Electrical equipment
- 118 -
4.4.2. DC power hookup of ignition system
●
Operating voltage requirements
●
Dimensions of cable
* It is recommended that each system be connected separately back to the power source. Determine the wire
size required.
Starting
20 VDC min.
Running
24 ~ 28 VDC
Distance in Cm
Minimum wire size
Distance in Cm
Minimum wire size
up to 762
16 AWG
2,012 - 3,048
10 AWG
793 - 1,219
14 AWG
3,079 - 4,877
8 AWG
1,250 - 1,981
12 AWG
Power supply spec: 5A continuous
Power supply
Regulator
Alternator
Battery
Battery
R
CPU-95 UNIT
Battery charger
-
+
-
+
Fuse rating
-
+
10A
+
-
-
+
EE3OM061
Switch rating
10A min
Содержание GV158TIC
Страница 1: ...950106 058010EN GV158TIC GV180TIC GV222TIC GAS GENERATOR ENGINE Operation Maintenance Manual...
Страница 2: ......
Страница 6: ...6 Engine Installation 143 6 1 Installing 143 6 2 Inspection Prior to Installation 144 Appendix...
Страница 130: ...Electrical equipment 124...
Страница 148: ...Maintenance of major parts 142...
Страница 152: ...Engine installation 146...
Страница 162: ...Appendix 156...