Conversion to a different gas category
Instruction manual DR-LA
35
is
12. Check whether there is a burner pressure regulator
fitted to the gas
control or simply a blank plate
.
n
Caution
In the event the supply pressure for a gas category is the same as the burner
pressure (see
) then the gas control must be fitted with a blank
plate with cork gasket. A burner pressure that deviates in comparison to the
supply pressure requires the use of a burner pressure regulator with rubber
gasket. Each conversion kit contains all the necessary components.
13. If the blank plate or burner pressure regulator need to be replaced:
-
Unscrew the connector
from the gas control.
-
Either, remove the blank plate
or burner pressure regulator
-
Either, fit the blank plate or burner pressure regulator supplied with the
conversion kit.
-
Refit the connector
to the gas control.
c
Note
14. Check the burner pressure and supply pressure (see paragraph
15. Remove the sticker showing the new gas category from the conversion kit
and attach it below the water heater’s rating plate. This clearly indicates that
the water heater may no longer be run on the gas for which it was originally
supplied.
Legend
through
d
burner pressure regulator
e
gas control connector
f
blank plate
g
supply pressure test nipple
h
gas control valve
Figure 3.10
Conversion of gas control
IMD-0131
Содержание DR-LA 110
Страница 2: ...2...
Страница 6: ...6 Instruction manual DR LA gis...
Страница 16: ...Functioning of the water heater 16 Instruction manual DR LA 2 gis...
Страница 42: ...Filling and draining 42 Instruction manual DR LA 4 gis...
Страница 46: ...Controls 46 Instruction manual DR LA 5 gis...
Страница 64: ...Appendices 64 Instruction manual DR LA A is...