BIOCLASS iC DX
16
DHW CIRCUIT'S SETUP PARAMETERS
The
BioClass iC DX
boiler is equipped with an electronic controller to regulate a domestic hot water
production service. The following parameters are used to configure the ACS service related parameters.
These parameters will only be accessible in the "Technical Menu".
16.1
Legionella protection function (P.17)
This option prevents the proliferation of legionella bacteria in the DHW tank. Every 7 days the
temperature of tank hot water is increased to 70 ºC to kill the bacteria. This function is only active if
the boiler is turned on and a DHW tank is connected. By means of parameter
P.17
the protection
against Legionella bacteria function may be activate or deactivate. By default this function is set
deactivated.
16.2
DHW re-circulation function (P.20 = 2)
The multifunction of the auxiliary relay output allows to install a DHW re-circulating pump in DHW
hydraulic circuit, in order to increase the comfort of DHW service. To activate this function read
“Multifunction-Relay functions”
section.