Environmental conditions
Instruction manual DR-LA
19
is
If the available clearance is less than 100 cm, flexible magnesium anodes
may be ordered from Hamworthy, the installation engineer / supplier.
n
Caution
When installing the water heater, be aware that any leakage from the it and/
or connections can cause damage to the immediate environment or floors
below the level of the boiler room. If this is the case, then the water heater
should be installed above a wastewater drain or in a suitable metal leak tray.
The leak tray must have an appropriate wastewater drain and must be at
least 5 cm deep with a length and width at least 5 cm greater than the
diameter of the water heater.
Figure 3.1
Working clearances
IMD-0135a