Downflo Evolution, DFE 2-8 to 5-80
26
Magnehelic
®
Gauge
The Magnehelic is a differential pressure gauge used
to measure the pressure difference between the clean-
air and dirty-air plenums and provides a visual display
of filter change requirements. The high-pressure tap is
located in the dirty-air plenum and the low-pressure tap
is located in the clean-air plenum.
1. Choose a convenient, accessible location on or near
the collector for mounting that provides the best
visual advantage.
2. Plug the pressure ports on the back of the gauge
using two, 1/8-in NPT pipe plugs supplied. Install two,
1/8-in NPT male adapters supplied with the gauge
into the high- and low-pressure ports on the side of
the gauges.
3. Attach the mounting bracket using three, #6-32 x 1/4-
in screws supplied.
4. Mount the gauge and bracket assembly to the
supporting structure using two, self-drilling screws.
5. Thirty-five feet of plastic tubing is supplied and must
be cut in two sections. Connect one section of tubing
from the gauge’s high-pressure port to the pressure
fitting located in the dirty-air plenum. Connect
remaining tubing from the gauge’s low-pressure
port to the fitting in the clean-air plenum. Additional
tubing can be ordered from your representative.
6. Zero and maintain the gauge as directed in the
manufacturer’s Operating and Maintenance
Instructions provided.
Magnehelic Gauge Installation
clean-air plenum
pressure tap location
3/8-in flat washer
1/8-in NPT coupling
support structure
mounting surface
#6-32 x 1/4-in mounting screws
mounting bracket
static pressure tee
1/8-in NPT x 90° elbow
1/8-in NPT adapter
1/8-in NPT adapter
3/8-in flat washer
dirty-air plenum pressure tap location
1/8-in NPT adapter
1/8-in NPT x 90°
male elbow
two, self-drilling screws
two, 1/8-in NPT pipe plugs
plastic tubing
two, 1/8-in NPT
adapters
low-pressure port
high-pressure port
Magnehelic gauge
1/8-in NPT x 90° male elbow
Содержание DFE 2-4
Страница 42: ...A 1 Donaldson Company Inc Appendix A Clean Change Bag In Bag Out Filter and Liner System...
Страница 56: ...B 2 Donaldson Company Inc Service Notes Date Service Performed Notes...
Страница 57: ...Downflo Evolution DFE 2 8 to 5 80 B 3 Date Service Performed Notes...
Страница 58: ...B 4 Donaldson Company Inc Date Service Performed Notes Service Notes...