dr-02 :
Target Frequency Input Method Setup
It sets up target frequency input method of drive.
dr-03 :
Target Frequency Value Setup
When using as a fixed frequency, it is possible to set up target frequency value.
Target Frequency Input Method (dr-02) should be set with FND.
dr mode (Drive Control Mode)
Drive
dr-12 :
Motor Rated Current
It sets up rated current (RMS) of the motor. It is based on the rated current indicated on the
nameplate of the motor.
dr-20 :
Motor Rotation Direction Selection
It sets up rotation direction of the pump.
Be sure to check the rotation direction of the pump for normal operation. As the rotation
direction may change according to wiring, be sure to check it.
dr-01 :
Command Input Location Setup
It sets operation command location.
When selecting FND key, it is possible to issue operation command using key on main body of drive.
When setting up terminal block, it is possible to issue operation command using external input(P1)
Setup Data
Functional Description
0 (Factory Setting)
Operation Command with FND
1
Operation Command with Terminal Block(P1)
Functional Description
Setup Data
0 (Factory Setting)
Setup with own PID operation
Related Function
1
Setup when using fixed freq.
on the main body of FND drive
Target Freq. Value Setup
dr-03
Setup with external voltage V1(0~10V)
Setup with external current I1(4~20mA)
2
3
Factory Setting
Input Range
30.0 [Hz]
Start Freq. (dr-42) ~Max Freq (dr-43)[Hz]
Setup Data
Functional Description
0 (Factory Setting)
Forward Direction– CW(Clockwise)
1
Reverse - CCW(Counterclockwise)