2.1.3  Gas connection

The gas supply to this appliance must be installed in 
accordance with BS 6891 and IGE/ UP/1,1A and 2.  
Fit the 1/2” manual gas shut off valve, supplied with this 
unit, immediately before the gas control valve. No heat 
or soldered joints must be applied in the vicinity of the 
gas control valve, as this could cause damage to the 
control. All connections and joints must be tested for gas 
soundness.

2.1.4  Draught diverter

The draught diverter, supplied separately in the delivery 
crate, 

MUST

 be fitted to the top of the heater in an 

unmodified condition before connecting the flue system. 

The sensor of the combustion products discharge safety 

device is pre-fitted to the draught diverter so care must be 

taken not to damage the capillary and thermostat. With 
the sensor facing forward, place the draught diverter over 

the flue tube and make sure the three legs engage with 

the slots in the top casing.
To complete the installation of the combustion products 
discharge safety device, remove the two screws from the 
top casing, position the bracket with the pre-assembled 
thermostat over the holes and re-apply screws.  
Complete the electrical circuit by connecting the two-pin 
plug to its appropriate socket on the top casing. If the 
safety device operates, the heater will shut down and only 
restart when the temperature of the sensor has dropped 

sufficiently for the button on the thermostat to be reset. 

Important

The combustion products discharge safety device must 
never be put out of operation. 

Re-entry of flue gases to the building could be harmful 

and cause poisoning or death. 

2.1.5   Flue system

The water heater must be fitted with a flue system 

connected to the draught diverter. The flue pipe must rise 

for at least 50 cm. vertically before the inclusion of any 

bends. If a horizontal run of flue is required this must be 

kept to the minimum length possible and incorporate a 
rise of 6 cm. per metre of run.

The flue system 

must

 be self-supporting and incorporate 

a removable section close to the heater to enable the 

diverter and flue gas baffle to be removed for cleaning.

The materials used for the flue system must be non-

combustible, mechanically robust and resistant to internal 
and external corrosion. Combustible materials in the 

vicinity of the heater and flue shall not exceed 65°C 

during heater operation. The flue shall not be closer 

than 50 mm to any combustible material, except where 
it passes through such material with a non-combustible 
sleeve when the air gap may not be less than 25 mm.

All flues must terminate in free air space approx. 

 

1,5 metres from any vertical surface of structure i.e. 
chimneystacks, roof parapets, etc. If an existing chimney 

or flue is to be used this must be swept clean and be 

free of debris before an approved liner is installed and 
connected to the water heater.

  Electrical supply 

Frequency 

      Fuse

 

230 V AC  

50 Hz 

          5 A

2.1.6   Electrical connection

An accredited electrical installation company must carry 
out all electrical connections in accordance with IEE 
regulations. The appliance must be connected to the 
mains by means of a permanent electrical connection.  

A Fused isolator must be fitted between the permanent 

connection and the water heater. The cable must have  
3 cores of at least 1.0 mm

2

. The connecting terminals  

for the electrical supply are indicated by the symbol for 
earth, N for neutral and L for live. Always check with a 
voltage tester that the live and the neutral have been 
connected correctly in the electrical supply. The electrical 
supply must comply with the requirements below:

The maximum power consumption is 25 W.
See appendix 1 electrical diagram for more information.

2.2   Commissioning

Filling the water heater

1.   Close the drain valve.
2.   Open the cold-water stop valve to the water heater 

and open all taps where hot water can be drained to 

remove air. The water heater is filled as soon as cold 

water flows from all taps.

3.   Close all hot water taps.

Putting into operation

1.   Check to see if the heater is filled with water 

by running a little to waste from a hot water tap 
connected to the system.

2.   Make sure that the ON/OFF switch is in OFF position.
3.   Make sure gas supply is fully purged of air and turn on 

manual gas valve.

4.   Switch the mains isolator to ‘ON’. Make sure that 

power is correctly supplied to the unit. Use a voltage 

tester to check that the live is to “L” and neutral to “N”. 

(Flame detection is phase sensitive).

5.   When first starting, the controller can be in the ‘lock 

out’ condition: depress the reset button to free the 
control. (After manual reset, an extended pre-purge/
waiting time will occur).

6.   Switch the ON/OFF switch into ON position. If the pilot 

fails to ignite within 25 seconds the controls will go 
to lock out and the reset button will need to be reset 
(wait 15 seconds before attempting reset). It may be 
necessary to repeat the lighting sequence a number 
of times if all the air has not been purged from the gas 
supply.

7.   The main burner pressure must be checked once the 

heater has operated for 10 to 20 minutes (see 2.4).

8.   Set the temperature regulator to the required setting 

(60°C is maximum recommended).

  Note

: If, during normal use, the reset button is 

pressed, the gas valves will close and the automatic 
ignition controller will start a new sequence after the 
reset button is released.

Shut down

Note

: The water heater must only be turned off when  

hot water will not be required for an extended period (e.g. 
holidays); otherwise it must be left on.
To shut down put the ON/OFF switch into OFF position.

Содержание DR-SA 16

Страница 1: ...OCUMENT IS FOUND RELATING TO SPECIFIC GAS TO BE FIRED BEFORE FIRING HEATER THIS WATER HEATER COMPLIES WITH ALL RELEVANT EUROPEAN DIRECTIVES PUBLICATION NO 500001135 ISSUE F APRIL 2012 Dorchester DR SA...

Страница 2: ...2...

Страница 3: ...ulation system 10 2 1 3 Gas connection 12 2 1 4 Draught diverter 12 2 1 5 Flue system 12 2 1 6 Electrical connection 12 2 2 Commissioning 12 2 3 Removing and replacing the control panel front cover 13...

Страница 4: ...All Dorchester heaters are factory assembled and delivered individually packed and shrouded in polythene on a wooden pallet Within the packaging wrapped separately is the draught diverter complete wit...

Страница 5: ...rol panel 8 Inspection cover plate 9 Intermittent pilot burner and flame probe 10 Cold water inlet c w inlet tube 11 Combustion products discharge safety device 12 T P valve connection 13 Outer casing...

Страница 6: ...safety thermostat is pre set to 90 C The control panel is also fitted with an ON OFF switch I 0 At setting I the gas control is activated on the basis of heat demand from the control thermostat At set...

Страница 7: ...ons It is recommended that a competent person carry out the necessary remedial action Important The combustion products discharge safety device must never be put out of operation Re entry of flue gase...

Страница 8: ...fice G30 mm 0 23 0 23 Heating time T 45 K min 43 55 DATA G31 37 mbar Nominal output kW 17 6 19 1 Nominal load gross kW 22 5 24 5 Supply pressure G31 mbar 37 37 Gas consumption G31 kg h 1 6 1 8 Diamete...

Страница 9: ...ordance with the above regulations install all gas appliances Failure to install appliances correctly could lead to prosecution It is in your own interest and that of safety to make sure that this law...

Страница 10: ...hardness 10 0 fH English hardness 7 0 eH 100 mg l CaCO3 Conductivity 125 S cm Acidity pH value 7 0 pH value 9 5 Note If the water specifications deviate from those stated in the table then the tank p...

Страница 11: ...A Gas supply B Hot water delivery C Cold water inlet D Hot water taps E Return circulation Figure 6 Connection diagram un vented systems Un vented system see figure 6 To install a Dorchester water hea...

Страница 12: ...arapets etc If an existing chimney or flue is to be used this must be swept clean and be free of debris before an approved liner is installed and connected to the water heater Electrical supply Freque...

Страница 13: ...n set to the correct value at the factory but it must be checked again at commissioning and during the once a year and every year maintenance by adopting the following procedure 1 Shut down the heater...

Страница 14: ...ode Note On no account remove the magnesium anode without checking to make sure that the heater is fully isolated and the pressure removed 1 Close the stop valve in the cold water supply pipe 2 Open t...

Страница 15: ...discharge safety device reset button firmly to make sure it is reset 6 Make sure the manual gas shut off valve is open 7 Switch the mains electricity supply to the heater ON Set the on off switch on t...

Страница 16: ...ducts discharge Investigate the cause blocked flue incorrect safety device has operated flue wind conditions incorrect ventilation and rectify before pressing reset button on the flue thermostat Insuf...

Страница 17: ...urner D Spark electrode E Flame probe G Combustion products discharge safety device H Control thermostat K Safety thermostat M Reset button N Terminal block P Terminal block R Earth terminals S Connec...

Страница 18: ...0308 236 R3...

Отзывы: