Installation
28
Instruction Manual DR-FC
3
is
3.9.1
Concentric wall flue terminal
shows the wall flue terminal prescribed by Hamworthy (installation
type C13).
Figure 3.4
Wall flue terminal
IMD-0397
Table 3.7
Concentric wall flue terminal specifications
Specification
Description
Manufacturer
Muelink & Grol
Model
M2000 MDV SE
(1)
Pipe material, flue gas discharge
Thick-walled aluminium with lip ring seal
Pipe material, air intake
Thin-walled galvanised sheet steel
Pipe diameter
Concentric
•
DR-FC 25: Ø 80/125 mm.
•
DR-FC 30, 45 and 60: Ø 100/150 mm.
1.
The M2000 MDV SE model is a special version of the
Mugro 3000 series
. No other wall flue terminal may be used, as the DR-FC-water
heater is approved exclusively for this model of wall flue terminal. You can order the wall flue terminal from Hamworthy or your trade
supplier, by specifying model: M2000 MDV SE.
Содержание DR-FC 25
Страница 2: ...2...
Страница 6: ...6 Instruction Manual DR FC gis A Appendices 95 A 1 Introduction 95 A 2 Electrical diagram DR FC 96...
Страница 16: ...Functioning of the water heater 16 Instruction Manual DR FC 2 gis...
Страница 42: ...Filling and draining 42 Instruction Manual DR FC 4 gis...
Страница 46: ...The control panel 46 Instruction Manual DR FC 5 gis...
Страница 50: ...Status of the water heater 50 Instruction Manual DR FC 6 gis...
Страница 56: ...Starting up and shutting down 56 Instruction Manual DR FC 7 gis...
Страница 68: ...Main menu 68 Instruction Manual DR FC 8 gis...
Страница 72: ...Service program 72 Instruction Manual DR FC 9 is...
Страница 88: ...Troubleshooting 88 Instruction Manual DR FC 10 gis...
Страница 90: ...Maintenance frequency 90 Instruction Manual DR FC 11 gs...
Страница 98: ...Appendices 98 Instruction Manual DR FC A is...