4
Once the system is completely installed, do a system reset:
1. Make sure the CCC 2 thermostat is in the OFF mode. See section, “C. Quick
Reference To Control Buttons” on page (5).
2. Simultaneously press and hold the
MODE
and
ZONE
buttons. See section, “C.
Quick Reference To Control Buttons” on page (5).
3. The LCD will display “IniT” and all available zones.
4. Release
the
MODE
and
ZONE
buttons.
5. Press
the
ON/OFF
button to exit system set up.
6. The furnace ON/OFF temperature differential should be set at this time. For
further information on furnace mode differential setting, see section, “F. “FURN”
/ “AQUA” - Furnace Or Aqua (Hydronic) Heating Mode” on page (12).
Any time a system reset occurs, the factory default settings are restored. See table,
“Factory Preset Settings” on page (4).
In the unlikely event of CCC 2 system memory loss or dip switch setting change, the
CCC 2 thermostat will require a system reset. For system reset procedure, see main
heading, “System Reset Procedure” on page (20).
Your Dometic CCC 2 thermostat has been pre-programmed. Review settings below
and adjust the settings to your personal comfort level.
Any time the CCC 2 is in an idle stage (not illuminated) you will need to wake it
up by pressing any button on the CCC 2 before it will recognize a new setting
attempt.
Factory Preset Settings
Factory Preset Settings Each Zone
All Zones
Program “1”
Function
Setting
Function
Setting
Time of Day (Clock)
— — —
Heating
68 °F / 20 °C
Each Zone
Cooling
72 °F / 22 °C
Relative Humidity
50%
Automatic
70 °F / 21 °C
Heating
68 °F / 20 °C
Fan Speed
Auto
Cooling
72 °F / 22 °C
Mode
Off
Automatic
70 °F / 21 °C
Time
8:00 AM
Fan Speed
Auto
Program “2”
Mode
Off
Heating
68 °F / 20 °C
Humidity (select models)
Off
Cooling
72 °F / 22 °C
Automatic
70 °F / 21 °C
Fan Speed
Auto
Mode
Off
Time
10:00 PM
ABOUT YOUR NEW THERMOSTAT
21
MAINTENANCE
A. Air Filter
NOTICE.
Periodic cleaning or replacement of the air conditioner/heat pump air
fi
l-
ters is required.
NEVER
run the air conditioner without the air
fi
lter in place. This
may plug the unit evaporator coil with dirt and may substantially degrade the perfor-
mance of the unit over time.
When a system fan run time exceeds 1000 hours the
fi
lter icon is displayed in the
LCD. (See section, “D. Quick Reference To LCD Icons” on page (5).) When this
occurs wash the
fi
lter with soap and warm water. Let dry and reinstall.
To reset the fan run time and clear the
fi
lter icon, hold the
INSIDE TEMP
and
°F / °C
buttons for 3 seconds. This will clear the fan run time for the current zone
selected.
B. Dometic CCC 2 Thermostat
NOTICE. DO NOT
spray water directly on the CCC 2 thermostat.
DO NOT
use
solvents for cleaning.
Clean the CCC 2 thermostat with a moist soft cloth.
SERVICE
In the unlikely event the unit fails to operate or operates improperly, check the fol-
lowing before calling your service center.
●
If your RV is connected to a motor generator, check to be sure the motor genera-
tor is running and producing power.
●
If the RV is connected to a power supply by a land line, check to be sure the line is
sized properly to run air conditioner load and it is plugged into the power supply.
●
Check your 120 Vac fuse or circuit breaker to see if it is open. Insure fuse is not
burnt, or circuit breaker is ”ON” and not activated.
●
Check your 12 Vdc fuse or circuit breaker to see if it is open.
●
After the above checks, call your local service center for further help. This unit
must be serviced by quali
fi
ed service personnel only.
When calling for service, always give the following:
●
Unit Model Number and Serial Number found on Identi
fi
cation Label located on
the Base Pan of unit bottom. It is necessary to remove the return air cover to
expose the rating plate.
●
Electronic Control Kit Part Number and Serial Number found on Identi
fi
cation
Label located on the side of the Kit. This kit is mounted in the return air cavity and
can be exposed by removing the return air cover.