 

compressors on industrial and commercial premises.

IGE/UP/10 

Installation of gas appliances in industrial and 

commercial premises. 

Part 1: 

flued appliances.

CIBSE Publications:- “CIBSE Guide”

Section B4 :

 Water Service Systems.

Some chemicals produce vapours that can cause 

rapid failure of main and pilot burners and storage 

tanks if they are drawn into the combustion air 

supply.

  Electrical supply 

Frequency 

      Fuse

 

230 V AC  

50 Hz 

          5 A

Содержание DR-SA 16

Страница 1: ...OCUMENT IS FOUND RELATING TO SPECIFIC GAS TO BE FIRED BEFORE FIRING HEATER THIS WATER HEATER COMPLIES WITH ALL RELEVANT EUROPEAN DIRECTIVES PUBLICATION NO 500001135 ISSUE F APRIL 2012 Dorchester DR SA...

Страница 2: ...2...

Страница 3: ...ulation system 10 2 1 3 Gas connection 12 2 1 4 Draught diverter 12 2 1 5 Flue system 12 2 1 6 Electrical connection 12 2 2 Commissioning 12 2 3 Removing and replacing the control panel front cover 13...

Страница 4: ...All Dorchester heaters are factory assembled and delivered individually packed and shrouded in polythene on a wooden pallet Within the packaging wrapped separately is the draught diverter complete wit...

Страница 5: ...rol panel 8 Inspection cover plate 9 Intermittent pilot burner and flame probe 10 Cold water inlet c w inlet tube 11 Combustion products discharge safety device 12 T P valve connection 13 Outer casing...

Страница 6: ...safety thermostat is pre set to 90 C The control panel is also fitted with an ON OFF switch I 0 At setting I the gas control is activated on the basis of heat demand from the control thermostat At set...

Страница 7: ...ons It is recommended that a competent person carry out the necessary remedial action Important The combustion products discharge safety device must never be put out of operation Re entry of flue gase...

Страница 8: ...fice G30 mm 0 23 0 23 Heating time T 45 K min 43 55 DATA G31 37 mbar Nominal output kW 17 6 19 1 Nominal load gross kW 22 5 24 5 Supply pressure G31 mbar 37 37 Gas consumption G31 kg h 1 6 1 8 Diamete...

Страница 9: ...ordance with the above regulations install all gas appliances Failure to install appliances correctly could lead to prosecution It is in your own interest and that of safety to make sure that this law...

Страница 10: ...hardness 10 0 fH English hardness 7 0 eH 100 mg l CaCO3 Conductivity 125 S cm Acidity pH value 7 0 pH value 9 5 Note If the water specifications deviate from those stated in the table then the tank p...

Страница 11: ...A Gas supply B Hot water delivery C Cold water inlet D Hot water taps E Return circulation Figure 6 Connection diagram un vented systems Un vented system see figure 6 To install a Dorchester water hea...

Страница 12: ...arapets etc If an existing chimney or flue is to be used this must be swept clean and be free of debris before an approved liner is installed and connected to the water heater Electrical supply Freque...

Страница 13: ...n set to the correct value at the factory but it must be checked again at commissioning and during the once a year and every year maintenance by adopting the following procedure 1 Shut down the heater...

Страница 14: ...ode Note On no account remove the magnesium anode without checking to make sure that the heater is fully isolated and the pressure removed 1 Close the stop valve in the cold water supply pipe 2 Open t...

Страница 15: ...discharge safety device reset button firmly to make sure it is reset 6 Make sure the manual gas shut off valve is open 7 Switch the mains electricity supply to the heater ON Set the on off switch on t...

Страница 16: ...ducts discharge Investigate the cause blocked flue incorrect safety device has operated flue wind conditions incorrect ventilation and rectify before pressing reset button on the flue thermostat Insuf...

Страница 17: ...urner D Spark electrode E Flame probe G Combustion products discharge safety device H Control thermostat K Safety thermostat M Reset button N Terminal block P Terminal block R Earth terminals S Connec...

Страница 18: ...0308 236 R3...

Отзывы: