Technical specifications
Instruction manual DR-LA
23
is
Tabel 3.5
Gas data
Gas category data
II
2H3+
Unit
DR-LA
30
DR-LA
40
DR-LA
45
DR-LA
60
DR-LA
75
DR-LA
95
DR-LA
110
Data for natural gas 2H: G20-20 mbar
Orifice diameter
mm
3.20
3.20
3.10
2.95
3.20
3.20
3.90
(1) = Blanking plate
(2) = Burner pressure regulator
(3) = High Low control
1, 2 or 3
2
2
2
2
2
2
2
Nominal load (gross)
KW
41.4
55.5
65.2
81.0
96.4
124.2
140.5
Nominal output
KW
31.7
42.0
49.3
61.2
72.9
93.9
107.5
Supply pressure
mbar
20
20
20
20
20
20
20
Burner pressure
mbar
8.5
8.5
8.5
8.5
8.5
8.5
8.5
Gas consumption
m
3
/h
4.0
5.4
6.3
7.8
9.4
12.1
13.7
Data for LP gas 3+
General
Orifice diameter
mm
1.70
1.70
1.70
1.50
1.70
1.70
2.25
G30-30 mbar (butane)
(1) = Blanking plate
(2) = Burner pressure regulator
(3) = High Low control
1,2, or 3
1
1
1
1
1
1
3
Nominal load (gross)
kW
40.9
54.2
66.9
79.2
94.3
121.2
135.7
Nominal output
kW
32.0
42.0
51.8
61.4
73.1
93.9
106.4
Burner pressure
mbar
30
30
30
30
30
30
30
Gas consumption
kg/h
3.0
4.0
5.0
5.8
7.0
9.0
10.1
G31-37 mbar (butane)
Orifice diameter
mm
1.70
1.70
1.70
1.50
1.70
1.70
2.25
(1) = Blanking plate
(2) = Burner pressure regulator
(3) = High Low control
1,2, or 3
1
1
1
1
1
1
3
Nominal load (gross)
kW
37.6
50.1
62.1
76.2
87.8
110.9
127.6
Nominal output
kW
29.4
38.7
48.0
58.9
67.9
85.7
99.8
Burner pressure
mbar
37
37
37
37
37
37
37
Gas consumption
kg/h
2.7
3.7
4.5
5.3
6.4
8.1
9.3
(1) Based on 1013.25 mbar and 15
o
C.
(2) If using a blank plate or high-low control program, instead of a burner pressure regulator, it is assumed that the burner pressure is equal
to the supply pressure. In practice however, the burner pressure will be lower.
Содержание DR-LA 110
Страница 2: ...2...
Страница 6: ...6 Instruction manual DR LA gis...
Страница 16: ...Functioning of the water heater 16 Instruction manual DR LA 2 gis...
Страница 42: ...Filling and draining 42 Instruction manual DR LA 4 gis...
Страница 46: ...Controls 46 Instruction manual DR LA 5 gis...
Страница 64: ...Appendices 64 Instruction manual DR LA A is...