CERTIFIED INSTALLATION
Certified installations require one roof vent and one
lower side vent.
For "Certified Vent System Kits" see page 15.
For further information contact your dealer or distributor.
METHODS OF INSTALLATION
The method of installation is shown in FIG. 9. It is
essential that all maximum or minimum dimensions are
strictly maintained as the performance of the refrigerator
is dependent on adequate flow of air over the rear of the
refrigerator.
NOTE: The upper vent should be centered over
the condenser at the back of the refrigerator.
VENTILATION HEIGHTS
Installation with roof
Minimum ventilation
vent and lower side vent
heights in
Refrigerator
Inches
mm
RM 1272
65
1651
CLEARANCES
Minimum clearances in inches to combustible materials
are:
G: Top
0
K:
Side
0
L:
Bottom 0
M: Rear
0
N:
See NOTE: Clearance "N" below.
NOTE: Clearance "M" is between the rearmost part of
the refrigerator and the wall behind the refrigerator.
NOTE: Clearance "N" is the distance between the bot-
tom of the lower vent to the roof material. For ventilation
height, see table VENTILATION HEIGHTS
See Figures 9, and 10.
Condenser
Ventilation
height
FIG. 9
FIG. 10
N
M
G
K
K
L
NOTE: Wood Strip
MUST be in place.
13-5/8"
28-5/8"
LOWER VENT CUTOUT
7