MCS T6, MCS T12, MCS T16
Programming
17
8.6
Restore Memorized Default Settings
The memorized default settings can be restored as follows.
➤
Enter the Program Mode.
➤
Set P-17 to “rSt”.
➤
Exit the Program Mode.
✓
The software version number (e.g. “A12”) appears in the display.
✓
The memorized default settings are restored and the Marine Climate System
returns to the Off Mode.
8.7
Programmable Parameters
Programmable Parameters Table
Program
number
Description
Default Range
P-1
Operating Mode
0
0
= Automatic mode
1
= Cool only mode
2
= Heat only mode
P-2
High Fan Speed Limit
(arbitrary units)
95
65 – 95
P-3
Low Fan Speed Limit
(arbitrary units)
55
30 – 64
P-4
Compressor Staging Time
Delay
15
5 – 135 s
P-5
Temperature Sensor
Calibration
Ambient
Temperature
Ambient 10 °F, –12,2 °C
P-6
Failsafe
3
0
= Minimum protection
1
= Continuous, no display
2
= Continuous, with display
3
= Four failures, reset required
P-7
Low AC Voltage Shut-
down (Volts)
115 V – OFF
220/230 V – OFF
75 – 105
175 – 205
P-8
De-Icing Cycle
1
OFF
1
= On with 5 °F, –15 °C faceplate
sensor differential
2
= On with 7 °F, –13,9 °C faceplate
sensor differential
MCS-6-12-16--O-West.book Seite 17 Dienstag, 14. November 2017 11:28 11