Installation, Operation and Maintenance manual
20
PowerCore
®
Dust Collectors - Series CPV
Refer also to figure 7.
1. Turn off and isolate any air movement equipment associated with the process
(e.g. fan) and check clean air chamber is at atmospheric pressure.
2. Isolate controller and/or compressed air supply.
3. Open access door by releasing fasteners. Swing door fully open and engage
door locking mechanism.
4. Release filter pack retainer wing nuts and washers. Remove filter pack retainers.
5. Remove each filter pack by lifting straight up.
6. Place filter pack into a sealable bag and dispose of the filter pack properly.
If in doubt regarding the safe disposal of the used filter pack, consult your
local regulations.
A
B
Figure 6: Filter pack replacement (CPV-6F illustrated)
7. Clean surface around openings where filter packs are seated to ensure a good seal.
8. Insert new filter packs into place, ensuring seal (A) overlaps the six filter pack
locators (B).
9. Replace filter pack retainers, replace washers and tighten wing nuts so that each
filter pack seal is seated firmly.
10. Disengage access door locking mechanism, then close and fasten access door.
Fan assembly removal/replacement
Isolate electric power supply.
Refer also to figure 8.
1. Disconnect electrical cables from terminal box.
2. Remove fan section top panel.
3. Remove side access cover.
4. Remove fan assembly securing bolts from inside clean air chamber.
5. The fan assembly can now be removed using a suitable lifting arrangement.