6

 PROGRAMMING & OPERATIONS

A. ON/OFF

To turn ON the CCC 2 thermostat when the back light is OFF, 

fi

 rst press any button 

to wake up the CCC 2 thermostat. Then press and release the 

ON/OFF

 button. The 

LCD will display the last programmed settings. To turn OFF the CCC 2 thermostat 
press the 

ON/OFF

 button and release. Only the time of day will display when the 

CCC 2 thermostat is in the OFF condition.

B. Clock Setting

Press the 

CLOCK

 button to initiate the clock setting sub-menu on the CCC 2 ther-

mostat. When in this menu, the 

hour

 digits will 

fl

 ash 

fi

 rst. The hour can be adjusted 

using the 

 or 

 buttons. Press the 

CLOCK

 button again and the 

minute

 digits will 

fl

 ash, allowing the minute setting to be adjusted using the 

 or 

 buttons. Press 

it a third time and the 

AM

 or 

PM

 icon will 

fl

 ash, allowing the AM or PM setting to be 

adjusted using the 

 or 

 buttons. Press it one more time to store the new time in 

memory and exit the clock setting sub-menu.

19

N. Power Interruption

In the event the power to the air conditioner or control is interrupted, the system will 
restart with the previous set points once power is restored.

O.  LCD Error Code

When the system determines that one of the faults listed below has occurred an er-
ror code will be displayed in the LCD for the zone in which the error occurred. During 
normal operation, a blinking zone number indicates a fault has occurred. The error 
code is displayed in place of the temperature set-point.
Error Code:
E1 Loss of communication between the CCC 2 thermostat and all system power 

module boards. System will shut down.

E1  Loss of communication between the CCC 2 thermostat and an individual system 

power module board. The LED will display error code “E1” and the zone number 
that lost communication. Any additional zones that loose communication will 
blink in addition to the current zone.

E2  Open circuit or out-of-range indoor temperature sensor. All heat, cool, and dehu-

midify operations will be locked out. Manual fan operation will continue.

E3 Shorted Indoor Temperature Sensor. All heat, cool, and dehumidify operation 

will be locked out. Manual fan operation will continue.

E4  Open circuit or out of range Outdoor Temperature Sensor (select models). Heat 

pump and dehumidi

fi

 cation operation will be locked out. Air conditioner, furnace, 

heat strip, and fan operation can continue to operate. 

E5  Open circuit or out-of-range freeze sensor. Air conditioner and dehumidi

fi

 cation 

operation will be locked out. Heat pump, furnace, heat strip, and fan operation 
can continue to operate but displays the last temperature set-point. 

E6  Open circuit humidity sensor (Select Models). Air conditioner and dehumidi

fi

 ca-

tion will be locked out. Heat pump, furnace, heat strip, and fan can continue to 
operate.

E7  Loss of 120 Vac power to all power module boards on the system. The system 

will shut down. 

E8  Invalid zone con

fi

 guration. The heat pump and heat strip DIP switches are both 

set to the ON position in one zone. Heat pump, heat strip, air conditioner, and 
dehumidify operation will be locked out in the affected zone.

E9 Invalid zone con

fi

 guration.  The  dehumidi

fi

 er DIP switch and either the heat 

pump or heat strip DIP switches are set to the ON position in one zone. Heat 
pump, heat strip, air conditioner, and dehumidify operation will be locked out in 
the affected zone.

SPECIAL FEATURES

Содержание 3314080 Series

Страница 1: ...N N3T 5L8 CANADA 519 720 9578 For Service Center Assistance Call 800 544 4881 COMFORT CONTROL CENTER 2 THERMOSTAT OPERATING INSTRUCTIONS REVISION Form No 3314149 018 10 11 Replaces 3314149 000 French 3314169 016 2011 Dometic LLC LaGrange IN 46761 PROGRAMMABLE THERMOSTAT MODEL 3314081 XXX WITH DEHUMIDIFY 3314080 XXX WITH OUT DEHUMIDIFY ...

Страница 2: ... 13 B Zone Control 13 C Dehumidify Select Models 13 D Program 1 2 14 E Examples Of Times Programmed 16 F CANbus Interface 16 G Auxiliary Heat Heat Pump Models Only 17 H Stage Select Two Air Conditioner Heat Pump Units Select Models On One Zone 17 I Stage Select Dual Compressor Air Conditioner Heat Pump Select Models 17 J Auto Generator Start AGS 18 K Load Shed 18 L Defrost Cycle Heat Pump Models O...

Страница 3: ...tat review the following diagrams and accompanying text that explain the functional characteris tics of this system Your CCC 2 thermostat is equipped with a liquid crystal display LCD that identifies the mode of operation OFF Cool Heat Pump Fan Heat Strip Auto Furnace or Aqua temperature set point zone identification 1 2 3 4 fan speed Auto Low Med High program 1 and 2 inside temperature clock F C ...

Страница 4: ... or replacement of the air conditioner heat pump air fil ters is required NEVER run the air conditioner without the air filter in place This may plug the unit evaporator coil with dirt and may substantially degrade the perfor mance of the unit over time When a system fan run time exceeds 1000 hours the filter icon is displayed in the LCD See section D Quick Reference To LCD Icons on page 5 When th...

Страница 5: ...art on the expected high outdoor ambient will greatly improve its ability to maintain the desired indoor temperature For a more permanent solution to high heat gain accessories like Dometic outdoor patio and window awnings will reduce heat gain by removing the direct sun They also add a nice area to enjoy company during the cool of the evening B Disclaimer The manufacturer of this air conditioner ...

Страница 6: ...shut down E1 Loss of communication between the CCC 2 thermostat and an individual system power module board The LED will display error code E1 and the zone number that lost communication Any additional zones that loose communication will blink in addition to the current zone E2 Open circuit or out of range indoor temperature sensor All heat cool and dehu midify operations will be locked out Manual...

Страница 7: ...ontacts or an off board relay from the RV power management system When the Load Shed signal is detected the compres sor shall turn OFF L Defrost Cycle Heat Pump Models Only To avoid frost formation on the outside coil and to obtain maximum performance when the outside temperature is less than 42 F 6 C and greater than 30 F 1 C a defrost cycle will be initiated While operating in this temperature r...

Страница 8: ...signated secondary the power module board DIP switch identified as Ext Stage must be set to the ON position in order to configure the power module board for the on demand secondary stage operation in this example Zone 2 and Ext Stage DIP switches are in the ON position In this stage configuration the CCC 2 thermostat temperature set point will be used for both the primary and the secondary stage a...

Страница 9: ... will be Auto LOW MED and HIGH The fan will run continuously during LOW MED and HIGH fan settings The fan will cycle ON and OFF with the thermostat on AUTO setting For more information on auto fan see section A Auto Fan on page 13 H Temperature Set Point Press the or button to change the temperature set point The temperature set point is indicated by 2 digits on the LCD Press the button to increas...

Страница 10: ... on the room air temperature and the temperature set point on the CCC 2 thermostat When the system calls for cooling there will be a delay of approximately 2 minutes During this delay the hour glass icon will be displayed in the LCD In auto fan the fan will turn ON first followed by the compressor in approximately 15 seconds In this mode there are 4 fan speed selections LOW The fan operates contin...

Страница 11: ...n immediately SPECIAL FEATURES 11 HIGH The fan operates continuously at high speed The compressor cycles ON and OFF AUTO When auto fan is selected the fan speed will vary depending on the differ ence between the temperature set point and the room temperature In auto fan the compressor and the fan will cycle ON and OFF with the thermostat The compressor shuts OFF first followed by the fan in approx...

Страница 12: ...he priority for selecting the heat source will be heat pump first furnace second and heat strip third MODE DESCRIPTION 13 SPECIAL FEATURES A Auto Fan When AUTO fan is selected the fan speed will vary depending on the difference between the temperature set point and the room temperature In AUTO fan the compressor and fan will cycle ON and OFF with the thermostat When the difference is 8 F C or more...

Отзывы: