RF Baghouse, Models RFT, RFW, and RFWH
16
Solid-State Timer Installation
The solid-state timer is used to control the filter cleaning
system.
The solid-state timer requires
a 105 to 135-Volt, customer-
supplied power supply.
Do not mount the solid-state timer directly
to the collector or the positive displacement
blower as mechanical vibration can damage
the timer.
1. Choose a location convenient for accessibility and
maintenance.
2. Using the wiring diagram supplied, wire the blower
motor, blower-motor starter, solid-state timer, and
solenoid valve. Use appropriate wire gauge for rated
amp load as specified by the local codes.
Timer Wiring
connected to
channel 1 as shown
Electrical installation, service
or maintenance work during
installation must be performed by a qualified
electrician and comply with all applicable
national and local codes.
Turn power off and lock out all power
before performing installation, service, or
maintenance work.
Do not install in classified hazardous
atmospheres without an enclosure rated for
the application.